Military Engineer Services Tender
BidAssist is a very user-friendly website which helps in finding the specific Assam e-tender that one is looking for. For getting any information or detail about any e-tender the Assam government must have posted, BidAssist is designed in such a manner so as to provide information on all government tenders in one place without any inconvenience.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date4 Jul 2024
Closing Date23 Jul 2024
Tender Amount₹ 40,00,000
Costs
EMD
₹ 80,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_663831_1Bid Award Id
ViewTender No
8973/B/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Removing surplus soil to a distance not exc 50m and depositing at level not exc 1.5m above the starting point complete all as specified and as directed.
91.35
-
-
Materials and labour for relaying old serviceable UG cable of any size/ type on trenches/ wall/ roof etc. after necessary repair/ rerouting works taking down old cable complete all as specified and as directed.
50
-
-
Materials and labour for cutting the faulty/damaged/burnt end portion of the UG cable of cross sectional area 25 sqmm to 35 sqmm 3.5 core and making good end termination with and including suitable size of aluminium thimble/lugs duly crimped with crimping tool and refixing in existing position including insulation tape, nuts, bolts etc. as required in distribution boards/LT panel boards/ Change over switch complete all as specified and as directed. ( Note :Necessary Excavation and earth work shall be measured and paid seperately if reqd.).
20
-
-
Materials and labour for cutting the faulty/damaged/burnt end portion of the UG cable of cross sectional area 50 sqmm 3.5 core and making good end termination with and including suitable size of aluminium thimble/lugs duly crimped with crimping tool and refixing in existing position including insulation tape, nuts, bolts etc. as required in distribution boards/LT panel boards/ Change over switch complete all as specified and as directed. ( Note :Necessary Excavation and earth work shall be measured and paid seperately if reqd.).
20
-
-
Materials and labour for cutting the faulty/damaged/burnt end portion of the UG cable of cross sectional area 70 sqmm to 120 sqmm 3.5 core and making good end termination with and including suitable size of aluminium thimble/lugs duly crimped with crimping tool and refixing in existing position including insulation tape, nuts, bolts etc. as required in distribution boards/LT panel boards/ Change over switch complete all as specified and as directed. ( Note :Necessary Excavation and earth work shall be measured and paid seperately if reqd.).
10
-
-
Materials and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 25 sqmm 4 core laid in trenches /floor or fixed on wall /pole including brass compression cable glands, terminal lugs etc, and taking down old cable complete all as specified and as directed.
495
-
-
Materials and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 50 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole including brass compression cable glands, terminal lugs etc, and taking down old cable complete all as specified and as directed.
340
-
-
Materials and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 70 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole including brass compression cable glands, terminal lugs etc, and taking down old cable complete all as specified and as directed.
170
-
-
Materials and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 95 sqmm 4 core laid in trenches /floor or fixed on wall /pole including brass compression cable glands, terminal lugs etc, and taking down old cable complete all as specified and as directed.
260
-
-
Materials and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 120 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole including brass compression cable glands, terminal lugs etc, and taking down old cable complete all as specified and as directed.
250
-
-
Materials and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 150 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole including brass compression cable glands, terminal lugs etc, and taking down old cable complete all as specified and as directed.
80
-
-
Materials and labour for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 185 sqmm 3.5 core laid in trenches /floor or fixed on wall /pole including brass compression cable glands, terminal lugs etc, and taking down old cable complete all as specified and as directed.
90
-
-
Supply and spreading clean dry river sand in cable trenches as in cable cushioning complete all as specified and as directed. (Note: Punned thickness shall be measured and paid)
79.16
-
-
Materials and labour for Sub class ‘B’ old size well burnt brick laid flat in trenches over the cable for protection of LT cable complete all as specified and as directed.
