Military Engineer Services Tender

BidAssist is a very user-friendly website which helps in finding the specific Assam e-tender that one is looking for. For getting any information or detail about any e-tender the Assam government must have posted, BidAssist is designed in such a manner so as to provide information on all government tenders in one place without any inconvenience.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date12 Dec 2023
Closing DateCancelled
Tender Amount₹ 43,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
All as per Item No. 01 here-in-above, but for One 3/5 pin socket outlet, 15 Amps, independent board, with cables 4 sq. mm size, complete all as specified and as directed by Engineer-in-charge.

20

-

-

... More
S&F of Switch piano, flush type single pole, One way 5/6 Amp, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

70

-

-

... More
S&F of Socket outlet 3/5 pin, 5/6A, flush type, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

10

-

-

... More
S&F of Switch socket combination 2 in 1, 3/5 pin, 15/16 Amp, flush type universal, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

20

-

-

... More
S&F of Switch socket combination 2 in 1, 3/5 pin, 5/6A flush type, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

30

-

-

... More
S&F of stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd., 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

10

-

-

... More
S&F of ceiling rose surface backelite three terminals, PVC/ polycarbonate, insulated body, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
S&F in-repair of Modular Switch, One Module, 1-Way, 10 Amps, 240 Volt, conforming to IS and connecting up, complete all as specified and as directed.

10

-

-

... More
S&F in-repair of Modular Switch, One Module, 1-Way, 20 Amps, 240 Volt, conforming to IS and connecting up, complete all as specified and as directed.

10

-

-

... More
S&F in-repair of Modular Socket, 3 Pin, combined, Two Module, 10 Amp, 240 Volt, conforming to IS and connecting up, complete all as specified and as directed.

5

-

-

... More
S&F in-repair of Modular Socket, 2/3 Pin, combined, Two Module, 20 Amp, 240 Volt, conforming to IS and connecting up, complete all as specified and as directed.

5

-

-

... More
S&F in-repair of Modular stepped type electronic fan regulator, Two module, 240V, AC, complete all as specified and as directed by Engineer-in-charge.

5

-

-

... More
S&F in-repair of modular cover plate (white) with frame, 1-module, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
S&F in-repair of modular cover plate (white) with frame, 2-module, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
S&F in-repair of modular cover plate (white) with frame, 3-module, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
S&F in-repair of modular cover plate (white) with frame, 4-module, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
S&F in-repair of modular cover plate (white) with frame, 6-module, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
S&F in-repair of modular cover plate (white) with frame, 8-module, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
S&F in-repair of Switch piano, flush type single pole, One way 5/6 Amp, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

130

-

-

... More
S&F in-repair of Socket outlet 3/5 pin, 5/6A, flush type, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
S&F in-repair of Switch socket combination 2 in 1, 3/5 pin, 15/16 Amp, flush type universal, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
S&F in-repair of Switch socket combination 2 in 1, 3/5 pin, 5/6A flush type, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

70

-

-

... More
S&F in-repair of Bell push, flush type, 5/6 amp, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

4

-

-

... More
S&F in-repair of Bell Buzzer/ Ding Dong, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

6

-

-

... More
S&F in-repair of stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd., 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
S&F in-repair of Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings, 220-240V, AC, complete all as specified and as directed by Engineer-in-charge.

30

-

-

... More
S&F in-repair of surface mounted PVC box of size 100 mm x 100 mm and 50 mm deep, complete all as specified and as directed by Engineer-in-charge.

50

-

-

... More
S&F in-repair of surface mounted PVC box of size 100 mm x 175 mm and 50 mm deep, complete all as specified and as directed by Engineer-in-charge.

50

-

-

... More
S&F in-repair of surface mounted PVC box of size 300 mm x 200 mm and 50 mm deep, complete all as specified and as directed by Engineer-in-charge.

20

-

-

... More
S&F in-repair of Sub-main Wiring with 2-Runs of Single Core 6.0 Sq mm PVC insulated FRLSH multi-stranded 1100 Volts grade with Copper Conductor drawn through and including Non-metalic Rigid PVC Casing capping ISI marked and its Accessories including 1-Run of Single Core 6.0 Sq mm PVC insulated FRLSH unsheated multi-stranded 1100 Volts grade with Copper Conductor Cable as Earth Continuty Conductor along with the Wiring and connected from DB to DB/Main Board and taking down the existing old unserviceable wiring, complete all as specified and as directed. NOTE :- (a) Cost of PVC Casing capping with all Fittings/Accessories will deem to be included in the quoted UNIT RATE. (b) Cables as mentioned in SCHEDULE ‘A’ Items and 1-Run of PVC Casing capping with all Fittings/Accessories will be measured and paid as ONE UNIT. (c) Sub-main Wiring will be measured PVC Casing capping only. Wire required for looping, etc as ordered will deem to be included in the quoted UNIT RATE.

