Military Engineer Services Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Costs
EMD
₹ 97,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_681999_1Bid Award Id
ViewTender No
CWE(U)/D-18/2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Material & Labour for transportation of transformer of capacity upto 400 KVA from MES Yard to site location using Hydra/Crane and truck as per requirement to replace defective transformer including installation, testing and connecting at site and to deposit the same to MES Yard after receipt and installation of repaired transformer at site complete all as specified and directed.
Note:- Contractor must arrange for transportation and installation for replacement of transformer at site immediately after receipt of verbal/telephonic/written complaint from JE/Engr-in-Charge within 1 day. Any delay beyond 1 day post receipt of complaint shall be penalized @ Rs 2500/- per day and shall be recovered from next due RAR.
3
-
-
... More
Material & Labour for alternative arrangement by hiring, transportation of transformer of capacity 500/630 KVA in place of unserviceable transformer on hire basis for 15 days including, installation, connecting and testing of transformer and return back after installation of repaired transformer complete all as specified and directed.
Notes:-
(i) Contractor must arrange hired transformer including transportation and installation at site immediately after receipt of verbal/telephonic/written complaint from JE/Engr-in-Charge within 1 day. Any delay beyond 1 day post receipt of complaint shall be penalized @ Rs 3500/- per day and shall be recovered from next due RAR.
2
-
-
... More
(ii) Repairing of transformer must be completed within 15 days after receipt of verbal/ telephonic/written complaint from JE/Engr-in-Charge. In case of any delay, no extra claim will be entertained towards hiring charges beyond 15 days and the contractor shall not be allowed to shift the hired transformer until replaced by repaired transformer. In case of any kind of fault/defect occurred in hired transformer, the contractor shall have to arrange further replacement without any additional cost and shall repair the defect from his own expenses.
(iii) Contractor should check the available infrastructure and to be sure regarding safety of hired transformer before installation. The rate quoted is deemed to be including transportation cost, earthing lead etc.
-
-
-
... More
Taking out the unserviceable copper winding from transformer of capacity upto 250 KVA after opening top cover, and carrying out the following work complete all as specified and directed :- (a) Dismantling of all attachment viz breather assembly, conservator, oil temperature gauge, HT/LT bushing etc. and keeping aside for reuse..
(b) Taking out the core with winding assembly.
(c) Removing of complete winding from core and dismantling the core, cleaning of core laminate sheet and keeping aside for reuse
(d) Cleaning of complete transformer tank oil fins, removing of sludge, and making the inside surface of tank dry by blowing of hot air as directed and specified.
(e) Painting of outside surfaces of transformer complete by means of spray machine as directed.
3
-
-
... More
All as per item No 6 here-in -before but capacity of transformer 315 to 630 KVA.
3
-
-
... More
Note for Item No 6 & 7 : - In case the defective transformer not repaired & installed at site within the specified period of 15 days from the date of handing over of defective transformer/complaint to contractor, a penalty recovery @ Rs 2500/- per day will be charged from his dues.
-
-
-
... More
(a) Repairs to the transformer of capacity upto 250 KVA as follows:-
(i) Rewinding of HT/LT leg coil complete using copper wire/strip of appropriate gauge, size and turn as per existing with double paper coated insulation including all requisite insulating materials like packing sleeves, separator, tapes etc. heating, varnishing the core and winding assembly after framing up top and bottom steel structure of transformer all as specified and directed. (ii) Replacement of all insulating materials other than incorporated for rewinding of HT/LT coils as per existing.
(iii) Fixing only HT procelain bushing with studs, nuts, washers 3 Nos. and LT procelain bushing with studs, nuts, and washers 4 Nos. and connection with primary and secondary windings and reconnecting with the main terminals as required and directed. (iv) Fixing only breather assembly, conservator, oil temperature gauge after proper cleaning, minor repairs etc. as required and directed.