7.82
-
-
Materials and labour for GI pipe light grade 40mm bore with all fittings laid in trenches or in floors, including taking up/ down old pipe complete all as speciffied and as directed
24
-
-
Materials and labour for GI pipe light grade 50mm bore with all fittings laid in trenches or in floors, including taking up/ down old pipe complete all as speciffied and as directed
20
-
-
Materials and labour for Manual boring under roads / hard standing by required T&P without disturbing the top surface of the road for passing the cable in GI Pipe 80mm dia complete all as specified and as directed.
24
-
-
Materials and labour for jointing heat shrinkable after removing faulty cable , straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 25 to 50 sqmm 3½ core 1100 volts grade and necessary testing after jointing including taking down complete all as specified and directed.
Note : For item No. 21 to 24 rate for necessary excavation is inclulded in the quoted rate, excavation beyond 6 mtr will be paid under relevant items .
5
-
-
Materials and labour for jointing heat shrinkable 1100 volts XLPE straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 70 to 120 sqmm 3½ core 1100 volts grade and necessary testing after jointing including taking down complete all as specified and directed
6
-
-
Materials and labour for jointing heat shrinkable 1100 volts XLPE straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 150 to 185 sqmm 3½ core 1100 volts grade and necessary testing after jointing including taking down complete all as specified and asdirected
6
-
-
Materials and labour for jointing heat shrinkable 1100 volts XLPE straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 240 to 300 sqmm 3½ core 1100 volts grade and necessary testing after jointing including taking down complete all as specified and asdirected
4
-
-
Supply and fixing in repair cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 6-16 Sqmm 4 core complete all as specified and directed.
6
-
-
Supply and fixing in repair cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 25-50 Sqmm 3.5 core complete all as specified and directed.
6
-
-
Supply and fixing in repair cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 70-120 Sqmm 3.5 core complete all as specified and directed.
6
-
-
Supply and fixing in repair cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 150-185 Sqmm 3.5 core complete all as specified and directed.
2
-
-
Supply and fixing in repair cable jointing kit for LT (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for for aluminium Conductor cable size 240-300 Sqmm 3.5 core complete all as specified and directed.
2
-
-
Supply and fixing MCCB with Thermal - magnetic release of 80-100 Amps, 4 Pole, 415V, 25 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories and taking down old unserviceable one complete all as specified and directed.
35
-
-
Supply and fixing MCCB with Thermal - magnetic release of 160-200 Amps, 4 Pole, 415V, 25 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories and taking down old unserviceable one. complete all as specified and directed.
21
-
-
Supply and fixing MCCB with Thermal - magnetic release of 200-250 Amps, 4 Pole, 415V, 25 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories and taking down old unserviceable one complete all as specified and directed.
13
-
-
Supply and fixing MCCB with Thermal - magnetic release of 320-400 Amps, 4 Pole, 415V, 36 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories and taking down old unserviceable one complete all as specified and directed.
7
-
-
Supply and fixing MCCB with Thermal - magnetic release of 500-630 Amps, 4 Pole, 415V, 70 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories and taking down old unserviceable one complete all as specified and directed.
1
-
-
Supply and fixing SS enclosure for MCCB of rating 250Amp In-built neutral Link for TPN system l IK08 and IP30 Protection having Louvers for better heat dissipation Suitable to accommodate upto 185 sq. mm. 3 1/2 core Aluminum armoured cable incl taking down unsv one and refixing serviceable/ new MCCB in enclosure and connectiing existing IC/OG cable with proper dimension lugs complete all as specified and directed.
4
-
-
Repairs/Maint of LT Panel board/box of various sizes including disconnecting all incoming and outgoing connection after taking necessary shut down, cleaning the carbon/rust from bus-bar, re-thimbling with new lugs/thimble of existing size,replacing burnt DMC insulator or bus bar supports as per exsiting one, removing old burn out wiring and re-wiring with new cable of exsiting size, including replacement of un-serviceable parts complete all as specified & directed. Note :- (i)New spares required shall be measured and paid separately under relevants items .
(ii) cost of unsheathed multistranded copper conductor of size upto 2.5sqmm for internal wiring like connection of CTs and DMC insulators are deemed to be included in quoted rate. (iii)Suitable size of copper/aluminium cable lugs to be provided by contractor for for fixing /jointing the cable in bus bar etc.