60

-

-

... More
S&F in-repair of Sheet Metal Enclosure MCB DB TPN, 4 way 415 volt, with 200 amps rated Bus-bar, Double door type MCB DB suitable for mounting incoming and outgoing MCBs of any type, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
S&F in-repair of Sheet Metal Enclosure MCB DB SPN, 2 way 240 volt, with 200 amps rated Bus-bar, Double door type MCB DB suitable for mounting incoming and outgoing MCBs of any type, complete all as specified and as directed by Engineer-in-charge.

10

-

-

... More
S&F in-repair of Sheet Metal Enclosure MCB DB SPN, 4 way 240 volt, with 200 amps rated Bus-bar, Double door type MCB DB suitable for mounting incoming and outgoing MCBs of any type, complete all as specified and as directed by Engineer-in-charge.

10

-

-

... More
S&F in-repair of Sheet Metal Enclosure MCB DB SPN, 8 way 240 volt, with 200 amps rated Bus-bar, Double door type MCB DB suitable for mounting incoming and outgoing MCBs of any type, complete all as specified and as directed by Engineer-in-charge.

18

-

-

... More
S&F in-repair of Sheet Metal Enclosure MCB DB SPN, 12 way 240 volt, with 200 amps rated Bus-bar, Double door type MCB DB suitable for mounting incoming and outgoing MCBs of any type, complete all as specified and as directed by Engineer-in-charge.

4

-

-

... More
S&F in-repair of MCB Triple Pole & Neutral (TPN), 'C' Curve, 63 Amps, 415 Volt for fixing on MCB DB’s, 10 KA, 50 Hz, conforming to IS/IEC 60898, connecting up and testing, complete all as specified and as directed by Engineer-in-charge.

6

-

-

... More
S&F in-repair of MCB Single Pole & Neutral (SPN), 'C' Curve, 32 Amps, 240 Volt for fixing on MCB DB’s, 10 KA, 50 Hz, conforming to IS/IEC 60898, connecting up and testing, complete all as specified and as directed by Engineer-in-charge.

60

-

-

... More
S&F in-repair of MCB Single Pole (SP), 'C' Curve, 6-32 Amps, 240 Volt for fixing on MCB DB’s, 10 KA, 50 Hz, conforming to IS/IEC 60898, connecting up and testing, complete all as specified and as directed by Engineer-in-charge.

80

-

-

... More
S&F in-repair of surface and wall mounted LED tube light fitting 1x 20W, (4 Feet) with aluminium housing & integrated electronic driver, 6500K, 220-240 Volts, AC decorative box type with and including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose to fitting, complete all as specified and as directed by Engineer-in-charge.

500

-

-

... More
S&F in-repair of surface and wall mounted LED tube light fitting 1x 10W, (2 Feet) with aluminium housing & integrated electronic driver, 6500K, 220-240 Volts, AC decorative box type with and including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose to fitting, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
S&F in-repair of Decorative wall light made up of high grade engineering plastic material suitable for 20 W LED lamp B22 base, with necessary elecrical connections, complete as all specified and as directed by Engineer-in-charge.

6

-

-

... More
S&F in-repair of 10 watt capacity, B-22 base LED Bulb/ lamp, complete all as specified and as directed by Engineer-in-charge.

200

-

-

... More
S&F in-repair of slim square panel LED luminaire with frame 600 mm x 600 mm, white powder coated with CRCA housing, 42 watt, 220-240 V, AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cables of suitable size, complete all as specified and as directed by Engineer-in-charge.

10

-

-

... More
S&F Energy saving new generation environmental friendly long life versatile presure die cast aluminium housing IP 66 building security light fitting luminaire with high power LEDs as light source and electronic driver of capacity 25 watts with pre wired and lens embedded PC cover having Bottom opening seperate driver compartment and Impact resistance of IK08 with necessary mounting arrangements, including taking down old unserviceable light fitting, complete all as specified and as directed by Engineer-in-charge.

56

-

-

... More
M&L for disconnecting and taking down ceiling fan of 1200/1400 mm sweep, sealing cable end, dismantling blades and removing fan and blades to store for Opening Stator, Cleaning of Parts, replacement of Unserviceable Parts as ordered, Greasing of Moveable Parts, re-winding the coil and Re-assembling the ceiling fan after proper repair and applying two coats of synthetic enamel paint over a coat of red oxide primer by spraying including filling cavities with filler, after cleaning all dust and necessary surface preparation including hanging the ceiling fan in original position and connecting up including provision of cable from ceiling rose or connector to fan (as/if required), complete all as specified and as directed by Engineer-in-charge. NOTE:- Spare-parts and cost of re-winding shall be measured and paid separately under relevent item.

