Military Engineer Services Tender

View complete overview of Chandigarh MES Tender

Military Engineer Services - MES Tender

Works
Civil And Construction
Civil Works Others
Eprocure
Opening Date27 Feb 2024
Closing Date25 Mar 2024
Tender Amount₹ 24,50,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Schedule A Notes, Schedule of Credit, Schedule B C D ,Special conditions, Particular specification and other connected documents
Report Missing Document

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
(i) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 25 KA, 4 pole with onload change over switch 100 Amp complete. (Out going) 01No (iii) Star Delta starter fully automatic complete up to 50 HP Pump set with single phase preventor - 01No (iv) 4 Nos Aluminium Bus bar of Capacity 150 Amps for Phase & Neutral (v) Cable gland with necessary end terminations for incoming and out going cables complete (vi) Indication Lamp set of 3 for RYB & N (vii) Digital Ameter with CTs Units - 01 Set (viii) Digital Voltmeter - 01 Set (ix) Selector switch - 01 Set (each set-02Nos) (x) MCB SPN 32AMP - 01No

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x300 Amps for Phase and 1x300Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 200 Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 160 Amps, Breaking capacity 36 KA, 4 pole (Out going) 01No (iii) MCCB 63 Amps, Breaking capacity 36 KA, 4 pole. (Out going) 02No (iv) MCB TPN 63 Amps, Breaking capacity 25 KA, 4 pole. (Out going) 01No (v) 4 Nos Aluminium Bus bar of Capacity 300 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 32AMP - 01No

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x150 Amps for Phase and 1x150Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 25 KA, 4 pole with onload change over switch 100 Amp complete. (Out going) 01No (iii) Star Delta starter fully automatic complete up to 50 HP Pump set single phase preventor - 01No (v) 4 Nos Aluminium Bus bar of Capacity 150 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 32AMP - 02Nos

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel INDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 2.00 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x150 Amps for Phase and 1x150Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 25 KA, 4 pole with onload change over switch 100 Amp complete. (Out going) 01No (iii) Star Delta starter fully automatic complete up to 50 HP Pump set single phase preventor- 01No (v) 4 Nos Aluminium Bus bar of Capacity 150 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 32AMP - 01No

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x150 Amps for Phase and 1x150Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 25 KA, 4 pole with onload change over switch 100 Amp complete. (Out going) 01No (iii) Star Delta starter fully automatic complete up to 30 HP Pump set single phase preventor - 01No (v) 4 Nos Aluminium Bus bar of Capacity 150 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 32AMP - 01No

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x375 Amps for Phase and 1x375Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 250 Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 25 KA, 4 pole with onload change over switch 100 Amp complete. (Out going) 01No (iii) MCCB 100 Amps, Breaking capacity 25 KA, 4 pole. (Out going) 01No (v) 4 Nos Aluminium Bus bar of Capacity 375 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 32AMP - 02Nos

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel INDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 2.00 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x150 Amps for Phase and 1x150Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

4

-

-

... More
(i) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 25 KA, 4 pole with onload change over switch 100 Amp complete. (Out going) 01No (iii) Star Delta starter fully automatic complete up to 25 HP Pump set single phase preventor- 02Nos (v) 4 Nos Aluminium Bus bar of Capacity 150 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 32AMP - 01No

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x240 Amps for Phase and 1x240Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 160Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole (Out going) 01No (iii) MCCB 63 Amps, Breaking capacity 36 KA, 4 pole. (Out going) 02No (iv) MCB TPN 63 Amps, Breaking capacity 25 KA, 4 pole. (Out going) 01No (v) 4 Nos Aluminium Bus bar of Capacity 240 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 32AMP - 01No

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel INDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 2.00 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x375 Amps for Phase and 1x375Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 250Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole (Out going) 01No (iii) MCCB 63 Amps, Breaking capacity 36 KA, 4 pole. (Out going) 02Nos (iv) MCB TPN 63 Amps, Breaking capacity 25 KA, 4 pole. (Out going) 01No (v) 4 Nos Aluminium Bus bar of Capacity 375 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 40AMP - 04Nos