15
-
-
Supply only 3 phase single function LED Voltmeter flush mounting 96X96mm of input voltage measurement range 50-520 VAC(P-P) , 5A,accuracy class 1 for LT panel board, complete all as specified and directed.
3
-
-
Supply only 3 phase single function LED Ammeter flush mounting 96X96mm ,CT secondary site selectable 1A/5A,accuracy class 1 for LT panel board, complete all as specified and directed
4
-
-
Supply only 3 phase VAF+ PF digital meter flush mounting 96X96mm of input voltage measurement range 50-520 VAC(P-P) , 5A,accuracy class1 for LT panel board, complete all as specified and directed.
4
-
-
Supply only Indoor tape insulated ring type low tension current transformers of ratio 500/5A accuracy class 1.0 for LT panel board, complete all as specified and directed .
4
-
-
Supply only LED Indicator lamps to be mounted on LT panel for R,Y,B phase (of colour Red,green,yellow) operates on 240V AC for fixing in the existing place in LT panel board, complete all as specified and directed .
15
-
-
Supply only FRLS PVC insulated single core unsheathed multistrand copper conductor for voltage grade 1100 V of size 25 Sqmm single core complete all as specified and as directed.
10
-
-
Supply only FRLS PVC insulated single core unsheathed multistrand copper conductor for voltage grade 1100 V of size 50 Sqmm single core complete all as specified and as directed.
10
-
-
Demolition of cement Concrete (unreinforced) of any description and in any positioncomplete all as specified and directed.
1
-
-
Materials and labour PCC 1:3:6 type C2 (using 40 mm graded stone aggregates), as in foundation filling, mass concrete, complete all as specified and as directed.
1
-
-
Materials and labour for cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) as in foundation complete all as specified and as directed.
1
-
-
Materials and labour for PCC 1: 3 : 6 type C-1 (using 20 mm graded mechanically crushed stone aggregate) as in mass concrete including necessary form work for coping to the new/existing steel poles complete all as specified and directed.
0.2
-
-
Repairs/Maint of APFC LT Panel board/box upto 100 kVAR capacity including disconnecting all incoming and outgoing connection after taking necessary shut down, cleaning the carbon/rust from bus-bar, re-thimbling with new lugs/thimble of existing size, removing old burn out wiring and re-wiring with new cable of exsiting size, including replacement of un-serviceable parts complete all as specified & directed. Note :- (i)New spares shall be measured and paid separately under relevants items .
(ii) cost of unsheathed multistranded copper conductor of size upto 2.5sqmm for internal wiring like connection of CTs deemed to be included in quoted rate. (iii) All calibration of meters and APFC controller to be done by contractor after fixing in position.
(iv)Suitable size of copper/aluminium cable lugs to be provided by contractor for for fixing /jointing the cable in bus bar etc.
10
-
-
Supply only switch disconnector-fuse unit of current rating 100 Amp having terminal shrouds on both sides including phase barrier open execution type suitable for DIN fuse-link(4P) complete all as specified and as directed.
1
-
-
Supply only switch disconnector-fuse unit of current rating 125 Amp having terminal shrouds on both sides including phase barrier open execution type suitable for DIN fuse-link(4P) complete all as specified and as directed.
1
-
-
Supply only digital 8 step APFC controller of size 96X96 for contactor switching, operating voltage 415V Volts complete all as specified and as directed.
5
-
-
Supply only Indoor tape insulated ring type low tension current transformers of ratio 100/5A accuracy class 1.0 for LT panel board, complete all as specified and directed.
6
-
-
Supply only Indoor tape insulated ring type low tension current transformers of ratio 200/5A accuracy class 1.0 for LT panel board, complete all as specified and directed.
6
-
-
Supply only 3 Phase, 415 V capacitor duty contactor ,with built in surge suppressor and encapsulated with damping resistor assembly suitable for 5 kVAr rating complete all as specified and as directed.
4
-
-
All as per item No. 54 but suitable for 10 kVAr rating.
4
-
-
All as per item No. 54 but suitable for 20 kVAr rating.
3
-
-
Supply only 3 Phase, 415 V power contactor of AC3 Rating 25 Amp complete all as specified and as directed.
4
-
-
Supply only 3 Phase, 415 V power contactor of AC3 Rating 32 Amp complete all as specified and as directed.
5
-
-
Supply only 3 Phase, 415 V power contactor of AC3 Rating 40 Amp complete all as specified and as directed.
8
-
-
Supply only coil for MNX 25 -MNX 40 contactor 240 V AC complete all as specified and as directed .
6
-
-
Supply only MNX contactor contact kit complete all as specified and as directed .
10
-
-
Supply only heavy duty cylindrical type capacitor of capacity 5 kVAR, suitable for operating on 440 volts 3 phase complete all as specified and as directed.
8
-
-
Supply only heavy duty cylindrical type capacitor of capacity 10 kVAR, suitable for operating on 440 volts 3 phase complete all as specified and as directed.
10
-
-
Supply only heavy duty cylindrical type capacitor of capacity 12.5 kVAR, suitable for operating on 440 volts 3 phase complete all as specified and as directed.
6
-
-
Supply only heavy duty cylindrical type capacitor of capacity 20 kVAR, suitable for operating on 440 volts 3 phase complete all as specified and as directed.
8
-
-
Supply only heavy duty cylindrical type capacitor of capacity 25 kVAR, suitable for operating on 440 volts 3 phase complete all as specified and as directed.
2
-
-
Supply and fixing standard duty box capacitor with inbuilt MCB of suitable rating and LED indication for indication of capacitor health of capacity 20kVAR with all necessary connection with LT panel complete all as specified and as directed .
2
-
-
Taking down old unsv/ corroded LT feeder pillar box/ DB Box/ Busbar Chamber of any sizes or types (after disconnection of all electrical connections) complete for replacement with new one complete all as specified and as directed .
3
-
-
Materials and labour for shifting LT panel box from inside the room after taking down all cable and dismantling existing foundation to outside the room and connection all cable to LT panel including necessary foundation complete all as specified and as directed .
1
-
-
Supply & fix fabrication of LT Panel CPRI (Tested) Board floor mounted outdoor cubical type with compartments for each out going and incoming feeders made of CRCA of 3.15 mm thick MS sheet power coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame with double hinged with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS tinned Aluminium bus bar with for three phase and neutral LT AC, 50 Hz ,415 V, 600 Amp capacity complete with powder coating, with accomodating following items:-Incoming:(a) MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA-01. Outgoing:(a) MCCB 4 Pole, 415 V, Adjustable type, 63 Amps with breaking capacity 36 KA-4 (b) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs( c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
1
-
-
Supply & fix fabrication of LT Panel CPRI (Tested) Board floor mounted outdoor cubical type with compartments for each out going and incoming feeders made of CRCA of 3.15 mm thick MS sheet power coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame with double hinged with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS tinned Aluminium bus bar with for three phase and neutral LT AC, 50 Hz ,415 V, 600 Amp capacity complete with powder coating, with accomodating following items:-Incoming:(a) MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA-01 Outgoing:(a) MCCB 4 Pole, 415 V, Adjustable type, 100 Amps with breaking capacity 36 KA-5 (b) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (c) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
1
-
-
Supply & fix fabrication of LT Panel CPRI (Tested) Board floor mounted outdoor cubical type with compartments for each out going and incoming feeders made of CRCA of 3.15 mm thick MS sheet power coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame with double hinged with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switcher gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS tinned Aluminium bus bar with for three phase and neutral LT AC, 50 Hz ,415 V, 600 Amp capacity complete with powder coating, with accomodating following items:-Incoming:(a) MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA-01 Outgoing:(a) MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA-08 (b) On load Changeover switch 200 Amps 4 Pole 415 Volts - 01 (c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kWH, etc with all connected CTs (d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
1
-
-
Materials and labour in repair earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick burried directly in ground (Earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below ground level connected to galvanised iron strip 25 X 4 mm as earth lead by means of bolts nuts, check nuts and washers of brass and as shown in electrical plate No 3 connected to earth test point including necessary excavation any type of soil, RCC chamber cover plate, wire mess, funnel, test point, 40 mm dia GI pipe light grade for protection pipe and watering etc complete and testing on completion. complete all as specified and as directed .