40

-

-

... More
M&L for re-winding the coil of ceiling fan 1200/1400 mm sweep with Supper Enameled Copper Wire of same Gauge and same Weight with Insulation Paper, Varnishing and Heating, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
Supply only Ball Bearing as approved suitable for Ceiling Fan of 1200mm / 1400 mm Sweep, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
Supply only Capacitor 3.15 mfd (as approved) 230 Volts, AC, 50Hz, suitable for Ceiling Fan of any Sweep and Make, complete all as specified and as directed by Engineer-in-charge.

200

-

-

... More
S&F in-repair of Thermostat/Thermal cutoff suitable for Water Storage Geyser of range 0-90ºC as required, conforming to IS (Make as approved) complete all as specified and as directed.

10

-

-

... More
S&F in-repair of Electro-plated Heating Element (as approved), suitable for Electric Geyser of 2.0 KW capacity, 240 Volts, complete all as specified and as directed. MAKE : BAJAJ/RECOLD/HAVELLS/USHA

10

-

-

... More
S&F in-repair of wall fastener of size 100mm long, 8mm dia with double washers including grouting for fixing of water heater and making good the disturbed surfaces as per existing, complete all as specified and as directed.

8

-

-

... More
S&F in-repair of PVC connection pipe of 450mm long (02 Nos) with brass connector series for both inlet and outlet of Geyser, complete all as specified ans as directed. MAKE:- PRAYAG/POLYTUF

10

-

-

... More
S&F in repair Plug Top of 3Pin, 15/16 Amps capacity with indicator, complete all as specified and as directed. MAKE:- ANCHOR/L&T/HAVELLS

10

-

-

... More
M&L for earthing complete with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth wire 4.00 mm dia by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 15 mm bore( light grade) and watering pipe 20 mm bore GI pipe (light grade) and chamber and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg. 50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excvation and earth work and removal of surplus soil complete all as shown in electrical plate no 3 of SSR PT 1, 1991 with charcoal dust and salt complete and earth lead connected to earthing test point (up to main switches, DBs) including taking down old unserviceable one, complete all as specified & testing on completion. NOTE:- (i) item includes the cost of 7.5 mtr length GI pipe for protection for GI earth wire. (ii) item rates includes the cost of 7.5 mtr GI earth wire.

4

-

-

... More
S&F in-repair of bracket suitable for LED Street light fitting/ house service bracket made out of 25mm bore (Dia) light grade GI pipe of 1.2m long, bend to required shape, including necesary clamps (Mild Steel Flat iron of 32x6mm) for fixing of building security/ street light fitting as per existing, complete all as specified and as directed by Engineer-in- Charge.

30

-

-

... More
S&F in-repair of 1100 volts grade heavy duty cable PVC insulated aluminium stranded conductor of, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular of 2.5 Sqmm section, complete all as specified and as directed by engineer-in-charge.

200

-

-

... More
All as per Item No. 59 here-in-above, but for cross-sectional area 4 Sqmm, complete all as specified and as directed by Engineer-in-charge.

500

-

-

... More
All as per Item No. 59 here-in-above, but for cross-sectional area 6 Sqmm, complete all as specified and as directed by Engineer-in-charge.

100

-

-

... More
All as per Item No. 59 here-in-above, but for cross-sectional area 10 Sqmm, complete all as specified and as directed by Engineer-in-charge.

200

-

-

... More
All as per Item No. 59 here-in-above, but for cross-sectional area 16 Sqmm, complete all as specified and as directed by Engineer-in-charge.

200

-

-

... More
S&F in-repair of Multistranded Copper Conductor cable of 3 Core 1.5 Sq mm size drawn through steel tubular poles for interconnection of cable looping box to street light Fitting, Post Top Lantern & etc including taking down old unserviceable cable complete all as specified and as directed by Engineer-in-charge.

50

-

-

... More
S&F in-repair of Energy saving new generation environmental friendly long life versatile presure die cast aluminium housing and heat resistant, IP 66 street light fitting luminaire with high power LEDs as light source and electronic driver of capacity 35/36 watts with pre wired and lens embedded PC cover having Top opening seperate driver compartment, with impact and corrosion resistant including thermal management in multiple optics and necessary mounting arrangements/ fixing bracket, complete all as specified and as directed by Engineer-in-charge.

40

-

-

... More
All as per Item No. 65 here-in-above, but for 60 Watt LED Street light, complete all as specified and as directed by Engineer-in-charge.