(v) Replacement of all unserviceable gasket from top cover, HT/LT bushing with new one by using rubberised gasket sheet 4.0mm/6.0mm thick duly pasted with suitable adhesive
3
-
-
... More
(vi) Replacement of unserviceable bolts with new one and fixing of existing serviceable bolts, nuts, washers of different sizes and tightening properly.
(vii) Repositioning of core and winding assembly inside the tank, assembling complete unit and making the transformer ready for filling oil and subsequent testing as directed. (viii) Filling/topping up of new transformer oil of required quantities .
(b) Material & Labour for transportation of repaired transformer to the original position (from where taken-down), disconnecting the alternative transformer, taking down the same, Re-installation of repaired indoor/outdoor transformer on 4/6 pole structure/ plinth/inside sub station, connecting electrically and mechanically, testing and commissioning complete all as specified and directed. Note :- HT/LT leg coils copper wire/strip and transformer oil required shall be measured and paid separately under relevant items of this Schedule here-in-after as supply only.
-
-
-
... More
All as per item No 8 here-in -before but capacity of transformer 315 to 630 KVA.
2
-
-
... More
Supply only HT coils with super enamelled copper wire /DPC of high quality duly matching with the existing guage and impedance.
400
-
-
... More
Supply only LT coils with super enamelled copper wire strip/DPC of high quality duly matching with the existing guage and impedance.
400
-
-
... More
Material & Labour for ON load Centrifuging and dehydration including filteration and cleaning of transformer oil by dehydration machine of 11/0.433 KV transformer installed at various site on plinth/4/6 pole structure of any capacity and topping up deficient transformer oil including testing of samples before and after dehydration and filteration complete all as specified and directed.
Note :- Deficient quantity of Transformer oil required for top up shall be measured and paid separately under item No 13 here-in -after as supply only.
10000
-
-
... More
Supply only transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5mm gap for filling in transformer or for topping up as required and directed
2500
-
-
... More
Supplying and fixing in replacement, Porcelain Transformer bushing on LT (440 Volt) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 160 KVA and re-connecting electrically and mechanically, testing complete all as specified and directed. Note.The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and provision of pad type bus bar almuminium of approppiate size /capacities of transformers with nut bolt & washers.
12
-
-
... More
All as per Serial item No 14 here-in-before but capacity 200 KVA to 315 KVA
12
-
-
... More
All as per Serial item No 14 here-in-before but capacity 400 KVA to 630 KVA
12
-
-
... More
Supplying and fixing in replacement, Porcelain Transformer bushing on HT (11 KV) side, including brass stems conical bush and gasket after disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 160 KVA and connecting electrically and mechanically, testing complete all as specified and directed. Note. The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers and connections.
9
-
-
... More
All as per Serial item No 17 here-in-before but 200 KVA to 315 KVA
9
-
-
... More
All as per Serial item No 17 here-in-before but 400 KVA to 630 KVA
9
-
-
... More
Supplying and fixing in replacement, all unserviceable gasket after disconnecting electrically and mechanically for indoor/outdoor transformer of capacity upto 160 KVA and re-connecting electrically and mechanically, testing complete all as specified and directed. Note. The rates quoted is deemed to be included the cost of necessary labour charges for draining out & re-filling transforer oil, opening of top cover by unscrewing nut, bolts washers etc.
3
-
-
... More
All as per Serial item No 20 here-in-before but 200 KVA to 315 KVA
3
-
-
... More
All as per Serial item No 20 here-in-before but 400 KVA to 630 KVA
3
-
-
... More
Supplying and fixing in replacement, Silica Gel Breather assembly including vent pipe and Silica Gel for indoor/outdoor transformers, capacity upto 160 KVA complete all as specified and directed.
3
-
-
... More
All as per Serial item No 23 here-in-before but capacity 200 KVA to 315 KVA
3
-
-
... More
All as per Serial item No 23 here-in-before but capacity 400 KVA to 630 KVA
3
-
-
... More
Supply and fixing Thermometer of transformer upto capacity 630 KVA complete all as specified and directed.
