Military Engineer Services Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Military Engineer Services - MES Tender
Eprocure
Opening Date14 Nov 2019
Closing Date10 Jan 2020
Tender Amount₹ 15,98,526 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 50,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2019_MES_297727_1Bid Award Id
ViewTender No
GE/TKD/EM/TOKEN-41/2019-20Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Certain amendments to BOQ pages at sl page No 21 (R) to 39(R) and Particular specification page No 134 (R)
BOQ Items
M&L for sand cushioning in trenches for protection of LT underground cable including watering and consolidation complete all as specified and directed by Engr-in-Charge.
75
-
-
Supply and laying well burnt sub class ‘B’ bricks, locally available in trenches for protection of underground cable complete all as specified and directed by Engr-in-Charge.
6100
-
-
M&L for jointing, testing and commissioning in replacement heat shrinkable straight through Jointing Kit suitable for LT Cable of size 70 Sq mm to 120 Sqmm, 3.5 or 4 core complete all as specified and directed by Engr-in-Charge. Make:- Cat No XSSO-4 of Denson/Cat No EPKJ0137 of Raychem/Cat No- MHSX1.1 KV(HSLA-3/4) of 3M
4
-
-
M&L for jointing, testing and commissioning in replacement heat shrinkable straight through Jointing Kit suitable for LT Cable of size 25 Sq mm to 50 Sqmm, 3.5/4 core complete all as specified and directed by Engr-in-Charge. Make:- Cat No XSSO-3 of Denson/Cat No EPKJ0130 of Raychem/Cat No- MHSX1.1 KV(HSLA-2/4) of 3M
4
-
-
Taking down old unserviceable security light fittings from pole upto 11 mtr height and S&F new LED street light fitting of capacity 60 watt 5700K, made up of pressure die cast housing with toughened glass and individual high power LEDs, IP66 protection and impact resistance of IK07 with 10KV built in surge protection device having top opening separate driver compartment with all electrical accessories complete all as specified and directed by Engr-in-Charge.
Make- Havells Cat No- ENDURAPEARLPLUS60WLED757 SASYTOPC/Cat No LTESS60WLED of C&S/Cat No BRTFG60WLEDV3 of Bajaj
35
-
-
Supply and lay LT UG Cable PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 25x4 Sqmm confirming to IS including taking out old unserviceable UG cable complete all as specified and directed by Engr-in-Charge.
250
-
-
Supply and lay LT UG Cable PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 35x4 Sqmm confirming to IS including taking out old unserviceable UG cable complete all as specified and directed by Engr-in-Charge.
150
-
-
Supply and lay LT UG Cable PVC insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 95x3.5 Sqmm confirming to IS including taking out old unserviceable UG cable complete all as specified and directed by Engr-in-Charge. Note -For Sch item No's 09 to 11 Excavation and earth work if any required shall be measured and paid separately under relevent items.
100
-
-
Taking out old Unserviceable street light timer switch and M&L for testing and commissioning of NATURE Switch for outdoor lighting automation using space grade sensors and an advances micro controller suitable for outdoor use having features Automatic Switching ON at Sunset, Automatic Switching OFF at dawn, No clock setting and time settings wide operating voltage range, High voltage trip and auto reset having specification 230 Volts, 50 Hz with all connected accessories of rating 12 KW 3 phase, current range 40 Amps complete all as specified and directed by Engr-in-Charge. Make- Model No- SWADEEP-02EC12KWP1P of KAKTIYA ENERGY SYSTEM or equivalent in Universal switch gear & control system/Havells
3
-
-
Taking out by disconnecting/unscrewing old unserviceable MCCB from the existing panel/DB and M&L for testing of MCCB 4 pole, 415 volts adjustable type, 160 Amps with breaking capacity 35/36 KA connection of incoming and outgoing supply complete all as specified and directed by Engr-in-Charge at site.