80

-

-

... More
S&F in-repair of Energy saving new generation environmental friendly long life versatile presure die cast aluminium housing and heat resistant, IP 66 Flood light fitting luminaire with high power LEDs as light source and electronic driver of capacity 70 watts with pre wired and lens embedded PC cover having Top opening seperate driver compartment, with impact and corrosion resistant including thermal management in multiple optics and necessary mounting arrangements/ fixing bracket, complete all as specified and as directed by Engineer-in-charge.

20

-

-

... More
All as per Item No. 67 here-in-above, but for 120 Watt LED Flood light, complete all as specified and as directed by Engineer-in-charge.

6

-

-

... More
S&F in-repair of IP-65, IK-08 rated robust designed Cone LED bollard garden Light Fitting with black ABS Plastic Spigot, Spun Aluminium Canopy with Opal Acrylic Diffuser and provision of LED Lamp 8 Watt duly pre-wired, including embedding on 150x150x300mm PCC Block 1:3:6 (20mm Graded Aggregate), complete as all specified and directed by Engineer-in-charge.

12

-

-

... More
S&F in-repair of decorative LED Post Top lantern light made in die cast aluminium spigot housing with decorative clear opal Acrylic diffuser for 360 degree indirect light IP 65 protection with impact and corrosion resistantand suitable for 20 Watt LED bulb with necessary elecrical connections with adequate size of Nuts and Bolts, complete as all specified and as directed by Engineer-in-charge.

10

-

-

... More
S&F in-repair of decorative (Opal moon) LED Gate light made in die cast aluminium spigot housing with decorative clear opal Acrylic diffuser for 360 degree indirect light IP 65 protection with impact and corrosion resistantand suitable for 15 Watt LED bulb with necessary elecrical connections with adequate size of Nuts and Bolts, complete as all specified and as directed by Engineer-in-charge.

50

-

-

... More
S&F in-repair of Pole Box/Junction Box of size 200 X 160 X 98mm (LxBxH) made out of Polycarbonate material totally enclosed, dust and vermin proof, door pasted with rubber gasket, water tight IP 66/67 protection single leaf shutter in front having proper locking arrangements, including provision of suitable connector for single phase connections loop in and out 10 to 16 Sqmm 4.0 Core aluminium armoured cable branch out 1.5 Sqmm single core PVC insulated copper cable and MCB SP 06 amps- 01 No and mounted on security light pole with suitable clamps (GI Flat iron of 25x3mm), nuts, bolts, complete all as specified and directed by Engineer-in-charge.

20

-

-

... More
Supply & laying of LT XLPE insulated cable, sheathed, screened, PVC bedded, Galvanised Steel Strip or Wire armoured, Electic Power Cable (heavy duty) with Aluminium Conductor, 1100 Volts grade, cross-sectional area 10 Sqmm 2.0 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing and taking down the existing old unserviceable cable, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

100

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 16 Sqmm 4.0 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

50

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 25 Sqmm 4.0 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

50

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 35 Sqmm 4.0 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

50

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 50 Sqmm 3.5 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

100

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 70 Sqmm 3.5 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

100

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 95 Sqmm 3.5 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

80

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 150 Sqmm 3.5 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

80

-

-

... More
All as per Item No. 73 here-in-above, but for cross-sectional area 185 Sqmm 3.5 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.

50

-

-

... More
M&L for boring holes horizontally under road without damaging the road surface with the help of GI tubing not exc. 80mm bore dia for passing of UG cable, complete all as specified and directed by Engineer-in-charge. NOTE: GI Pipe will be measured and paid separately.

24

-

-

... More
M& L for Excavation in trenches n.exc 1.5m wide and n.exc 1.5 m in depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc. and getting out in soft/loose soil complete all as per specified and as directed by Engineer-in-charge.

120

-

-

... More
M&L for Returning, filling in, including spreading, leveling, watering and well ramming in layers n exc 25cm complete all as per specified and as directed by Engineer-in-charge.

70

-

-

... More
M&L for Removing excavated material not exc. 50 m & depositing where directed at a level not exc. 1.5 m above starting point complete all as per specified and as directed by Engineer-in-charge.

50

-

-

... More
M&L for Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 230mm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180mm thickness, complete all as per specified and as directed by Engineer-in-charge. NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only will be measured and paid for.

35

-

-

... More
Supply & Laying Sub-Class B Bricks, well burnt, laid breadth wise along the length of cable laid in trenches over sand cushion laid for UG cable protection, complete all as specified and as directed by Engineer-in-charge.

3.5

-

-

... More
S&F of Galvanised Iron Pipe 40mm bore (dia) ‘light grade’ for protection of UG Cable, laid under Floors or Road Crossing, fixing to Pole with and including Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed by Engineer-in-charge.