18
-
-
Materials and labour for painting of steel tubular LT poles including cross arms, clamps, back plates etc. in situ with one under coat and one finishing coat of aluminium paint after cleaning /preparation of surfaces including making white and black stripes 30 cm wide 5 Nos with two coats of synthetic enamel paint and marking of pole No, Substation No, etc. complete all as specified and directed.
303
-
-
Materials and labour for complete removal of existing treatment of LT Panel, box, board, cross arms etc and applying two coats synthetic enamel paint over a coat of red oxide primer, complete all as specified and as directed.
20
-
-
Materials and labour for Cross arms, bracings, supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps, stay clamps, D clamps nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed including painting with two coats of aluminium paint over a coat of red oxide primer including taking down the old unserviceable cross arms, clamps etc complete all as specified and as directed.
0.5
-
-
Materials and labour for Prunning / trimming the branches of trees if any along overhead line, 3 m on all side below/ above/ sides of overhead line and removing the same upto a distance of 150m, each span not exceeding 45 m complete all as specified and as directed.
80
-
-
Supply and fixing in repairs insulators pin type LT 1100 Volts grade porcelain vitreous white or brown including one galvanized mild steel spindle, two galvanized iron washers, iron nut, 100 mm height, 65 mm dia complete all as specified and directed.
20
-
-
Supply and fixing in repairs shackle type insulator LT 1100 volt grade porcelain vitreous white or brown including galvanised mild steel straps, washers, insulator bolts, nuts 12 mm dia, 75 mm height and 90 mm dia, section of straps 31mmx3mm of insulator complete all as specified and directed.
20
-
-
Materials and labour for Stringing / stretching, including jointing in situ of each span not more than 45 m between two electric poles having 4 Nos of ACSR conductors of any size including GI earth continuity wire, with/ without guarding wires on electric poles of any size at different locations all as directed to the extent of permissible sag or tension by removing jumpers or bindings from insulators and making fresh binding with aluminium tapes after stringing complete all as specified and as directed.
(Note :- One span measured as 4 Nos wire of LT over head line and 2 Nos of earth wire.)
80
-
-
Materials and labour for Stringing / stretching, including jointing in situ of each span not more than 45 m between two electric poles having 2 Nos of ACSR conductors of any size including GI earth continuity wire, with/ without guarding wires on electric poles of any size at different locations all as ordered to the extent of permissible sag or tension by removing jumpers or bindings from insulators and making fresh binding with aluminium tapes after stringing complete all as specified and as directed.
(Note :- One span measured as 2 Nos wire of LT over head line and 1 Nos of earth wire.)
60
-
-
Materials and labour for ACSR conductors (weasel type) for LT OH lines on poles including stringing, binding with aluminium wire 14 SWG or aluminium tape including jumpers complete connecting of disconnected cable, service cable and street light connection including dismantling of unserviceable ACSR conductor of any size from any position complete all as specified and as directed.
1
-
-
Materials and labour for erection and fixing of steel tubular swaged pole type 410 SP - 31 (9.00 metres long) confirming to IS- 2713 Part I to III 1980 with and including cast iron base plate, finial taper plug, nuts, bolts and washers etc. fixed in PCC foundation duly painted painted with two coats of Aluminium paint over a coat of red oxide primer including preparation of surface and including dismsntling of old pole of any size and description with foundation, PCC coping etc. complete all as specified and as directed.
4
-
-
Materials and labour for stay assembly comprising 14mm dia iron stay bow, stay strand wire of size 7/3.15mm with stay rod of diameter 16mm complete with all accessories as shown in electrical plate no. 1 of SSR part-I 2009 including dismsntling of old stay assembly of any description with foundation, etc. complete all as specified and as directed.
3
-
-
Materials and labour for loop type insulator, vitreous porcelain, white, brown or green with overall dimension 90mmX140mm, clearence of hole 25.5mm suitable for 1100 Volts complete all as specified and as directed.
3
-
-
Disconnecting from LT poles or transformer and taking up loop of underground cable , of sizes of cros- sectional area 70-120 sqmm 3.5 cutting the faulty damaged portion of cable , replace with new end termination outdoor heat shrink type including excavation, returning filling and all connected materials complete all as specified and directed.
(Note:-Necessary excavation , sand cushioning ,cable cover as bricks etc beyond 5 mtr should be measured and paid separately)
4
-
-
All as per item No.86 here in above but size 150-185 sqmm 3.5 Core.
2
-
-
All as per item No.86here in above but size 240-300 sqmm 3.5 Core.
1
-
-
Materials and labour in repair for cradles, hexagonal/rectangular, fabricated with galvanized steel wire 4 mm dia including stretching, sagging and jointing in position as a continuous earth wire on pole and for guarding complete all as specified and directed.
0.3
-
-
Supply and fixing in repair street light junction box of size 155 x210x92mm made of high quality polycarbonate with IP-66 protection (Dust and vermin proof according to IEC-60529) totally insulated made of halogen and silica free recyclable material having high quality gasket made out of polyurethane with MCB, DP, 10KA, 6 Amps to be fixed on Din rail , with locking arrangement with cable gland suitable upto 10 sqmm cable and necessary fixing arrangements such as clamps, nuts, bolts etc complete all as specified and directed.
6
-
-
Supply and fixing LED street light of capacity 46/45 Watt made up of pressure die cast aluminium housing with high power LED as light source and lens embedded PC cover including electronic driver should have luminaire efficacy ≥120 lumens/watt,CRI70 ,PF 0.95,CCT≥5500,IP66,impact resistance IK 07 ,inbuilt protection against lightning , over voltage , short circuit and surge/spike protection device upto 5 kV including taking out old unserviceable luminare complete all as specified and directed.
16
-
-
Supply and fixing street light fitting of 90 Watt LED made of pressure die cast aluminium housing with toughned glass and LEDs with secondary optics and IP 66 protection and lens embedded PC Cover having top opening seperate driver compartment ,should have luminaire efficacy ≥110 lumens/watt, CRI70, PF 0.95, CCT≥5500, IP66, impact resistance IK 07, inbuilt protection against lightning, over voltage, short circuit and surge/spike protection device upto 5 kVcomplete also tested for 440 Volt for 8 hour Phase to phase without any damage taking out old unserviceable luminare complete all as specified and directed.
8
-
-
Supply and fixing LED flood light of capacity 50 Watt made up of pressure die cast aluminium housing with high power LED as light source and lens embedded PC cover including electronic driver should have LED efficacy≥100 lumens/watt,CRI70 PF 0.95,CCT≥5500,IP66,impact resistance IK 07 ,inbuilt 5kV surge protection device including taking out old unserviceable luminare complete all as specified and directed complete all as specified and directed.
6
-
-
Supply and fixing LED flood light of capacity 100 Watt made up of pressure die cast aluminium housing with high power LED as light source and lens embedded PC cover including electronic driver should have LED efficacy ≥100 lumens/watt,CRI70 PF 0.95,CCTCCT≥5500,IP66,impact resistance IK 07 ,inbuilt 5kV surge protection device including taking out old unserviceable luminare complete all as specified and directed.
4
-
-
Supply and fixing in repairs street light bracket made of GI pipe 40 mm bore light grade(bend to shape) , 1.5 metre long and fixed with Ms flat iron clamp(clamp shall be 40 X 5mm ), nuts, bolts and washers on pole complete all as specified and directed.
10
-
-