3
-
-
... More
Material & Labour for painting of transformer installed on plinth/4/6 pole structures at various site of capacity 100 to 630 KVA with existing colour, with spraying machine, after cleaning, preparation of outer surface of transformer, including writing of SM No, MES and capacity of transformer complete all as specified and directed.
40
-
-
... More
Earthing complete in replacement with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 3.5 m below normal ground level) with top edge of earth plate not less than 2.5m below normal ground level, connected to galvanized iron strip 32X6 mm by means of electric arc welding of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other side complete all as specified, including testing and commissioning complete all as directed.
Note : - (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe light grade etc.
(b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI earthing and protection pipe upto 7.5 meter beyond the earth plates electrode.
10
-
-
... More
Disconnecting electrically & mechanically outdoor transforemrs upto 630 KVA capacity, lowering down/getting out from plinth carefully for repairing /making of plinth of transformer and re- connecting electrically and mechanically after repairing/making of plinth , testing and commissioning complete all as specified and directed.
Note:- (a) Rate is deemed to be inclusive for hydra , men power, and other items required for temp energization of transformer.
(b) Material & Labour used to repair the Plinth shall be measured and paid separetely under items of sch of work here-in -after.
4
-
-
... More
Supply & Fixing in replacement 100 mm bore GI Pipe light grade with necessary accessories/ fittings for cable protections complete all as directed at site.
30
-
-
... More
Supply & Fixing in replacement MS angle iron, flat,Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed .
3
-
-
... More
Supply & Fixing in replacement 3.15mm dia MS wire 75x75mm mesh , made up into mattress or cages appx 2.00 mtr height and fixed with flate iron /angle by welding in position complete all as specified and directed .
12
-
-
... More
Supply and fill in replacement silica gel in breather of transformer complete all as directed.
10
-
-
... More
Material & Labour in replacement 32x6mm galvanised iron strip for earth continuity conductor for earthing of transformer , GOD , 4/6 pole , structure etc complete all as specified and directed.
20
-
-
... More
Material and labour for servicing/testing of breaker/control panel including CT, PT and relays in control panel of VCB of capacity 1250/800/630 Amps and rating 11 KV complete as details mentioned as under:-
(a) Details of servicing of breaker :-
(i) Adjustment of mechanism if required.
(ii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and insulating materials shall be wiped with a clean cloth.
(iii) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(iv) Check for rust and wear.
(v) Check Spring Tension and pitting of the Cluster Contacts.
(vi) Visual check for rust and deformation.
(vii) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(viii) Check for loosened connections, rust, damaged lead wires.
(ix) Check whether the contacts are damaged by arcing.
40
-
-
... More
(x) Checking of control circuit & tighten the connections if any.
(xi) Check close & trip coil.
(xii) Checking of Jaw Contacts Conditions and repair/adjust.
(xiii) Replace the jaw contacts,If required.
(xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish.
(xv) Replacement of Dashpot/shock absorbers .
(xvi) Replacement of carbon brush of spring charging motor
(b) The following test shall be carried out:-
(i) Primary Injection Test of CT / PT
(ii) Closing & Opening Timing Test for all three poles.
(iii) IR Test with megger in open and closed condition.
(iv) Contact resistance test for all three poles
(v) Closing coil resistance
(vi) Tripping coil resistance.
(c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay:-
(i) Over current and earth fault relay
(d) Testing of followig Aux relay
(i) DC Supply supervision relay.
(ii) Master trip relay
-
-
-
... More
Supplying ,fixing & testing in replacement master trip relay , 50/24 Volt DC in control panel including wiring complete as directed at site
12
-
-
... More
Supplying ,fixing & testing in replacement Trip circuit supervision relay , 50/24 Volt DC in control panel including wiring complete all as specified and directed.
8
-
-
... More
Supplying ,fixing & testing in replacement DC supervision relay relay , 50/24 Volt DC in control panel including wiring complete all as specified and directed.
8
-
-
... More
Supplying ,fixing , testing of SF 6 gas pressure supervision relay , 50/24 Volt DC in control panel including wiring complete all as specified and directed.
