Military Engineer Services Tender

If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.

Military Engineer Services - MES Tender

Works
Security and Emergency Services
Eprocure
Opening Date12 Apr 2024
Closing Date6 May 2024
Tender Amount₹ 44,64,000 
Notes
Download

Costs

Summary

Cwe/ggn/ft-23/2023-24 Provn Of Fire Hydrants And Automated Fire Alarm System In Tech Area At Mcc Af Stn Basant Nagar Under Ge (af) Faridabad

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY FOR FIRE HYDRANT as listed in Sch 'A' Section-III (refer prepriced shedule attached seperately)

1

-

1638802.48

... More
MISCELLANEOUS ITEMS under Sch 'A' Section-IV are not prepriced by MES and item Rate to be quoted by contractor for each item.

-

-

-

... More
Supply and fix MS cabinet (approx 750mm x 600mm x 450mm) to encl fire brigade inlet connections fabricated from 16 gauge sheet with full front glass door and locking arrangement painted and mounted on masonry platform complete all as specified and directed

8

-

-

... More
Supply, installing testing and commissioning of factory made and tested (Including CPRI test cetified) indoor type floor mounted LT panel board, cubical type suitable for 415 Volts 3 phase, 4 wire 50Hz, Ac supply system having busbar chember with insulated AL busbar of rating 300 A for phase installed on porcelin/ SMC insulators. The panel shall be dust and vermin proof IP-54 class protection and made out of 2.00 mm thick CRCA MS sheet and angle iron frame 40x 40x 6mm thick frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coat of red oxide primer, front and back opening type with aproaches for cable entry with double door shutter and locking arrangements including internal wiring with PVC insulated stranded copper conductor cable FRLS confirming to IS:694, sheathed 1100V grade of appropriate size The panel shall be comprising of following:-

1

-

-

... More
INCOMING (i) Mains MCCB 4 pole 250Amps with adjustable setting, 415 Volts with breaking capacity 25 KA. -01 No. (ii) Aluminium Bus bar three phase 4 wire 300 amps 1100 volts -01 Set. (iii) Digital type voltmeter 0-500 volts and with selector switch-01 No. (iv) Digital Amp meter with CTs & built in selector switch-01 No. (vi) Indication lamp RYB-01 Set. OUTGOING- (i) MCCB 3 pole 125 Amps,, 415 Volts with breaking capacity 25 KA.-01No. (ii) MCCB 3 pole 160 Amps, 415 Volts with breaking capacity 25 KA.-01 No.

-

-

-

... More
Supplying, installation, testing & commissioning of 1, 2, 4 and 8 loop Analogue Addressable Fire Alarm Control Panel expandable via plug-in loop driver boards, loop current minimum 500mA per loop, dual flash based microprocessor, supports to connect minimum 120 detectors and devices in any combination in each loop via fully digital communication protocol, equipped with a white backlit display ( 240x64 ) graphical LCD Display with at least 6 lines of information, 200 zones (soft zones) per panel and 2000 zones on network, fully programmable via alphanumeric keypad or configuration software without using any king of DONGLE/LICENCE OR SPECIAL CABLE, dedicated USB and RS-232 serial port for direct or PC connection. panel support 5000 historic events and 500 fire alarm events. Panel shall be equipped with in-built multi-meter for live monitoring of loop current, earth voltage, loop voltage etc. Panel shall support peer to peer networking between panels capable of networking 32 nodes on standard networking and 200 nodes on secured network.Panel housing shall meets min IP30 ingress protection classification finished in RAL 7035. The panel shall be capable of providing output for BMS/ SCADA software through optional Modbus/ Bacnet module. Independently certified as complying with requirements of BS EN 54 Part 2, 4 and 13/. 1 Loop Panel with Network card

3

-

-

... More
Supplying, installation, testing & commissioning of repeater panel with 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required. Complete all as specified and directed.

1

-

-

... More
Supplying, installation, testing & commissioning of Intelligent Analogue Multisensor (combination of smoke and heat including both ROR & fixed) Detector with base and inbuilt Isolator/ Isolator Module and special algorithms to utilize information from both smoke and heat sensing elements to ensure high level of immunity to false alarms without compromising genuine alarm sensing performance. Programmable multiple smoke sensitivity level and 5 modes of operation, the detector shall be capable of operating in heat only mode. Bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED's with 360 degree view of status, auto- addressable/electronically, Independently certified as complying with requirements of BS EN 54 Part 5, 7 and 17.

220

-

-

... More
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. Complete all as specified and directed.

100

-

-

... More
Supplying, installation, testing & commissioning of Intelligent Analogue addressable resettable Manual Call Point , with in-built bi-directional short circuit isolator. Bi-Colour LED for local indication of device status, single action operation, reset to normal condition using special reset key. Independently certified as complying with r quirements of BS EN 54 Part 11 and 17. Complete all as specified and directed.

6

-

-

... More
Supplying, installation, testing & commissioning of Intelligent Analogue Single Input/ Monitor Module with inbuilt Isolator/ Isolator Module , microprocessor controlled interface modul for Flow switch monitoring and other input purposes , with in-built short circuit isolator, 360 degree view LED's for local indication of device status, auto-addressable. Independently certified as complying with r quirements of BS EN 54 Part 18 and 17. Complete all as specified and directed.

3

-

-

... More
Supplying, installation, testing & commissioning of Intelligent Analogue Relay Output/ Control Module with inbuilt Isolator/ Isolator Module , for control of third party/auxiliary devices using single volt-free change-over relay contact, with in-built short circuit isolator, Bi-colour LED's for local indication of device status, auto-addressable. Independently certified as complying with requirements of BS EN 54 Part 18 and 17. Complete all as specified and directed.

3

-

-

... More
Supplying, installation, testing & commissioning of Addressable (SLC) loop powered Wall Sounder with inbuilt Isolator/ Isolator Module and Beacon for providing Audible and Visual Alarms in response to the output signal from the control panel , however if the OEM is supplying conventional hooter cum strobe then they should consider individual module (for addressing purpose) and EN/UL listed monitored power supply for the devices in the same cost, 32 selectable tone and adjustable sound level, maximum output volume @ 1M distance 100 dB(A), output tone frequency range 440 Hz to 2900 Hz, Visual alarm device output frequency 0.5 or 1Hz. Independently certified as complying with requirements of BS EN 54 Part 3, 23 and 17. Complete all as specified and directed.

6

-

-

... More
Supplying and Laying of 2X1.5 sqmm fire survival armoured cable.Complete all as specified and directed.

2000

-

-

... More
Supplying and Laying of 32mm HDPE pipe, ISI marked. Complete all as specified and directed.

300

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.