Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_673412_1Bid Award Id
ViewTender No
8815/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Supply and fix in repairs, MCCB 160 Amps,25 KA,415 volts,FP,50 Hz, adjustable & thermal magnetic released type complete all as specified and directed.
6
-
-
Supply and fix in repairs, MCCB 200 Amps,36 KA,415 volts,FP,50 Hz, adjustable & thermal magnetic released type complete all as specified and directed.
8
-
-
Supply and fix in repairs, MCCB 250 Amps,36 KA,415 volts,FP,50 Hz, adjustable & thermal magnetic released type complete all as specified and directed.
8
-
-
Supply and fix in repair MCB 63 Amps,10 KA, ''C" series, 415 volts,FP,50 Hz complete all as specified and directed.
20
-
-
Supply and fix in repair MCB 40 Amps,10 KA, "C" sreies, 415 volts,FP,50 Hz complete all as specified and directed.
25
-
-
Supply, installation, testing and commissinoning of LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC, 50Hz indoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening, locking arrangement, cable alleys, bus bar chamber and switch gear compartment, hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length, incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted with and including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation of size not less than 600x600x600mm for each leg and ground clearance not less than 450mm as per site requirement complete all as specified and directed including comprising of following :-
Incomer
(a) ACB 800 Amps, 4 pole, 50KA, 415 Volts AC 50 Hz, draw out type, manual spring charge mechanism, digital voltmeter 0-500 Volts and ammeter 0-600 Amps, CT's, LED phase indicating lamps complete -01 No.
Outgoing
(a) MCCB 400 Amps, TPN, 36 KA, 415 volts, 50 Hz supply - 01 No. (b) MCCB 350 Amps, TPN, 36 KA, 415 Volts, AC, 50 Hz -03 No.
(c) MCCB 250 Amps,TPN, 36 KA, 415 Volts, AC 50 Hz -02 Nos.
(d) MCCB 100 Amps, TPN, 25 KA, 415 Volts, AC, 50 Hz -03 No.
(e) Aluminium bus bar 1450 Amps, TPN - 01 Set.
(f) Change over switch - 320 Amp- 01 Nos
(g) MCB 6 to 16 Amps - 06 Nos
1
-
-
Supply, installation, testing and commissinoning of LT panel board suitable for working on 3 phase, 4 wire, 415 volts, AC, 50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening, locking arrangement, cable alleys, bus bar chamber and switch gear compartment ,hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate,aluminium bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length,incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted with and including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation of size not less than 600x600x600mm for each leg and ground clearance not less than 450mm as per site requirement complete all as specified and directed including comprising of following :-
Incomer-
(a) MCCB 400 Amps, FP, 36 KA, 415 volts, 50Hz, adjustable & thermal magnetic released type-1 No.
Outgoings
(a) MCCB 100 Amps, TPN, 25 KA, 415 volts, 50Hz, adjustable & thermal magnetic released type-3 No (b) MCB 40 Amps,TP, 10 KA,415 volts,50Hz- 9 Nos (Outgoing)
(c) Digital voltmeter,with VSS , Digital, Ammeter,with CTs & ASS-01 set
(d) LED phase indication lamps RYB-01 set
(e) Aluminium bus bar TPN 800 Amps rating -01 set
(f) MCB 6 to 16 Amps - 06 Nos
1
-
-
Supply, installation, testing and commissinoning of LT panel board suitable for working on 3 phase ,4 wire ,415 volts, AC ,50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening,locking arrangement, cable alleys, bus bar chamber and switch gear compartment ,hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate,aluminium bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length,incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted with and including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation of size not less than 600x600x600mm for each leg and ground clearance not less than 450mm as per site requirement complete all as specified and directed including comprising of following :-
Incomer
(a) MCCB 400 Amps, FP, 36 KA,415 volts,50Hz, adjustable & thermal magnetic released type-1 No.
Outgoings
(a) MCCB 100 Amps,TPN, 25 KA,415 volts,50Hz-6 No
(b) Digital voltmeter,with VSS , Digital, Ammeter,with CTs & ASS-01 set
(c) LED phase indication lamps RYB-01 set
(d) Aluminium bus bar TPN 800 Amps rating -01 set
(e) MCB 6 to 16 Amps - 06 Nos
2
-
-
Supply, installation, testing and commissinoning LT panel board suitable for working on 3 phase ,4 wire ,415 volts, AC ,50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening,locking arrangement, cable alleys, bus bar chamber and switch gear compartment ,hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate,aluminium bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length,incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted with and including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation of size not less than 600x600x600mm for each leg and ground clearance not less than 450mm as per site requirement complete all as specified and directed including comprising of following :-
Incomer
(a) MCCB 500 Amps, FP, 36 KA, 415 volts, 50Hz-1 No.