10
-
-
... More
Supply, installation and testing in replacement Numerical Relay draw out type in HT 11 KV VCB Panel comprising of new and modern numerical scheme for detecting, indicating and tripping the breaker on faults over-current and earth-fault in any of the three phases, Trip circuit supervision relay, 5% pick up for OC and 5% for EF. The relay shall also have the following features as minimum; (i) Programmable rated current 1A & 5A, (ii) Last 8 fault record & 200 event record with time stamping, (iii) 4 analog CT & 3 PT input, 8 DI & 8 DO, (iv) Communicable on IEC61850 protocol, (v) Disturbance recording upto 300 cycles, (vi) Self supervision function.
5
-
-
... More
The relay shall be fully integrated with the feeder, internally capturing feeder statuses if available including Breaker On, Off, Spring Chrgd, Test, Service, AC-Fail, Trip circuit healthy relay, PT supervision, inter panel tripping, Master trip relay, local remote and display the same locally on a built-in LCD screen and suitably labeled status LEDs. Relay shall have facility to locally Trip/Close the breaker as a backup to TNC switch provided separately on the panel. The relay shall be fixed on new 2mm CRCA sheet of matching existing VCB panel color and suitable size covering all blank space formed by removing old mechanical type IDMT relay complete including associated wiring and integration with existing HT VCB panel complete all as specified and directed.,
-
-
-
... More
Material and labour in replacement Retro Reflective installation sign boards of size 5 feet x 4 feet fabricated out of 16 gauge MS sheet frame duly welded/riveted with MS square pipe of size 25mm x25mm at height 2.00 meter above ground level on stainless steel heavy duty pipe of size 50mm bore embaded 60 CM in PCC 1:2:4 type B 1 block of size 45cmx45cmx60cm including necessary excavation and earth work.The steel portion of the board shall be painted in stove enameled paint and the front & back of the frame shall be overall sheathed with blue colour base painter adhesive tape. The wiriting matter will be in English language on both sides with reflective adhesive painter tapes complete all as pecified and directed.
6
-
-
... More
Supply installation & commissioning in replacement of 24V/40A Float Cum Boost Battery Charger unit including battery bank comprising 02 Nos of 12 Volts-100 AH sealed maintenance free battery. The CCCV battery charger consisting of copper wound, air cooled transformer, 01 Set single phase full wave bridge rectifier consisting of diodes and SCRs, liberally rated mounted on heat sink and complete with resistor/condenser network for surge supperssion. During auto float mode automatic changeover shall take place from float mode to boost mode and vice versa, 01 Set of solid state constant potential controller to stabilize the DC output voltage of the float cum boost charger, 01 No electronic controller, DC digital ammeter, DC digital voltmeter, Potentiometer, DC, MCB for reverse battery protection. The charger should have alarm annunciation with visual and audible alarm with manual reset facility for fuse fail alarm. Float cum boost battery charger and DC distribution board shall be housed in powder coated sheet steel cubicle with panels of 1.6mm thickness, louvers for ventilation, gland plate will be provided for cable entry from bottom. The battery charger shall be divided into two compartments. The upper compartment shall house the battery charger & DCDB with all necessary controls. The lower compartment shall be suitable for housing the batteries. Tech specification shall be as under:-
2
-
-
... More
(a) Input working voltage-180 -270 Volts (b) Nominal Input Voltage - 230 V , AC , 50 Hz,1
(c) On load input power factor - 0.8
(d) On load unit watt efficiencies- 80% (e) No load losses of complete charge- 10% (f) Ripple contents on the load (RMS)= 1% to 5% (g) Over load - 110% for 30 minutes and will give visual indication for over load condition. (h) Boost charging - 2.4 V/Cell .
(j) Float charging -2.15 V/Cell
(k) Float cum boost charging-Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode.
(l) Reverse polarity -No damage will caused . A visual indication for reverse polarity will appear with an audio alarm.
(m) Short circuit-MCB protecton provided.
