Military Engineer Services Tender

View complete overview of Daman & Diu MES Tender

Military Engineer Services - MES Tender

Works
Security and Emergency Services
Eprocure
Opening Date11 Dec 2023
Closing Date13 Jan 2024
Tender Amount₹ 32,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Ditto - all as per item No. 01 above but for Jocky pump monoblock type pumpset of Capacity 7.5 HP. . Notes for items No 1 to 4 :- Quoted rate is deemed to include the following elements:- (i) Cost for transportation of pump set to the approved workshop for carrying out repairs and also for taking back from the workshop to the site of the work. (ii) Cost of replacement of all components, and repairs to make the pumpsets fully functional shall be deemed to be included except the cost of spares included in item Nos 4 to 18 which shall be measured and paid separately as supply only. (iii) Any civil work required for installation of pump motor assembly shall be deemed to be included in quated rate.

17

-

-

... More
Supply only Gun metal bushes for 100HP pump set (Suitable for kirloskar make pump set existing at site)

1

-

-

... More
Supply only Gun metal bushes for 83HP pump set (Suitable for kirloskar make pump set existing at site)

1

-

-

... More
Supply only Gun metal bushes for 12.5HP pump set (Suitable for kirloskar make pump set existing at site)

1

-

-

... More
Supply only Gun metal bushes for 7.5HP pump set (Suitable for kirloskar make pump set existing at site)

17

-

-

... More
Supply only Gland packing set for 100HP pump set.

1

-

-

... More
Supply only Gland packing set for 83HP pump set .

1

-

-

... More
Supply only Gland packing set for 12.5HP pump set .

1

-

-

... More
Supply only Gland packing set for 7.5HP pump set .

17

-

-

... More
Supply only Double ball Bearing for 100HP pump set (Make SKF Cat No 6407)

1

-

-

... More
Supply only Bearing for 83HP pump set (Make SKF Cat No 6307-6308).

1

-

-

... More
Supply only Bearing for 12.5HP pump set (Make SKF Cat No 6307-6308).

1

-

-

... More
Supply only Bearing for 7.5HP pump set (Make SKF Cat No 6307-6308).

17

-

-

... More
Supply only Water seal packing for 100HP pump set.

1

-

-

... More
Supply only Water seal packing for 83HP pump set.

1

-

-

... More
Supply only Water seal packing for 12.5HP pump set.

1

-

-

... More
Supply only Water seal packing for 7.5HP pump set.

17

-

-

... More
Supply only Shaft sleeves for 100HP pump set (Suitable for kirloskar make pump set existing at site)

1

-

-

... More
Supply only Shaft sleeves for 83HP pump set (Suitable for kirloskar make pump set existing at site).

1

-

-

... More
Supply only Shaft sleeves for 12.5HP pump set (Suitable for kirloskar make pump set existing at site).

1

-

-

... More
Supply only Shaft sleeves for 7.5HP pump set (Suitable for kirloskar make pump set existing at site).

17

-

-

... More
M & L for taking out of Fladet UV & IR and Complete Servicing and maintenence, repairs and handed over to users high level satisfaction and Engineer-in-charge and refixing of Fladet series (FD Series) UV & IR tripple IR, including suitable for multispecrum infrared flame detector for instantaneous and reliable flame detection,operating angle 120 degree field of view, operating range of -50 degrees to 75 degrees, rugged, explosion-proof housing, stand alone operation and connected to variety of control devices to create a dependable fire mounting system, flame detector with Ex-proof enclosure flickering LED indication for normal operation 24 Vdc 4wire system with fully adjustable swivel mounting base complete all as specified and directed by Eng-in-charge. Make GE/HONEYWELL/TAKEX Note :- All spear parts and components including labour charges are deemed to be included in the quoted rate by the firm.

4

-

-

... More
M & L For taking out the unserviceable water foam sprinkler nozzle and Complete Servicing, maintenence, repairs and refixing of water foam sprinkler nozzle dia 15 bsp 1/2 inch BSPT, made of brass and bronze, operating pressure 2.1 Bar (30PSI) to 4.2 Bar (60 PSI), pendent type, having K-Factor K-42, approx discharge 61 LPM at 2.1 bar complete all as specified and directed. Make New age/HD FIRE

450

-

-

... More
Taking out old unserviceable cable and Supply, laying, connecting and testing of 1.5 sqmm, 2 core, 1100 volts, twisted pair, PVC insulated, FRLS, multistranded copper conductor GI wire armoured cable confirming to IS standards and specification including medium grade, 25 mm dia MS (ERW) , ISI marked conduit pipe and material and labour for providing acrylic fire stop sealant in the opening cables passing through fire compartment wall of RCC , floors, measonary walls to provide upto 2 hrs fire rating complete all as specified and directed by Engineer -in-charge . Make - KEI/ Havells/Polycab

1700

-

-

... More
M & L for taking out old unserviceable hose pipe and supply and fixing 63mm dia 15m long hose pipe externally elastomeric coated all synthetic jacketted rubberised febric reinforced rubber lined (RRL) non percolating flexible fire fighting hose delivery resistant to liquids chemical abrasion & heat havinh 38kg/Sqcm working pressure bearing IS: 636 type "A" mark fitted with gunmetal instantaneous pattern heavy duty male & female delivery heavy duty hose coupling bearing IS:903 mark binded by copper wire with necessary fittings all as specified and directed by Engineer-in-charge :- Newage/ Essel/ Exflame.

18

-

-

... More
M & L for taking out old unserviceable fire brigade breaching unit, four way and complete Servicing and maintenence, repairs and refixing of fire brigade breaching unit, four way, fire brigade inlet/collecting heads, comprising of four instantaneous male inlet coupling with plug and steel chain, ISI marked with IS No 5290, design pressure up-to 24 kg/Sqcm, operating pressure 7 kg/Sqcm, made in gun metal body with 63mm dia gun metal, instanteous inlet, NRV, Flanged type suitable to be installed over 150mm bore pipe line with necessary fittings and one number non return valve and a butterfly valve on the line upto the ring alongwith necessary components like special fittings, bends, flanged tees etc, complete in all respects, all as specified and directed. Make:- New age India / Shah Bhogilal/ New Tech

5

-

-

... More
Supply and fix in repairs first aid fire hose reel wall mounted swivel type fitted with 30 mtrs long 20mm dia, high pressured dunlop hose confirming to IS;5132 with 15mm dia outlet gun metal nozzle with shut off valves as per IS 884-1969 complete all as specified and directed. Make:- New age/Essel/Exflame/Winco/Padmini.

12

-

-

... More
Supply and fix in repairs fire hose cabinet box of size 800x600x250 mm made of 16 swg MS sheet for mounting of fose reel of size 63 mm dia of 15 mtr long and nozzle with double leafed glazed shutters and door frame made of 16 guage MS sheet painted fire red out side and brilliant white inside and lettering as "FIRE HOSE" including locking arrangement and fixing by providing MS clamps, nut, bolts,etc duly painted with red colour at suitable place as per site requirment complete all as specified and directed.

12

-

-

... More
Supply, install, test and commissioning in repairs addressable electronic hooter cum strobe and connecting with fire cables complete all as specified and directed.

15

-

-

... More
Supply and fix in repair 63mm dia stainless steel adaptor coupling complete all as specified and directed

25

-

-

... More
Supply & fix in repair 63mm dia stainless steel branch pipe complete all as specified and directed.

25

-

-

... More
Supply and fix in repairs fire hydrant landing valve 63mm dia, gun metal confirming to IS-5290 type 'A' instantaneous type single headed outlet with brass spindle cast iron wheel coupling cap with chain etc, and ISI marked suitable for connecting hose pipe and all as specified and directed. Make;- New age/essel/exflame

8

-

-

... More
Supply and fix in repairs fire hydrant landing valve 63mm dia, gun metal confirming to IS-5290 type 'A' instantaneous type double headed outlet with brass spindle cast iron wheel coupling cap with chain etc, and ISI marked suitable for connecting hose pipe and all as specified and directed. Make;- New age/essel/exflame

5

-

-

... More
Supply, install, test and commissioning in repairs fire alarm siren 1.5 km range out door type including electrical contactor relay and linked to the main fire alarm panel complete with control wiring and accessories and necessary fixing arrangement with suitable MS bracket on roof top of building and all as specified and directed. Make:KHERAJ/Morley/Edward/L&T

2

-

-

... More
Supply and fixing in repairs sluice vale 150 mm bore with flanged ends cast iron body non rising type brass spindle with nuts class PN 1.6 suitable for 150 mm dia CI/ DI/ MS pipe ISI marked conforming to IS -8329/IS- 14846 including all joints with rubber or fibre board/ bolts/ nuts , washers etc complete all as specified and directed by Engineer-in- Charge.

3

-

-

... More
M & L for preperation of surface and painting with two coats of Red synthetic enamel paint for old pipes of any description, n. exc 60 cm girth including holder bats, distance pieces, etc. (length measured over bends, branches etc.)

41.7

-

-

... More
M & L for painting of sluice valve/ NRV after prepare the surface by scrpping old paint/ iron rust using steel scrapping brush or any other appliances using one coat of synthetic enamel paint of existing colour complete all as specified and directed by Engr-in-Charge for 80mm dia

3

-

-

... More
All as per ser item No. 40 but 100 mm dia

3

-

-

... More
All as per ser item No. 40 but 150 mm dia

2

-

-

... More
Supply and fixing 100mm Cast iron Foot valve including taking down from the suction side of pumpset from the sump and making good the distrubed all as specified and directed Make : Kirloskar/Kartar/Upadhyay

1

-

-

... More
Supply and fixing 150 mm Cast iron Foot valve including taking down from the suction side of pumpset from the sump and making good the distrubed all as specified and directed Make : Kirloskar/Kartar/Upadhyay

2

-

-

... More
Supply & Fixing in repairs solenoid valve 24V, DC, 100 mm Operating pressure 0-10 kg/Sqcm, Model UW100 including necessary fittings and making connections complete in all respect and all as specified and directed. Make NEWAGE/ EXFLAME/NEW TECH/ HD FIRE

7

-

-

... More
Supply and fixing in repairs of water foam sprinkler nozzle dia 1/2 inch BSPT made brass and bronze operating pressure 2.1 bar (30 psi) to 4.2 bar (60 psi) pendent type having K facor, K-42 approx discharge 61 LPM at 2.1 bar complete all as specified and directed by Engineer-in-charge . . Make NEWAGE/ EXFLAME/NEW TECH/ HD FIRE

40

-

-

... More
M & L For Taking out old unserviceable manual call point and supply , installing, testing and commissioning of double action pull push type manual call point glass break system, housed in MS enclosure with mounting accessories complete in all respect and all as specified and directed by engineer-in-charge. Make :- GE/ HONYWELL/ NOTIFIER/ EXFLAME/HONEYWELL

15

-

-

... More
M & L For Taking out old unserviceable fire alarm control panel and supply, installation, testing and commissioning in repairs of main fire alarm control panel fabricated by MS sheet not less than 16 guage having MS sheet rear enclosure ABS plastic front cover addressable analogue fire detection and alarm type with capacity of 2 loops panel size not less than 391.5x390x145 mm of approximate weight 4.5 kg, suitable canopy 3 nos for mounting on wall to withstand 0 degree to 40 degree temperature, relative humidity 5% to 95% non condencing IP 30 (BS EN 54) protection conforming to BSEN 54 comprisig to RS 232 communication port, req-signal port for foam generator, with dc power backup for 72 Hrs in standby mode and 15 min in alarm condition, 99 to 200 charactor display. Each loop shall support analogue/ addressable devices for maximum system capacity and have TCP/IP facility and QWERTY keypad for programming. operating voltage of the pannel should be 230 volts AC (+ 15%, -15% ), 50 hz PSU rating, 24 volt dc , 4A , standby batteries 2x17 AH duration 48 hrs with network card or repeater connected 24 hrs. Auxillary output 24 Volt DC, 250mA fused all as specified and directed by engineer-in-charge. MAKE: GE/HONEYWELL/BLUESTAR/EXFLAME .

3

-

-

... More
M & L for Taking out old unserviceable HID flash light with 12 Volt Lithium-Ion battery and supply, fixing of HID flash light ,dual mode portable , housing constructed of machined aerospace grade, aluminium alloy designed for rugged use, machined aluminium reflector,IP-68 water proof protection, dust & dirt proof,having 50 watt 4700 lumens, beam lengh 7000 feet and 35 watt made 3500 lumens beam length 5000 feet, continious operation of 110 minutes, overall weight 1.9 Kg with one number 12 Volt Lithium-Ion battery facility of charging 110 Volt to 220 Volts AC, Complete all as specified and directed by engineer-in-charge. MAKE: Magna light or Equivalent in XENON

6

-

-

... More
M & L for Taking out old unserviceable Multi sensor detector and supply, installing, testing and commissioning in repairs of high impact engineering construction, white or black finished with LED operation, integral micropeocessor intallegent 4D multi sensor detector, analogue, addressable with multiple sensitivity sensing smoke, heat, ionization & photoelectric element and converting into digital signals of sensitivity range or window of .67-3.70% obscuration per foot, five settings rangng from the least sensitive at 3.5% obscuration/ ft to the most sensitive at 1% obscuratio/ ft and 75% of alarm sensitivity setting to adjustable at site, levels programmable for timed, automatic day/ night sensitivity selection including having facilities of fat stable communication, environmental compansation, automatic mapping, stand alone operation etc. with junction box and other accessories detectors shall be UL Listed having the following technical specifications and as specified and directed. Make:- HONEYWELL cat pt No. AT-IPHSI 4D OR EQUIVALENT OF GE/ FYKE i) Ion sensor (unipolar) 0.135 u C Americium 241 ii) Photo Sensor on light scattering principle iii) Heat sensor- alarm at +65 degree farnahite (35 degree cent) above ambient iv) Environmental limits- air velocity 0-500 ft/min (0-2.53 m/s) v) Temperature range- 32 degrees to 100 degree F ( 0 degree to 38 degree centigrade) vi) Humidity- 0-93% non condensing vii) Altitude- 5000ft (1523m) above sea level max viii) Operating Voltage- 15.2 to 19.9 Vdc (19 vdc nominal).

80

-

-

... More
M & L For Taking out old unserviceable Communication system with 24 V dc Battery and complete Servicing and maintenance,repairs and handed over to users high level satisfaction and engineer-in-charge and refixing of Communication system between all hangers P-52 and pump room with 24 Vdc Battery back up complete with all accessories and devices required for effective communication system for auto operation of fire alarm, extiquishing system and all as specified and directed. Note :- All spear parts and components including labour charges deemed to be included in the quoted rate by the firm.

3

-

-

... More
M & L For Taking out old unserviceable butterfly valve, and complete Servicing and maintenance , repairs and refixing of cast iron body, wafer type ISI marked , butterfly valve, confirming to IS- 13095, pressure rating PN 16, stainless STEEL SS 316(CF8M) disc,single piece SS304 shaft, EPDM sleeve,Luberized bushing,as per BS stranded lever operated type. Make Audco/Huniwell/Kirloskar 150mm dia Note:- The butterfly valve shall be fitted between two flanges on either side of pipe flanges .The valve edge rubber shall be projected outside such that they are welded with in the pipe flanges to prevent leakages.

2

-

-

... More
All as per ser item No. 52 but 100 mm dia

17

-

-

... More
All as per ser item No. 52 but 80 mm dia

5

-

-

... More
S&F Gun-metal, globe or gate valves 25 mm dia with iron wheel head, screwed both ends for iron pipe and fixed in repair with taking down old u/s gate valve of any type . Make - ZOLOTO/ HM/ KIRLOSKAR

8

-

-

... More
M & L For Taking out old unserviceable pressure guages and Supply & Fixing pressure guages of range 20 Kg/Sqcm for pumpset complete with ball valves for isolation, siphon, fittings. Make:- Feibig/Uday/EXFLAME

4

-

-

... More
M & L For Servicing and re programming of fire alarm panels of hangers including all connected accessories all as specified and directed by Engr-in-charge.

7

-

-

... More
M&L For Servicing and re progamming ( re configure) testing and commissioning and adrressable fire alarm control panel in pump house ( for two loop panel)

3

-

-

... More
M & L for Supply and repalcement of 12 v 7 AH maitenence free battries for fire alarm panel . Complete all as specified and directed by Engr-in-charge . Make - Exide or equivalent as approved by Garrison Engineer

22

-

-

... More
M & L for Supply and repalcement of 12 v 135 AH maitenence free battries for diesel engine pump set . Complete all as specified and directed by Engr-in-charge .Make - Exide or equivalent as approved by Garrison Engineer

1

-

-

... More
Hydro Testing of Fire Extinguisher 45Ltr M/Foam with necessary test certificate complete all as specified and directed.

10

-

-

... More
Hydro Testing Fire Extinguisher CO2 4.5 KGwith necessary test certificate complete all as specified and directed.

30

-

-

... More
Hydro Testing Fire Extinguisher ABC 6KG with necessary test certificate complete all as specified and directed.

35

-

-

... More
Hydro Testing Fire Extinguisher ABC 4KG with necessary test certificate complete all as specified and directed.

35

-

-

... More
Refilling of Fire Extinguisher 45Ltr M/Foam with necessary test certificate complete all as specified and directed.

10

-

-

... More
Refilling of Fire Extinguisher CO2 4.5 KG with necessary test certificate complete all as specified and directed.

20

-

-

... More
Refilling of Fire Extinguisher ABC 6KG with necessary test certificate complete all as specified and directed.

20

-

-

... More
Refilling of Fire Extinguisher ABC 4KG with necessary test certificate complete all as specified and directed.

20

-

-

... More
Supply and fix in repair Foam Fire Extinguisher 45 Ltr with necessary test certificate complete all as specified and directed.

5

-

-

... More
Supply and fix in repair Fire Extinguisher CO2 Type 4.5 KG with necessary test certificate complete all as specified and directed.

8

-

-

... More
Supply and fix in repair ABC Fire Extinguisher - 6KG with necessary test certificate complete all as specified and directed.

10

-

-

... More
Supply and fix in repair ABC Fire Extinguisher - 4KG with necessary test certificate complete all as specified and directed.

10

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.