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x240 Amps for Phase and 1x240Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 250Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 100 Amps, Breaking capacity 36 KA, 4 pole (Out going) 01No (iii) MCCB 63 Amps, Breaking capacity 36 KA, 4 pole. (Out going) 02Nos (iv) MCB TPN 63 Amps, Breaking capacity 25 KA, 4 pole. (Out going) 01No (v) 4 Nos Aluminium Bus bar of Capacity 375 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 40AMP - 04Nos

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x150 Amps for Phase and 1x150Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

1

-

-

... More
(i) MCCB 100Amps, Breaking capacity 36 KA, 4 pole. (Incoming) 01No MCCB make of : Legrand/L&T/Havells (ii) MCCB 63 Amps, Breaking capacity 36 KA, 4 pole (Out going) 01No (v) 4 Nos Aluminium Bus bar of Capacity 150 Amps for Phase & Neutral (vi) Cable gland with necessary end terminations for incoming and out going cables complete (vii) Indication Lamp set of 3 for RYB & N (viii) Digital Ameter with CTs Units - 01 Set (ix) Digital Voltmeter - 01 Set (x) Selector switch - 01 Set (each set-02Nos) (xi) MCB SPN 40AMP - 01No

-

-

-

... More
Supply, install, testing & commissioning of distribution LT panel OUTDOOR of suitable size factory fabricated(Approved by CPRI) outdoor cubical/KIOSK type totally enclosed made out of 3.15 mm thick MS sheet and inner comparments of 2.00mm thick steel sheet enclosure with double door shutter with locking arrangement and angle iron legs made out of 50mmx50mmx 6 mm thick MS angle mounted on plateform suitable for operation on 3 phase,4 wire ,bus bars of capacity 3x100 Amps for Phase and 1x100Amps for neutral and fixed on insulators with digital volt meter - 01 No and digital ammeters for all the outgoings, indication lamps prewired with hinged panel door(covers) on two sides with handle,bottom gland plate and locking arrangement consisting of sufficient no's of circular cable entry holes at bottom only with suitable PVC/Rubber bushes to prevent water/moisture inside the enclosure ,required no's of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with strandard copper conductor FRLS wires of adequate size,duly powder coated internally & externally of approved shade with PCC foundation mounted on epoxy insulators with and constitute the following :- complete comprising of the following :-Make of the Panel board confirming to CPRI specifications only

3

-

-

... More
(i) MCB TPN 63 Amps, Breaking capacity 15 KA, 4 pole. (Incoming) 01Nos MCB make of : Legrand/L&T/Havells (ii) MCB 63 Amps,SP 240V (Out going) 03Nos (iii) 4 Nos Aluminium Bus bar of Capacity 100 Amps for Phase & Neutral (iv) Cable gland with necessary end terminations for incoming and out going cables complete (v) Indication Lamp set of 3 for RYB & N (vi) Digital Ameter with CTs Units - 01 Set (vii) Digital Voltmeter - 01 Set (viii) Selector switch - 01 Set (each set-02Nos) (ix) Power contator with digital timer and manual switch on panel outdoor ( control Panel from outdoor) - 01No

-

-

-

... More
M&L for earthing complete with galvanized steel earth plate, electrode 60cm x 60cm x 6.0mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to using galvanised iron strip 25×4mm as earthing lead as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel, connected to earthing test point, earth plate electrode surrounded by mixer of common salt and charcoal dust, including 20mm dia GI watering pipe ‘medium grade’, funnel with wire mesh, earthing chamber with cement concrete (1:2:4) type B-1, RCC chamber cover 80mm thick (1: 1 ½ : 3) type B1, excavation & earth work all as shown in electrical plate No 5 of SSR (Part-I) and testing on completion, complete all as specified and directed.

36

-

-

... More
Dismantaling of unsv LT panels complete all as specified and directed.

18

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.