-
-
-
... More
Material and labour for Preparation of old painted surfaces of steel by brushing/cleaning stain, greasy spots with thinner, applying two coats of synthetic enamel paint by spray machine on all sides of 11 KV VCB panel including writing of MES /SM No and details of feeder as directed by Engr-in-charge on graphic plastic sheet complete all as directed .
20
-
-
... More
Disconnecting HT supply from 11 KV , 630 Amps RMU , 5/4 way and servicing and overhauling of RMU , checking of tripping mechanism , greasing of moving contacts , cleaning of carbon from main contacts , checking of spring tension ,Checking of loosened bolts and nuts, checking of loosened connections, rust, damaged lead wires, checking of spring charging motor , Improvement of resistance of CTs , PT, epoxy insulator and epoxy body by applying post heated varnish complete all as directed and testing on load
6
-
-
... More
Material and labour for checking the existing pressure of SF6 Gas in Gas Chamber of 11 KV , 630 Amps RMU , 5/4 way before filling and topping up the SF6 gas in the chamber of RMU including supervision of gas filling/topping up process and checking the pressure of gas after filling complete all as directed at site.
8
-
-
... More
Supplying and fixing in replacement operating mechanism (2PA Mechanism W/O hex Rod) for 11 KV , 630 Amps RMU , 5/4 way complete all as specified and directed at site by Engr-in -charge
2
-
-
... More
Supply and fixing in replacement cable Boots 11 KV, in 630 Amps RMU, 5/4 way complete all as specified and directed.
6
-
-
... More
Supplying and fixing in replacement associated ring-core cast-resin insulated CTs 100/50/1 -1 Amp , 2.5 VA, 10P10 for protection in 11 KV, 630 Amps RMU complete all as specified and directed.
2
-
-
... More
Supplying and fixing in replacement associated ring-core cast-resin insulated CTs 60/30/1-1Amp , 2.5 VA, 10P10 for protection in 11 KV, 630 Amps RMU complete all as specified and directed.
2
-
-
... More
Supplying and fixing in replacement 1-Ph (11kV/rt3):110 VAC, 50VA Potential transformer in 11 KV, 630 Amps RMU (Ring main unit) complete all as specified and directed.
2
-
-
... More
Supply and fixing in replacement 1-Ph (11kV/rt3):110VAC, 500VA Auxiliary transformer in 11 KV, 630 Amps RMU (Ring main unit) complete all as specified and directed.
2
-
-
... More
Suplying and laying as replacement in sub station fixing 3.3 to 11 KV electrical insulation mat of size 5 mtr x 1 mtr x 2.5 mm thick specification as per IS 15652 2006 complete all as specified and directed.