Outgoings
(a) MCCB 100 Amps, TPN, 25 KA, 415 volts, 50Hz-2 No
(b) MCCB 63 Amps, TPN, 25 KA, 415 volts, 50Hz-2 No
(c) MCB 40 Amps,TP, 10 KA, 415 volts, 50Hz- 9 Nos
(d) Digital voltmeter,with VSS , Digital, Ammeter, with CTs & ASS-01 set
(e) LED phase indication lamps RYB-01 set
(f) Aluminium bus bar TPN 800 Amps rating -01 set.
(g) MCB 6 to 16 Amps - 04 Nos
3
-
-
Supply, installation, testing and commissinoning of LT panel board suitable for working on 3 phase , 4 wire , 415 volts, AC , 50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening,locking arrangement, cable alleys, bus bar chamber and switch gear compartment ,hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate,aluminium bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length,incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted with and including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation of size not less than 600x600x600mm for each leg and ground clearance not less than 450mm as per site requirement complete all as specified and directed including comprising of following :-
Incomer
(a) MCCB 350 Amps, FP, 36 KA, 415 volts, 50Hz, adjustable & thermal magnetic released type-1-1 No
Outgoings
(a) MCCB 63 Amps, TPN, 25 KA, 415 volts,50Hz-2 No (b) MCB 40 Amps,TP, 10 KA, 415 volts, 50Hz- 6 Nos
(c) Digital voltmeter,with VSS , Digital, Ammeter, with CTs & ASS-01 set
(d) LED phase indication lamps RYB-01 set
(e) Aluminium bus bar TPN 400 Amps rating -01 set
(f) MCB 6 to 16 Amps - 06 Nos
1
-
-
Supply, installation, testing and commissinoning of LT panel board suitable for working on 3 phase ,4 wire , 415 volts, AC , 50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening,locking arrangement, cable alleys, bus bar chamber and switch gear compartment ,hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate,aluminium bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length,incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted with and including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation of size not less than 600x600x600mm for each leg and ground clearance not less than 450mm as per site requirement complete all as specified and directed including comprising of following :-
Incomer
(a) MCCB 400 Amps, FP, 36 KA, 415 volts, 50Hz, adjustable & thermal magnetic released type-1 No.
Outgoings
(a) MCCB 63 Amps, TPN, 25 KA, 415 volts, 50Hz-4 No (b) MCB 40 Amps, TP, 10 KA, 415 volts, 50Hz- 4 Nos (c) Digital voltmeter with VSS , Digital, Ammeterwith CTs & ASS-01 set
(d) LED phase indication lamps RYB-01 set
(e) Aluminium bus bar TPN 800 Amps rating -01 set
(f) MCB 6 to 16 Amps - 06 Nos
1
-
-
Supply, installation, testing and commissinoning LT panel board suitable for working on 3 phase ,4 wire ,415 volts, AC ,50Hz Outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation factory fabricated made out of 3.15 mm thick CRCA sheet duly powder coated and shall be CPRI approved and as approved by GE. The Panel shall have front and rear opening,locking arrangement, cable alleys, bus bar chamber and switch gear compartment ,hinged door with rubber gasket, bottom cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate,aluminium bus bar duly covered with heat shrink sleeves colour coaded duly fixed on DMC/SMC insulators, housed in a separate bus bar chamber and control wiring with copper conductor cables of adequate size and length,incoming and outgoing MCCBs shall have extended bus bar links and mounted on 50x50x5mm size MS angle iron frame duly painted with and including PCC 1:2:4 Type B1 (using 20 mm graded stone aggregate) in foundation of size not less than 600x600x600mm for each leg and ground clearance not less than 450mm as per site requirement complete all as specified and directed including comprising of following :-
Incomer
(a) MCCB 500 Amps, FP, 36 KA, 415 volts, 50Hz, adjustable & thermal magnetic released type-1 No
Outgoings
(a) MCCB 100 Amps, TPN, 25 KA, 415 volts, 50Hz-5 No (b) MCCB 63 Amps, TPN, 25 KA, 415 volts, 50Hz- 2 No (Outgoing)
(c) MCB 40 Amps, TP, 10 KA, 415 volts, 50Hz- 4 Nos (Outgoing)
(d) Digital voltmeter with VSS , Digital, Ammeter with CTs & ASS-01 set
(e) LED phase indication lamps RYB-01 set
(f) Aluminium bus bar TPN 900 Amps rating -01 set
(g) MCB 6 to 16 Amps - 06 Nos
2
-
-
Supply, laying in trenches/ducts/along wall/through pipes etc, testing and commissioning LT cable, XLPE insulated, galvanized steel strip armoured, 1100Volts grade with multistranded aluminium conductor of cross sectional area 240 sqmm, 3.5 core including making cable connections by providing necessary aluminium lugs duly crimped properly and stainless steel glands, nuts, bolts and washers including removing old unserviceable item complete all as specified and directed. Note for item No 17 to 25 :- (i) Excavation & Earth work,sand cushioning, cable cover and protection pipe shall be measured and paid separately.
(ii) The cable shall be in one length unless otherwise directed by the GE.
200
-
-
Supply , laying and testing LT cable XLPE insulated, galvanised steel strip armoured, 1100 volts grade with multistranded aluminium conductor of cross-sectional area 185 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc including removing old unserviceable item complete all as specified and directed.
220
-
-
Supply, laying and testing LT cable XLPE insulated, galvanised steel strip armoured, 1100 volts grade with multistranded aluminium conductor of cross-sectional area 150 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc including removing old unserviceable item complete all as specified and directed.
220
-
-
Supply, laying and testing LT cable XLPE insulated,galvanised steel strip armoured, 1100 volts grade with multistranded aluminium conductor of cross-sectional area 120 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc including removing old unserviceable item complete all as specified and directed.
190
-
-
Supply, laying and testing LT cable XLPE insulated, galvanised steel strip armoured, 1100 volts grade with multistranded aluminium conductor of cross-sectional area 95 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc including removing old unserviceable item complete all as specified and directed.
190
-
-
Supply, laying and testing LT cable XLPE insulated, galvanised steel strip armoured, 1100 volts grade with multistranded aluminium conductor of cross-sectional area 70 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc and testing including removing old unserviceable item complete all as specified and directed.
280
-
-
Supply, laying and testing LT cable XLPE insulated,galvanised steel strip armoured,1100 volts grade with multistranded aluminium conductor of cross-sectional area 50 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc including removing old unserviceable item complete all as specified and directed.
280
-
-
Supply, laying and testing LT cable XLPE insulated,galvanised steel strip armoured,1100 volts grade with multistranded aluminium conductor of cross-sectional area 35 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc including removing old unserviceable item complete all as specified and directed.
260
-
-
Supply, laying and testing LT cable XLPE insulated,galvanised steel strip armoured,1100 volts grade with multistranded aluminium conductor of cross-sectional area 16 sqmm, 4 core laid in trenches/pipes/ducts/walls and connection with necessary cable lugs and glands, nuts, bolts and washers etc including removing old unserviceable item complete all as specified and directed.
250
-
-
Supply and lay GI pipe 50mm dia "Medium grade" in any length with all GI fittings such as socket, elbow, bend, union, Tee etc laid in trenches/duct/culvert/road crossing etc for protection of cables including removing old unserviceable item complete all as specified and directed.
50
-
-
Material and labour for GI pip 80 mm dia "Medium grade " complete with all fittings laid in trenches,road/culvert crossing,on wall, floors,on roof,on pole, for cable protection complete all as specified and directed .
40
-
-
Material and labour for PCC 1:3:6 type C1 using 20 mm graded coarse aggregate for platform, mass concrete and coping including form work all as specified and directed.
4
-
-
Supply and filling in and spreading unwashed river sand for cushioning and covering the under ground cables in trenches and punning to provide required cover complete all as specified in SSR Part-I and as directed. Note: Punned thickess i.e 18 cm shall be measured for paymeny purpose.
85
-
-
Supply and laying unreinforced precast factory made concrete cable cover, class LV, Type -I, flat, size 250mm x 150mm x 40mm, complete all as specified and directed.
9200
-
-
Excavation in trenches , not exceeding 1.5 mtr wide and not exc 1.5 mtr depth for laying of cables, pipe lines, protection pipes and foundations etc and getting out in any type of soil complete all as specified and directed.
250
-
-
Returning filling in soil including spreading leveling watering and well rammimg in layer n exc 25 cm complete all as specified and directed
135
-
-
Removing excavated soil not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point all as specified and directed
115
-
-
Material and labour in replacement for earthing complete with galvanised steel earth plate electrode 600mmX 600mmX 6.3 mm thick buried directly in ground vertically (earth pit not less than 2.25 metres deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron strip of size 25 x 4 mm from earth electrode to test point or up to 7.5mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate no 3 of SSR Part-I provision of G I Pipe 40mm bore light grade for protection of GI strip and GI watering pipe of 20 mm bore medium grade, GI funnel with wire mesh, including char-coal, salt packed all around the earth electrode plate in layers, PCC earth pit chamber 1:3:6 type C1, RCC cover 1:2:4 type B1, excavation, earth work in any strata and returning filling, removal of surplus soil and testing for required value, complete all as specified and directed.
22
-
-
Material and labour in replacement for synthetic insulating mat of 2 mtr x 1mtr x19 mm thick complete all as specified and directed
12
-
-
Material and labour for fault finding of LT cables of size 50 to 240 sqmm X 3.5 core and any length with fault detective machine by thumbing method and suitable voltage and all as per manufactures instructions including providing straight through joint and additional cable of same existing size suitable to site requirement complete all as specified and directed.
7
-
-
Supply & fixing in repairs LED phase indicating lamp R Y B colour as required at site in existing panel boards complete all as specified and directed.
3
-
-