50

-

-

... More
All as per Item No. 88 here-in-above, but for 50mm bore (dia) GI Pipe, complete all as specified and as directed by Engineer-in-charge.

30

-

-

... More
All as per Item No. 88 here-in-above, but for 80mm bore (dia) GI Pipe, complete all as specified and as directed by Engineer-in-charge.

24

-

-

... More
S&F in-repair of aluminium lug suitable for making connection of aluminium armoured xlpe cable of size upto 25 Sqmm, complete all as specified and as directed by Engineer-in-charge.

30

-

-

... More
All as per Item No. 91 here-in-above, but for cable size 35-95 Sqmm, complete all as specified and as directed by Engineer-in-charge.

100

-

-

... More
All as per Item No. 91 here-in-above, but for cable size 120-240 Sqmm, complete all as specified and as directed by Engineer-in-charge.

36

-

-

... More
Supply & Erecting in true vertical in-repair of Steel Tubular Swaged Pole Type 410-SP-31 (9.00 Metre long) including Cast Iron Base Plate, Finial Taper Plug, Cap, Mild Steel Bolts, Nuts, Screws with and including applying two coats of Black Bituminous Paint Internally and Externally from bottom End of Pole upto PCC Coping and applying two Coats of Aluminium Painting over a coat of Red oxide Primer including necessary earthwork in excavation in any type of soil, removal of surplus soil to a distance of not exceeding 50.0m, Cement Concrete 1:3:6, type C-2 (40mm graded aggregate) as in Foundation of Poles filled upto ground level and Cement Concrete 1:2:4, Type B-1(20mm graded aggregate) as in Coping/Padestal of Poles and finishing the Concrete surfaces Fair and Even including necessary Formwork as required at Site(s), complete all as specified and as directed by Engineer-in-charge. NOTE: Earthwork, Cement Concrete, etc. will not be measured and paid separately.

8

-

-

... More
M&L for Aluminium conductor steel reinforced (ACSR) (size and type as required at site) drawn for overhead lines with permissible sags and providing jumper with and including copper binding wire or aluminium tapes, including stringing, tightening, etc., including dismantling the existing old unserviceable ACSR, complete all as specified and directed by Engineer-in-charge. NOTE:- Cost of binding wire is deemed to be included in unit quoted rate.

2

-

-

... More
M&L for mild steel Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one red oxide primer coat, one under coat and one finishing coat of aluminium paint, including dismantling the existing old unserviceable cross-arms, complete all as specified and directed by Engineer-in-charge.

1

-

-

... More
S&F in-repair of Stay assembly of 16mm dia 1.18m long stay rod complete with all accessories as shown in electrical plate No. 1, size of plate 230x230x6mm, complete all as specified and directed by Engineer-in-charge. Note:- Cost of 01 no 65 x 90mm porcelain, vitreous, white, brown or green Loop type insulator, Galvanised stay strand of 7/3.15mm size upto 7.50m long stay strands with clamps and bolts, excavation and concrete shall deemed to be included in unit quoted rate.

6

-

-

... More
S&F in-repair of Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade, complete all as specified and directed by Engineer-in-charge.

30

-

-

... More
S&F in-repair of Shackle Type, porcelain, vitreous, white, brown or green insulator including one 31x3mm galvanised mild steel straps, washers, 12mm dia insulator bolts, washers and nuts, 75mm height, 90mm dia for 1100 volts grade, complete all as specified and directed by Engineer-in-charge.

16

-

-

... More
S&F in-repair of On load Changeover Switch with sheet metal enclosure and advanced neutral switch, Four Pole (FP), 63 Amps, 415 Volts, conforming to IS/IEC 60947-3 with and including all accessories, connecting up and re-fixing of cables with proper lugs, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
All as per Item No. 100 here-in-above, but for 100 Amp capacity Changeover Switch, complete all as specified and as directed by Engineer-in-charge.

1

-

-

... More
M&L for preparing old painted surfaces by scraping and removing old paints, rust, etc. from Steel Tubular Poles (above the Planting Depth and PCC Copings of 9.0 Metre length Pole) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying one Coat of synthetic enamel paint in alternate Yellow & Black Strips (5 Nos. Strip of 300 mm wide each) and remaining portion of Pole and Cross Arms, Cable Protection Pipe, Brackets, etc. treated with One Coat of Aluminium Paint, including writing of pole numbers with black synthetic enamel paint, complete all as specified and as directed by engineer-in-charge.

210

-

-

... More
S&F in-repair of MCCB 4 Pole, 415 Volts, 350 Amps, 50 Hz, conforming to IS/IEC 60898, with Thermal Magnetic release, overload, short circuit fault protection 3 phase, breaking capacity 36 KA, Ics=100% of Icu, with Spreader terminal of both ends, connecting and testing, complete all as specified and as directed by Engineer-in-charge.

1

-

-

... More
All as per Item No. 103 here-in-above, but for 250 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.

1

-

-

... More
All as per Item No. 103 here-in-above, but for 200 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.

1

-

-

... More
All as per Item No. 103 here-in-above, but for 160 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.

1

-

-

... More
All as per Item No. 103 here-in-above, but for 100 Amp capacity MCCB, breaking capacity 30 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
All as per Item No. 103 here-in-above, but for 63 Amp capacity MCCB, breaking capacity 30 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.

2

-

-

... More
M&L for earthing complete with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead of 32x6 mm by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 40 mm bore( light grade) and watering pipe 50 mm bore GI pipe (light grade) and chamber and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg. 50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excvation and earth work and removal of surplus soil complete all as shown in electrical plate no 3 of SSR PT 1, 2009 with charcoal dust and salt complete and earth lead connected to earthing test point (up to main switches, DBs) including taking down old damaged earthing, complete all as specified & testing on completion. NOTE:- (i) item includes the cost of 7.5 mtr length GI pipe for protection for GI earth lead. (ii) item rates includes the cost of 7.5 mtr GI earth lead.

6

-

-

... More
M&L for complete servicing, greasing of the pump motor sets of capacity upto 30 HP by dismantling from the position,unscrewing nut bolt, bushes, cleaning, greasing and replacement of unsv bushes, gasket, gland packing/water seals, oil ring, nut bolts of suitable size including re-assembling the same in position and connect to the both end terminal circuit testing and commissioning complete all as directed. (Note:- 1. Arrangement of necessary T&P items required for dismantaling and reassembling pump motor set shall be deemend to be included in the quoted rate. 2. Cost of new bushes, gasket, gland packing nut bolts etc shall be deemened to be included in the quoated rate.)

16

-

-

... More
S&F in repair Pressure gauge 100mm dia upto 10 Kg/cm2 rating complete with bolts, nuts and rubber insertions as required complete all as per specified and directed.

4

-

-

... More
M&L for dismantling centrifugal pump of capacity upto 15 HP from motor and inlet outlet GI pipes and taking out for workshop for repair of impeller,casing water seal, shaft etc complete all as specified and directed.

4

-

-

... More
M&L for dismantling centrifugal pump of capacity more than 15 HP upto 30 HP from motor and inlet outlet GI pipes and taking out for workshop for repair of impeller,casing water seal, shaft etc complete all as specified and directed.

1

-

-

... More
S&F in replacement of new ball bearing suitable for pump of capacity upto 15 HP as per existing make and model after dismentalling of old unsv ball bearing from motor as specified and directed.

4

-

-

... More
S&F in replacement of new ball bearing suitable for pump of capacity more than 15 HP upto 30 HP as per existing make and model after dismentalling of old unsv ball bearing from motor as specified and directed.

2

-

-

... More
S&F in replacement Fan blade suitable for upto 30 HP induction motor after dismentalling of old unsv from motor as specified and directed.

1

-

-

... More
S&F in replacement Shaft stainless steel along with key and check nut of induction motor any type after dismentalling of old unsv from pump motor as specified and directed.

1

-

-

... More
Material and labour for lifting up submersible pump set of capacity upto 30 HP including column pipe from bore well and re-lowering the same with replacement of damaged gasket, nut and bolts etc. after development of bore well / maint of submersible pumpset complete all as specified and directed.

1

-

-

... More
M&L for Developing tube well with air compressor of suitable capacity till the water is free from sandy/muddy and suitable for potable water quality all as specified and directed by Engineer-in-Charge. Note:- The unit rate include for arrangement of suitable capacity of air compressor, Diesel to run the compressor and related accessories, tools etc for developing of borewell. No extra payment shall be made on this account.

1

-

-

... More
Material and labour for yield test for the developed bore well by continuously pumping for 16 hours with 25% extra of as per capacity of submersible of respective borewell to determine safe pumping yield complete complete all as specified and directed.

1

-

-

... More
S&F in replacement of PVC insulated three core sheathed submersible flat cable of size 10 Sqmm for submersible pumps with copper conductor 1100 Volts grade conforming to IS:694/1990 ISI all as specified and directed.

100

-

-

... More
S&F in replacement of PVC insulated three core sheathed submersible flat cable of size 6 Sqmm for submersible pumps with copper conductor 1100 Volts grade conforming to IS:694/1990 ISI all as specified and directed.

60

-

-

... More
S&F in replacement of submersible safety wire for bearing of weight upto 500 Kg all as specified and directed.

100

-

-

... More
M&L for re-winding Submersible motor of capacity more 15 HP upto 30 HP after lifting up of submersible pump set including column pipe from bore well, disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire of same guage with necessary insulation materials including complete overhauling and lowering of submersible set with column pipe in the borewell with new nuts bolts gasket etc and necessary connection to the terminal complete all as directed. (Note :- Major spares if required will be paid under respective items mentioned below)

1

-

-

... More
M&L for re-winding of submersible motor of capacity uto 15 HP after lifting up of submersible pump set including column pipe from bore well, disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire of same gauge with necessary insulation materials including complete overhauling and lowering of submersible set with column pipe in the borewell with new nuts bolts gasket etc and necessary connection to the terminal complete all as directed. (Note :- Major spares if required will be paid under respective items mentioned below)

3

-

-

... More
Supply only Key for motor coupling

1

-

-

... More
Supply only CI clip thrust bearing locking part

1

-

-

... More
Supply only Pin for motor base part

1

-

-

... More
Supply only Pin for thrust bearing

1

-

-

... More
Supply only Cable clip for motor

1

-

-

... More
Supply only Cable seal rubber

1

-

-

... More
Supply only Gasket

1

-

-

... More
Supply only Stud for upper flange stainless steel

1

-

-

... More
Supply only Stud for lower flange

1

-

-

... More
M&L for re-winding of more than 15 HP upto 30 HP induction motor disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire with necessary insulation materials including change of Key for motor coupling, Gasket complete overhauling and re-fixing motor, pump on frame with new nuts bolts etc and necessary connection to the terminal complete all as directed.

1

-

-

... More
M&L for re-winding of capacity upto15 HP induction motor disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire with necessary insulation materials including change of Key for motor coupling, Gasket complete overhauling and re-fixing motor, pump on frame with new nuts bolts etc and necessary connection to the terminal complete all as directed.

3

-

-

... More
Taking out 100 mm bore GI/CI/MS Water main from trenches and staking at site complete all as directed.

42

-

-

... More
Supply ,fixing and testing of MS ERW pipe of nominal dia 100 mm in replacement of old unsv GI/MS pipe inclduing special supplied and laid complete as per IS 3589 (1981) having thickness 6.0mm complete all as speified and directed.(making of flanges, welding, tapering to desire shape, Rubber gasket all shall be deemend in the quoated rate)

20

-

-

... More
Supply, laying and testing ductile iron pressure pipe socket and spigot end, class K-7, confirming to IS-8329/2000 blast furnace slag cement with portland cement properties suitable for Push - on- joint with inside cement mortar lining, internal metallic zinc coationg and external black bitumen coating of size 100 mm dia duly ISI marked laid in trenches etc complete all as specified and directed.

22

-

-

... More
M&L for DI fittings for DI pipe flange/ spigot and socket of size 80 mm to 200 mm bore such as bends(any type,radius and angle) tapers any type (straight, bend, increasing,decreasing or double socket etc) Tee pieces single branch, 'Y' junction, double branch, cross(all sockets or socket and spigot) collars caps and plugs complete all as specified and directed.

40

-

-

... More
Supply & Fixing, jointing and testing of cast iron Non Return Valve (NRV) ISI mark (PN-1.6) of size 100 mm bore, without bypass arrangement, swing type, conforming to IS-5312, complete with nuts, bolts, washers and gaskets including taking out old unserviceable NRV, complete all as directed by Engineer-in-charge.

2

-

-

... More
Supply and Fix CI water type butterfly valve 100 mm dia without lugs, lever operated CI disc, EPDM rubber lining including taking down old u/s one.

4

-

-

... More
Supply & Fixing, jointing and testing of cast iron sluice Valve ISI mark (PN-1.6) of size 100 mm bore confirming to IS 14846-2000, flanged ends drilled having Stainless steel spindle with cast iron wheel at top complete with nuts, bolts, washers and gaskets including taking out old unserviceable sluice valves, complete all as specified and as directed by Engineer-in-charge.

8

-

-

... More
Supply and fix cast iron foot valve100 mm dia screwed type ISI marked, as per IS 4018, including necessary rubber gasket, nut bolt,and taking out the unserviceable foot valve complete all as directed.

1

-

-

... More
Dismantling and lowering down 5 mm thick pressed steel side plates of size 1.22m x 1.22m from pressed steel water tank on 40 feet staging, carefully without damage to other members after necessary unscrewing of bolts, nuts, washers etc including separating serviceable side plates and kept in safe custody for reuse in the same work complete all as specified and as directed by Engineer-in-charge.

14

-

-

... More
Dismantling and lowering down 6 mm thick pressed steel side plates of size 1.22m x 1.22m from pressed steel water tank on 40 feet staging, carefully without damage to other members after necessary unscrewing of bolts, nuts, washers etc including separating serviceable side plates and kept in safe custody for reuse in the same work complete all as specified and as directed by Engineer-in-charge.

16

-

-

... More
Supply, errection, hoisting and fixing of new pressed steel side plate of 1.22mx1.22m and 5 mm thick, made to required shape and drilling necessary holes for fixing of bolts and nuts in existing pressed steel water tank on 40 feet staging complete all as specified and as directed by Engineer-in-charge.

8

-

-

... More
Supply, errection, hoisting and fixing of new pressed steel side plate of 1.22mx1.22m and 6 mm thick, made to required shape and drilling necessary holes for fixing of bolts and nuts in existing pressed steel water tank on 40 feet staging complete all as specified and as directed by Engineer-in-charge.

10

-

-

... More
Fixing only old serviceable pressed steel side plate of size 1.22mx1.22m obtained from serial item No. 91 here-in-before of 5 mm thickness with nuts, bolts and washers in existing pressed steel water tank after proper cleaning with the help of wire brush on 40 feet staging complete all as specified and as directed by Engineer-in-charge.

6

-

-

... More
Fixing only old serviceable pressed steel side plate of size 1.22mx1.22m obtained from serial item No. 92 here-in-before of 6 mm thickness with nuts, bolts and washers in existing pressed steel water tank after proper cleaning with the help of wire brush on 40 feet staging complete all as specified and as directed by Engineer-in-charge.

6

-

-

... More
Dismantling and lowering down mild steel tie bar made out of angle iron size 65mm x 65mm x 6mm and 2.00 metre long each from pressed steel water tank on 40 feet staging without any damage to other members with necessary unscrewing of bolts, nuts and washers complete all as specified and as directed by Engineer-in-charge.

45

-

-

... More
Supply, errection, hoisting and fixing mild steel tie bars made out of angle iron of size 65mmx65mmx6mm and 3.00 metre long Each and drilling necessary holes for fixing of bolts & nuts in existing pressed steel water tank on 40 feet staging complete all as specified and as directed by Engineer-in-charge.

30

-

-

... More
Fixing only serviceable tie bars obtained from serial item No 97 above duly cleaned complete all as specified and as directed by Engineer-in-charge.

15

-

-

... More
Supply and fixing mild steel machine made nut and bolt 16-20 mm dia and not exceeding 5 cm long nuts and bolts with washers for fixing of steel plates, tie bars, etc. complete all as specified and as directed by Engineer-in-charge.

30

-

-

... More
Supply and fixing mild steel machine made nut and bolt 11-15 mm dia and not exceeding 5 cm long nuts and bolts with washers for fixing of steel plates, tie bars, etc. complete all as specified and as directed by Engineer-in-charge.

30

-

-

... More
M&L for fixing leak proof materials comprising of lead wire, glass wool and black putty in existing pressed steel tanks to ensure water tightness after taking out old existing jointing materials by burning with blow lamps and cleaning and jointing surface complete all as specified and as directed by Engineer-in-charge.

60

-

-

... More
M&L for construction of Brick Masonry Valve Pit, of size 1200mm X 1200mm X 1200mm (Internal dimension), one Brick thick wall in cement mortar 1:4 on 150mm thick PCC 1:4:8, type D-2 (40mm graded aggregate) in Foundation, Rendering 15mm thick in CM 1:4 internally upto full depth and externally upto 150mm below GL, providing 3mm thick MS black Sheet Valve Pit Cover, welded with 40X5mm Flat Iron Frame alround including provision of Hinges, Handle and Locking Arrangement and 50 x 50 x 6mm Angle Iron Frame fixed on Top of Valve Pit by means of Holdfast 150mm long, embedded in PCC 1:2:4 (20mm graded aggregate) Block of size 230 x 200 x 100 mm, applying two coats of Synthetic enamel Paint over a coat of Red Oxide Zinc Chrome Primer after preparation of all exposed to Steel Surfaces including necessary Earth Work in Soft/Loose Soil and demolition of existing damaged valve pit, complete all as directed by Engineer-in-charge.

2

-

-

... More
S&F in repair fully automatic star delta starter 30 HP in sheet metal encloser type MN with single phase protection feature, AC 3 Phase 415 Volt 50 Hz, complete all as specified and diredted by Engineer-in-charge. Make Havells/Standard/L&T/Harsh.

1

-

-

... More
S&F in repair fully automatic star delta starter 17.5 HP in sheet metal encloser type MN with single phase protection feature, AC 3 Phase 415 Volt 50 Hz, complete all as specified and diredted by Engineer-in-charge. Make Havells/Standard/L&T/Harsh.

3

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.