5
-
-
... More
Supply and fixing Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
-
-
-
... More
95 Sqmm 3 core.
2
-
-
... More
120 Sqmm to 185 Sqmm, 3 core.
2
-
-
... More
240 Sqmm to 300 Sqmm, 3 core.
2
-
-
... More
Supply and fixing Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-
-
-
-
... More
95 Sqmm 3 core.
2
-
-
... More
120 Sqmm to 185 Sqmm, 3 core.
2
-
-
... More
Supplying, installation, commissioning and testing of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 400/200/5-5 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering and associated wiring including taking down old UNSV CTs complete all as specified and directed
2
-
-
... More
All as per item No 55 here-in-before but having ratio 200/100/5-5
3
-
-
... More
All as per item No 55 here-in-before but having ratio 150/75/5-5
3
-
-
... More
All as per item No 55 here-in-before but having ratio 100/50/5-5
3
-
-
... More
All as per item No 55 here-in-before but having ratio 60/30/5-5
3
-
-
... More
All as per item No 55 here-in-before but having ratio 50/25/5-5
3
-
-
... More
Supplying and fixing Potential Transformers, Draw-out type in existing HV panel for easy maintenance, 11kV/rt3:110V/rt3, 50VA, Cl.0.5 with associated gun-type HRC fuses and MCBs for HT/LT isolation including taking down old UNSV PTs complete all as specified and directed
3
-
-
... More
Supplying, installation, commissioning and testing of PT unit three phase, three limbs, upto 11 KV draw-out type, resin cast dry type, single ratio having primary voltage 11 KV & secondary voltage 110 volts, 50 VA class-1 including necessary bus bar connections & wiring for metering including taking down old UNSV PTs complete all as specified and directed
3
-
-
... More
Supply & Fixing LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etc for 11 KV control panel and associated wiring, if reqd, including taking down old UNSV LED indication complete all as specified and directed
20
-
-
... More
Supply and installation Anti-condensation space-heater withThermostatic control in cable and circuit breaker compartments of HT switchgears including taking down old UNSV heater complete all as specified and directed
12
-
-
... More
Supply & Fixing of vacuum interrupter suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV vacuum interrupter complete all as specified and directed
3
-
-
... More
Supply & Fixing of isolating contact assembly suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV contact assembly complete all as specified and directed
3
-
-
... More
Supply & Fixing of fixed contact block complete suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV contact block complete all as specified and directed
3
-
-
... More
Supply & Fixing of moving contact block complete suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV moving contact block complete all as specified and directed
3
-
-
... More
Supply & Fixing of motor & gear assembly 230V AC suitable for 400/630/800 amps, 11 KV HT VCB, testing & puting on load including taking down old UNSV motoer gear assembly complete all as specified and directed
3
-
-
... More
Supply & Fixing of spring gear suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV spring bearing gear complete all as specified and directed
3
-
-
... More
Supply & Fixing of closing coil assembly 24 volts DC suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV closing coil complete all as specified and directed
12
-
-
... More
Supply & Fixing of tripping coil assembly 24 volts DC suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV tripping coil complete all as specified and directed
12
-
-
... More
Supply and fixing close/trip coil 24V DC for 11 KV HT VCB of capacity 400/630/800 Amps capacity including taking down old UNSV close/trip coil complete all as specified and directed
12
-
-
... More
Supply & Fixing of panel door lock suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV panel ddor lock complete all as specified and directed.
12
-
-
... More
Supplying & Fixing auxillary switch (7 No + 7NC) suitable for 400/630/800 amps, 11 KV HT VCB including taking down old UNSV auxillary contact complete all as specified and directed
12
-
-
... More
Supply and fixing T&C Switch for Breaker ON/OFF purpose in HT 11 KV VCB panel including associated wiring, if reqd, for proper functioning of switch including taking down old UNSV T& C switch complete all as specified and directed
10
-
-
... More
Supply & Fixing Caution plate “CAUTION MEN AT WORK of size 40cmx15cm made out of white acrylic sheet with Red coloured glow tape including taking down old UNSV caution plate complete all as specified and directed
50
-
-
... More
Supply & Fixing of HRC fuse of capacity 20 Amps for VCB including taking down old UNSV PTs including taking down old UNSV HRC fuse complete all as specified and directed
50
-
-
... More
Supply & Fixing of MCB 20 to 32 Amps DP including taking down old UNSV MCBs complete all as specified and directed
18
-
-
... More
Supply & Fixing of Digital Amp meter (CT secondary site selectable 5A) for 11 KV VCB Control Panel including taking down old UNSV meter complete all as specified and directed.
12
-
-
... More
Supply & Fixing of Digital Volt meter Secondary voltage 110 V for 11 KV VCB Control Panel including taking down old UNSV meter complete all as specified and directed.
12
-
-
... More
Supply & Fixing and installation battery 12 volts,100 AH, dry type in replacement of old unserviceable battery in battery charger with suitable size of new copper battery terminal and lugs and initialy charging, commissioning and testing complete including taking down old UNSV battery complete all as specified and directed.
4
-
-
... More
Supply and fixing in replacement of feeder Protection relay for overcurrent and earth fault relay of 11 KV VCB HT Panel complete all as specified and directed.
2
-
-
... More
Supply and fixi ng in replacement of Electronic Trivector meter, 3 phase 4 wire suitable for 11 KV VCB HT Panel compllete all as specified and directed.