Make- Cat No-IHLFNF0160 of Havells/Cat No DPX160 of Legrand /Cat No 830110 of Indo Asian
2
-
-
Taking out by disconnecting/unscrewing old unserviceable MCCB from the existing panel/DB and M&L for testing MCCB 4 pole, 415 volts adjustable type, 200 Amps with breaking capacity 35/36 KA connection of incoming and outgoing supply complete all as specified and directed by Engr-in-Charge at site. Make- Havells Cat No IHLFNF0200/Cat No 420248 of Legrand/ Cat No Du200CM981110000 of L&T
2
-
-
Taking out by disconnecting/unscrewing old unserviceable MCCB from the existing panel/DBs and M&L for testing MCCB 4 pole, 415 volts adjustable type, 400 Amps with breaking capacity 35/36 KA connection of incoming and outgoing supply complete all as specified and directed by Engr-in-Charge at site.
2
-
-
Taking out by disconnecting/unscrewing old unserviceable MCCB from the existing panel/DBs and M&L for testing MCCB 3 pole, 415 volts, adjustable type, 160 amps with breaking capacity 35/36 KA connection of incoming and outgoing supply complete all as specified and directed by Engr-in-Charge at site.
2
-
-
Supply and laying electrical rubber insulating Mat of size 01 metre wide X 10 metre long having thickness 2.5 to 3.2 mm of black/grey colour (as per site requirement) with anti skid top surface suitable for 11 KV power supply as per IS-15652:2006 complete all as specified and directed by Engr-in-Charge.
40
-
-
Supply and laying electrical chequered rubber mat as per IS-5424/69, size 1x2 mtr with 19 mm thick, black in colour complete all as specified and directed by Engr-in-Charge.
6
-
-
M&L for PVC flat twin core cable with aluminium conductor of size 10 Sqmm 2 core suitable for 1100 volts power supply including taking out old one complete all as specified and directed by Engr-in-Charge.
800
-
-
Taking out by disconnecting/unscrewing all electrical connection of unserviceable post top light and M&L for testing of post top of 35 Watts capacity suitable for 240 volts, 50 Hz single phase power supply, light, spun aluminium landscape luminaire with high power LEDs as light source with all standard accessories complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No-RUBYPT35WLED75PSYMTOPC/
Cat No LTGLC30WHPLED of C&S/
Cat No HLPT-01-30-CW of Halonix
6
-
-
Taking out old unserviceable landscape light from the existing position and M&L for testing and commissioning of landscape luminaire aluminium cast for diffused lighting with high power LEDs as light source having height 1.0 metre of 08 watts capacity suitable for single phase, 240 volt, 50 Hz power supply complete all as specified and directed by Engr-in-Charge. Note- Necessary PCC and excavation work will be measured and paid separately.
Make- Havells Cat No-BAMBOOBL8WLED857SSYMTOPC 91.0M/Bajaj Cat No BGBOS6009WLED/Cat No BCP151 of Phillips
30
-
-
Supply and lay LT UG Cable PVC insulated armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 10Sqmm 2 Core complete all as directed by Engr-in-charge.
400
-
-
Taking out by disconnecting/unscrewing all electrical connection of unserviceable flood light from at a height upto 12 mtr and M&L for testing of flood light of 50 watts capacity suitable for 240 volts, 50 Hz single phase power supply, fabricated with die cast aluminium with high power LEDs as light source with all accessories complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No-JETACOMPACTOFL50WLED 757LTG/Cat No LFBX11-50-CDL of CG/
Cat No LTEF150WHPLED of C&S
5
-
-
Taking out by disconnecting/unscrewing all electrical connection of unserviceable flood light from at a height upto 12 mtr and M&L for testing of flood light of 100 watts capacity suitable for 240 volts, 50 Hz single phase power supply, fabricated with die cast aluminium with high power LEDs as light source with all accessories complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No-JETAIRISFLS100WLED757ASYMLTG/ Cat No HLFLD-ML50-100-CW of Halonix/
Cat No LTEF100WHPLED of C&S
6
-
-
Taking out by disconnecting/unscrewing all electrical connection of unserviceable Highbay light from at a height upto 12 mtr and M&L for testing of Highbay light of 100watts capacity suitable for 240 volts, 50 Hz single phase power supply, fabricated with die cast aluminium with high power LEDs as light source, IP-65 complete with all standard accessories complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No SAUCERNEOP100WLED75760DLTG/ Cat No HLBL-ML02-100-CWL of Halonix/
Cat No LTEF100WHPLED of C&S
4
-
-
Taking out by disconnecting/unscrewing all electrical connection of unserviceable vertical medium bay light from at a height upto 12 mtr and M&L for testing of vertical medium bay light of 90watts capacity suitable for 240 volts, 50 Hz single phase power supply, fabricated with die cast aluminium with high power LEDs as light source, IP-54 with all standard accessories complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No ENDURAHIBRITEPLUSHBP90WLED 765S90DTOLENS/Cat No HLMBLD-10-90-CWL of Halonix/
Cat No LTEF90WHPLED of C&S
4
-
-
Taking out old unserviceable bus chamber of any rating and M&L for bus bar chamber current rating 200 Amps 8 way type suitable for 415 Volts, 50 Hz AC supply making all incoming and outgoing connections complete all as specified and directed by Engr-in-Charge.
2
-
-
Taking out old unserviceable bus chamber of any rating and M&L for bus bar chamber current rating 100 Amps 8 way type suitable for 415 Volts, 50 Hz AC supply making all incoming and outgoing connections complete all as specified and directed by Engr-in-Charge.
2
-
-
Taking out old unserviceable MCB any type and M&L for MCB ‘C’ series 63 Amps, 4 pole rating, as per IS-60898-1, 415 Volts, 50 Hz, 10 KA, complete all as directed by Engr-in-charge.
12
-
-
Taking out old unserviceable MCB any type and M&L for MCB ‘C’ series 63 Amps, 2 pole rating, as per IS-60898-1, 240 Volts, 50 Hz, 10 KA, complete all as specified and directed by Engr-in-Charge.
15
-
-
M&L for providing cement concrete type B2 1:2:4 using 40 mm graded stone aggregate in foundation, filling and mass concrete including dismantling existing work complete all as specified and directed by Engr-in-Charge.
3.5
-
-
M&L for Excavation by Trench less Boaring Technology method for making holes under road, pavement, hard standing using Ultra sound technique and engaging necessary Machine including HDPE pipe duly ISI marked of dia 100 mm suitable for 0.4 MPA working pressure complete all as specified and directed by Engr-in-Charge. Note - HDPE pipe and making good the disturbed surface is deemed to be included in rate quoted by the Contractor.
40
-
-
M&L for Excavation by Trench less Boaring Technology method for making holes under road, pavement, hard standing using Ultra sound technique and engaging necessary Machine including HDPE pipe duly ISI marked of dia 50 mm suitable for 0.4 MPA working pressure complete all as specified and directed by Engr-in-charge.
Note - HDPE pipe and making good the disturbed surface is deemed to be included in rate quoted by the Contractor.
60
-
-
S&F high sensitivity PIR presence/absence detector with direct dim DALI/DSI system complete all as directed by Engr-in-charge. Make- Bajaj Cat No-EBDHS-DD/ Cat No MSPO2 of Havells/ Cat No 048803 of Legrand
3
-
-
Taking down /dismantling of old unserviceable solar street light from the existing location and M&L for testing and commissioning of all in one solar street light having luminaire wattage 12 Watt, LED type, Maximum power point tracking (MPPT) SCC solar charge controller, Mono Crystalline SPV panel of 30 watts, Lithium Ferro Phosphate Battery (LiFe04) 12.8 Volts and 14 AH with 2 days backup complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No-KHSTAKU7CBAF012/Cat No HLSSL-01-12W-30A-wp of Halonix/ Cat No 112567 of Bajaj
3
-
-
Supply, Fixing and Commissioning of solar LED standalone street light system having luminaire wattage 15 watts with LED street light, 5 meter long tubular pole with base plate, 40 AH Gel battery, 75 watts solar panel including making PCC base for installation of light as per the company guidlines and taking out old unserviceable street light from the existing position complete all as directed by Engr-in-charge. Make- Havells Cat No-15WSOLARSLS/ Cat No HLSSL-01-15w-3DA-WP of Halonix / Cat No 112569 of Bajaj
2
-
-
M&L for Commissioning and Testing of panel board Power safe enclosures (Load Bank MCCB incomer and 4P MCCB outgoing) confirming to IS:8623, IEC:60439, powder coated CRCA sheet enclosure having 250 Amps AA frame MCCB, single door type with 4 outgoing ways with all connected accessories complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No-IHVGF25004 / Cat No JN2B00004516 of HAGER/ Cat No DBVTH004SD of L&T
3
-
-
M&L for Commissioning and Testing of Cable alley for G frame panel boards, outgoing 4 pole MCCB confirming to IS:8623, IEC : 60439, powder coated CRCA sheet enclosure suitable for 250 Amps incomer MCCB and 4pole outgoing MCCB GF 8 ways complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No - ISSBOU0678 /Cat No VYDOOE2 of HAGER
3
-
-
Supply, Fixing, Testing and Commissioning of pre-wired metre module with digital voltmeter, ammeter, selector switch, CTs control, fuse & indicating lights confirming to IS:8623, IEC : 60439, powder coated CRCA sheet enclosure suitable for 4 pole MCCB G frame enclosures complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No ISSBOU0711/ Cat No VYOOM2 of HAGER
4
-
-
M&L for Testing and Commissioning of ‘G’ frame fixed thermal type MCCB 4 pole 25 KA, 100 Amps suitable for mounting on ‘G’ frame load bank enclosure as a outgoing circuit GH frame complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No - IHLGHF0100# / Cat No ISDA067406R of ABB/ Cat No CM9793300K2 of L&T
16
-
-
M&L for Testing and Commissioning of ‘G’ frame fixed thermal type MCCB 4 pole 35/36 KA, 250 Amps suitable for mounting on ‘G’ frame load bank enclosure as a outgoing circuit GH frame complete all as specified and directed by Engr-in-Charge. Make- Havells Cat No - IHLFNF0250# /Cat No CM98065OOPO(DU250) of L/T /Cat No ISDA06870R1 of ABB
4
-
-
Supply, Installing, Testing and Commissioning of feeder pillar box outdoor type, fabricated from quality 3.15 mm thick CRCA sheet and angle iron including powder coated, making earth connections etc. The panel should be dust and vermin proof factory fabricated, CPRI approved totally enclosed free standing/wall mounting type extendable from both sides, suitable for 415 volts, 50 Hz 3 phase 4 wire system complete in all respect and confirming to latest relevant of ISI specifications including necessary connections, inter connections with copper conductor cable of required size cable tray gear mounted complete suitable to AC 23 duty confirming to IS-4064 and with and including the following accessories :- BUS BAR CHAMBER:- 300 Amp TPN, Aluminium conductor, Supported on insulated plate form, interconnection of all incomings & outgoings. Note- (i) Necessary excavation and PCC required to carried out for installation of LT panel board is deemed to be included in quoted rate. (ii) Old unserviceable/MCCBs of any rating and type retrieved from the Old panel will be the Govt. property).
(a) Bus bar chamber of 3 phase 4 strip 415 volts with 375 main and 250 Amps Neutral, Aluminium strip 1 set Supported on insulated plate form, interconnection of all incomings & outgoings. Contd on next page...
2
-
-
Contd sl item No 42.00:
(b) MCCB 4 pole in coming 250 Amp 35/36 KA with earth fault relay -01 Nos
(c) MCCB 4 pole out going 160Amp 25 KA = 02 Nos (d) MCCB 4 pole out going 125 Amp 25 KA = 02 Nos (e) MCCB 4 pole out going 100 Amp 25 KA = 01 Nos (f) Digital Voltmeter 0-500W volt = 01
(g) Digital Amp meter 0 -200 Amp = 01
(h) Indicator lamp yellow , Red , blue (j) Complete wiring of the panel board.
(k) MCB 32 Amps SPN - 04 Nos
(l) CT ratio 250/5 amps
-
-
-
Supply, install, testing and commissioning of feeder pillar box outdoor type, fabricated from quality 3.15 mm thick CRCA sheet and angle iron including powder coated, making earth connections etc. The panel should be dust and vermin proof factory fabricated, CPRI approved totally enclosed free standing/wall mounting type extendable from both sides, suitable for 415 volts, 50 Hz 3 phase 4 wire system complete in all respect and confirming to latest relevant of ISI specifications including necessary connections, inter connections with copper conductor cable of required size cable tray gear mounted complete suitable to AC 23 duty confirming to IS-4064 and with and including the following accessories :- Contd on next page...
1
-
-
Contd sl item No 43.00:
BUS BAR CHAMBER:- 500 Amp TP, Aluminium conductor, Supported on insulated plate form, interconnection of all incomings & outgoings. Note- (i) Necessary excavation and PCC required to carried out for installation of LT panel board is deemed to be included in quoted rate. (ii) Old unserviceable/S MCCBs of any rating and type retrieved from the Old panel will be the Govt. property.
(a) Bus bar chamber of 3 phase 4 strip 415 volts with 500 Amps main and 250 amps Neutral, Aluminium strip 1 set Supported on insulated plate form, interconnection of all incomings & outgoings.
(b) MCCB 4 pole in coming 315 Amp 35/36 KA with earth fault reley -01 Nos
(c) MCCB 4 pole out going 200Amp 25 KA = 02 Nos (d) MCCB 4 pole out going 160 Amp 25 KA = 02 Nos (e) MCCB 4 pole out going 125 Amp 25 KA = 02 Nos (f) Digital Voltmeter 0-500W volt = 01
(g) Digital Amp meter 0 -200 Amp = 01
(h) Indicator lamp yellow , Red , blue (j) Complete wiring of the panel board.
(k) MCB 32 Amps SPN - 04 Nos
(l) CT ratio 300/5 amps
-
-
-
Dismantling of old existing looping box including disconnecting of incoming/outgoing cables & removing from site and Supply, installation and testing of non transparent SMC Kiosks box 3 phase with 4 Nos bus bar, 63 Amps aluminium 4 Wire and 01 Nos Kit cat fuse of 10 Amps factory made, outdoor type made out of 14 gauge steel sheet, locking arrangement, front side of suitable size 300x200x100mm complete all as specified and directed by Engr-in-Charge.
35
-
-
Dismantling of old existing looping box including disconnecting of incoming/outgoing cables& removing from site and Supply, installation and testing of non transparent SMC Kiosks box 3 phase with 4 Nos heavy duty connector 100 Amps, outdoor type made out of 14 gauge steel sheet, locking arrangement, front side of suitable size 250x150x100mm complete all as specified and directed by Engr-in-Charge.
20
-
-
Dismantling of old existing Bus bar chamber/ panel including disconnecting of incoming/outgoing cables & removing from site and Supply, installation and testing of Outdoor type Bus bar box having CRCA sheet thickness 3.15 mm, with bus bar rating 600 Amps with 4 strips aluminium having enclosure size 900x700x600 mm with angle iron of 50x50x6 mm , locking arrangement, having minimum height 1.5 feet duly grouted or welded on floor including, powder coated paint complete all as specified and directed by Engr-in-Charge.
2
-
-