1
-
-
... More
Material & Labour for cutting and removing grass, vegetation bushes etc from surrounding of transformer,4 pole/6 pole,Lt panels, sub stn surrounding area, in and outside area of HT/LT Sub stn and removing all rubbish to a distance not exceeding 50m complete all as specified and directed.
1000
-
-
... More
Removing the waste building materials at our substation, such as rock, sand, bricks, tiles and mud need to be loaded onto a vehicle and disposed of at a location outside.Its the contractor responsibility to arrange for the disposal site etc complete all as specified and directed.
20
-
-
... More
Material and labour for spreading if stone aggregate of normal size not more than 25mm under 4/6 pole HT structure/surrounding area of outdoor RMU manually without damaging any equipments , cable or parts , spreading & levelling of finished gravel uniformly in layers n. ecc. 15cm thick watered and rammed to true surface all as specified and directed
20
-
-
... More
Labour only for Applying two coats of synthetic enamel paint over steel,wire mesh and iron surfaces old painted surfaces of any description and clamps, bolts above GL exceeding 10cm width or girth complete all as specified.
410
-
-
... More
Material & Labour for re-painting of LT Steel tubular poles of any sizes with apply of 2 coats of aluminium paint including rubbing with wire brush/emery paper & writing pole Nos in appropriate size of letters including making yellow and black strips upto height of 1.5 mtr above from ground level complete all as specified and directed.
450
-
-
... More
Material & Labour for re-painting of LT Panels/feeder pillars of approx size 2 to 4 Sqm with 2 coats of super enamal paint over a coat of red-oxide with sparygun including writing of feeder pillar numbers in appropriate size of letters complete all as specified and directed.
20
-
-
... More
Supply, laying, jointing, testing and commissioning in replacment of LT underground cables 1100 volts grade, PVC insulated XLPE and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-1554 marked, laid in trenches complete all as specified and directed. Cables of the following sizes:-
Note Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately.
-
-
-
... More
16 Sqmm 4 core
900
-
-
... More
25 Sqmm 4 core
900
-
-
... More
35 Sq mm 3.5 core.
600
-
-
... More
50 Sq mm 3.5 core.
600
-
-
... More
Supplying, laying, jointing testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed of following sizes :-
-
-
-
... More
95 sqmm 3 core.
250
-
-
... More
120 sqmm 3 core.
200
-
-
... More
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft/loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level complete all as specified and directed.
502.2
-
-
... More
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick complete all as specified and directed.
295.35
-
-
... More
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified and directed.
206.85
-
-
... More
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, ccomplete all as specified and directed.
Note : Measurement shall be taken after punning down.
136.08
-
-
... More
Supply & Fixing sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as specified and directed.
4752
-
-
... More
All as per srl item No 97 here-in-before but using old bricks obtained under srl item No 93 here in before.
7128
-
-
... More
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm complete all as specified and directed.
864
-
-
... More
All as per srl item No 99 here-in-before but using old un-reinforced precast concrete cable cove obtained under srl item No 01 here in before.
1296
-
-
... More
Boring of hole under road , pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine suitable for HDPE pipe of 150mm dia complete all as specified and directed
145
-
-
... More
Supply and fixing LED lights fitting 1x 40W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete.
100
-
-
... More
Supply & Fixing service connection with PVC insulated and PVC sheathed flat twin core cable 1100V grade heavy duty electric cable served all PVC sheathed in service connections suspendedsuspension wire and loop insulators and as directed of size 06 Sqmm cross sectional area stranded aluminium conductor.
1040
-
-
... More
Material & Labour for PCC (1:3:6) type C-2 (using 40 mm graded stone aggregate as in floors or paving 50mm thick and finished even and fair with out using extra cement all as specified
800
-
-
... More
Preparation of new/old plastered surfaces of all and applying two coat of cement base paint including priming surface with chalk whiting complete all as spd
200
-
-
... More
(xi) All existing earthing of the lifts shall be maintained and made fully functional by the contractor to the entire satisfaction of the Engr-in-Charge.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements