Military Engineer Services Tender
... More
BidAssist is a very user-friendly website which helps in finding the specific Assam e-tender that one is looking for. For getting any information or detail about any e-tender the Assam government must have posted, BidAssist is designed in such a manner so as to provide information on all government tenders in one place without any inconvenience.
Costs
EMD
₹ 56,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_698980_1Tender No
84128/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
Dismantling ACSR Conductor of any Size including PVC/ Fiber Line Separator/ Spacers of OH Electric Lines from Electric Poles, etc., complete all as specified and as directed.
2
-
-
... More
Dismantling Unserviceable/ Rusted GI Earth Wire, Cradles Guards of any Size from Electric Poles, etc., complete all as specified and as directed.
1
-
-
... More
Dismantling Stay Assembly complete of any description, complete all as specified and as directed.
NOTE : Unserviceable Stay Assembly will be Dismantled at Ground Level and Disturbed Ground will Made Good as directed for which Earth Work, Demolition Cement Concrete, etc. will not be Measured separately for Payment.
4
-
-
... More
Disconnecting & Taking down/ out Unserviceable LT Cable, UG/ Service Connection Cable of Size 16 Sqmm, 2.0/ 4.0 Core and any description from Poles, Trenches, Floors, Walls, GI Pipes, etc., complete all as specified and as directed.
NOTE : Necessary Earth Works will be Measured & Paid under appropriate Items.
300
-
-
... More
Disconnecting & Taking down/ out Unserviceable LT Cable, UG Cable of Size 25/ 35/ 50 Sqmm, 3½/4.0 Core and any description from Poles, Trenches, Floors, Walls, GI Pipes, etc., complete all as specified and as directed.
NOTE : Necessary Earth Works will be Measured & Paid under appropriate Items.
380
-
-
... More
Disconnecting & Taking down/ out Unserviceable LT Cable, UG Cable of Size 70/ 95 Sqmm, 3½ Core and any description from Poles, Trenches, Floors, Walls, GI Pipes, etc., complete all as specified and as directed.
NOTE : Necessary Earth Works will be Measured & Paid under appropriate Items.
260
-
-
... More
Disconnecting & Taking down/ out Unserviceable LT Cable, UG Cable of Size 120 Sqmm, 3½ Core and any description from Poles, Trenches, Floors, Walls, GI Pipes, etc., complete all as specified and as directed.
NOTE : Necessary Earth Works will be Measured & Paid under appropriate Items.
200
-
-
... More
Excavating in Trenches, not exc. 1.50 Metre Wide and Depth not exc. 1.50 Metre for Taking out/up and Laying of Water Mains, Cables, Electric Poles, etc., Forming Surfaces to required Foundation, etc. and getting out as in Soft/Loose Soil, complete all as specified and as directed.
277
-
-
... More
Excavating in Trenches, not exc. 1.50 Metre Wide and Depth exc. 1.50 Metre but not exc. 3.00 Metre for Electric Poles, etc., Forming Surfaces to required Foundation, etc. and getting out as in Soft/Loose Soil, complete all as specified and as directed.
0.28
-
-
... More
Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in layers not exc. 25 Cm, Providing Heaps along the Route of the Water Mains, Cable Lines, etc. with surplus Soil in Soft/Loose Soil, complete all as specified and as directed.
179
-
-
... More
Removing Excavated Materials (Soils) not exc. 50.00 Metre and depositing where directed at a level not exc. 1.50 Metre above the Starting Point in Soil, complete all as specified and as directed.
98
-
-
... More
M&L Horizontal Boring of Holes under Road, Pavement, Hardstanding by Trenchless Technology Using Ultra Sounding Technique/ Manual and necessary Machine/ T&P suitable for GI Pipe upto 80mm Bore (dia), complete all as specified and as directed.
NOTE : GI Pipe will be Measured & Paid for separately under appropriate Item.
24
-
-
... More
M&L Cutting on Existing Road not less than 0.50 Metre in Depth and not less than 0.30 Metre in Width including Make Good the same with Cement Concrete 1:3:6 (40mm graded stone aggregates) exc. 150mm thick and not exc. 200 mm on Top Layer after necessary Returning, Filling in, Well Ramming and Levelling in Layers to match the Existing Surface Levels after Filling of Cement Concrete, complete all as specified and as directed.
NOTE : Cement Concrete will be Measured & Paid for separately under appropriate Item.
18
-
-
... More
M&L Cement Concrete 1:4:8 (40mm graded stone aggregates) in Foundation, Filling and Mass Concrete, etc. including Use and Waste of Formwork as required/ ordered, complete all as specified and as directed.
NOTE : Cost of Formwork will deem to be included in the Quoted Unit Rate.
0.28
-
-
... More
M&L Cement Concrete 1:3:6 (40mm graded stone aggregates) in Foundation of Stay Assembly, Filling to Electric Poles, Trenches, etc. including Use and Waste of Formwork as required/ ordered, complete all as specified and as directed.
NOTE : Cost of Formwork will deem to be included in the Quoted Unit Rate.
4.29
-
-
... More
M&L Cement Concrete 1:2:4 (20mm graded stone aggregates) in Coping of Electric Poles, etc., Weathering Slightly Rounded or Chamfered Angle and Throating, Finishing all Exposed Faces of Concrete including Use and Waste of Formwork as required/ ordered, complete all as specified and as directed.
NOTE : Cost of Formwork will deem to be included in the Quoted Unit Rate.
0.37
-
-
... More
M&L Steel Tubular Swaged Pole Type 410 SP-22 (8.5 Metre long) complete with Mild Steel Base Plate, Finial Taper Plug, Bolts, Nuts & Screws, etc. as specified including One coat Aluminium Paint over One Coat of Red Oxide Zinc Chrome Primer, Providing 3 No. Band/ Strap with Paint Black/ Yellow Colour 300mm apart from Plinth Block and Numbering of Pole/ Painting embedded portion of Pole with One coat of Bituminous Paint, complete all as specified and as directed.
NOTE : Necessary Earth Works & Concrete Works will be Measured and Paid separately under relevant Items.
4
-
-
... More
M&L Cross Arms, Bracings, Supports, Clamps and Back Plates, Fabricated from Structural Steel Sections including Nuts, Bolts, Washers, etc., Welding, Bending Cold or Hot, Drilling Holes for Bolts, in any Shape or Size as indicated or directed and Applying Two Coats of Aluminium Paint over a Coat of Aluminium Oxide Primer after Preparation of Surfaces, complete all as specified and as directed.
2.5
-
-
... More
S&F Insulator Pin type, 50mm Height, 65mm dia for 550 Volt grade, Porcelain, Vitreous, White, Brown or Green including One Galvanised Mild Steel Spindle Two Galvanised Iron Washer and One Galvanised Iron Nut, complete all as specified and as directed.
40
-
-
... More
S&F Insulator Pin type, 150mm Height, 150mm dia for 11000 Volt grade, Porcelain, Vitreous, White, Brown or Green including One Galvanised Mild Steel Spindle Two Galvanised Iron Washer and One Galvanised Iron Nut, complete all as specified and as directed.
3
-
-
... More
S&F Disc type Insulator, Porcelain, Vitreous 145mm High and 255mm Dia Ball and Socket type, White, Brown or Green, Single Disc Assembly for Tension with Tension Clamps for Conductors, Working Pressure 11000 Volt grade, complete all as specified and as directed.
3
-
-
... More
M&L ACSR Conductor of any Size for LT Over Head Line including Stringing Conductor fixed on Poles and binding with Aluminium Binding Wire, etc., complete all as specified and as directed.
NOTE : Sizes of Conductor will be as per Site requirement/ as directed.
2
-
-
... More
S&F PVC/ Fiber Flat Spacer/ Separator 2/ 3 Wire System suitable for LT Over Head Line 1100 Volt Conductor for Horizontal/ Vertical Two No. in Span and Fixing with and including Aluminium Bolts, Nuts & Washers, complete all as specified and as directed.
60
-
-
... More
S&F PVC/ Fiber Separator 4/ 5 Wire System suitable for LT Over Head Line 1100 Volt Conductor for Horizontal/ Vertical Two No. in Span and Fixing with and including Aluminium Bolts, Nuts & Washers, complete all as specified and as directed.
85
-
-
... More
M&L Galvanised Iron Wire 3.15mm or 4.0mm dia as Continuous Earth Wire, Guards and Cradles (Hexagonal/ Rectangular), etc. and binding with and including GI Binding Wire 1.6mm dia, complete all as specified and as directed.
1
-
-
... More
M&L Stay Assembly Complete with all Accessories such as Mild Steel Galvanised Flat Iron Stay Clamp, Galvanised Stay Wire 7/3.15mm stranded, One Insulator Loop type Porcelain Vitreous (White, Brown or Green) Overall Dimension 90x140mm and Clear-ance of Hole 25.5mm, Stay Grips, Mild Steel Galvanised Stay Bow, Thimbles Galvanised Steel 14mm dia & 400mm long, 14mm dia Mild Steel Galvanised Stay Rod 1800mm long and Mild Steel Galvanised Stay Plate of Size 300x300x6.0mm all as shown in Electrical Plate No. 1 of MES Schedule Part-I, complete all as specified and as directed. NOTE : Necessary Earth Works and Cement Concrete Works will be Measured and Paid separately under appropriate Items.
4
-
-
... More
M&L Switch Air Break, Gang Operated of Current Rating upto 200 Amp, 11000 Volt, Triple Pole, Mechanically Operated mounted on Insulator and Steel Frame, with Operat-ing Mechanism Worked from Ground Level including Taking down/ out Unserviceable Switch Air Break, Gang Operated from any Situation, complete all as specified and as directed.
1
-
-
... More
M&L Drop out Expulsion Fuse upto 50 Amp, Single Pole suitable for 11000 Volt grade including Taking down/ out Unserviceable Drop out Expulsion Fuse from any Situation, complete all as specified and as directed.
3
-
-
... More
M&L HT Lightening Arrester of Discharging Capacity 65 kA, 11000 Volts grade, Expulsion type and complete with all Fittings including Taking down/ out Unserviceable Lightening Arrester from any Situation, complete all as specified and as directed.
3
-
-
... More
M&L Painting to Erected HT Steel Tubular Pole (11 Metre long) except Embedded Portion but including all Mild Steel Works viz Cross Arms, Channels, Flat Iron Clamps, etc. with Two Coats of Aluminium Paints, Providing 07 No. Bands/ Straps with Synthetic Enamel Paint (any tint 30 Cm Wide/ Height Each) from Top of Plinth/ Concrete Block and Writing Letters/ Pole Number not less than 50mm with different Tint in Black Ground, complete all as specified and as directed.
NOTE : Cost of any Arrangements/ Scaffolding required for Painting to Erected HT Steel Tubular Pole will deem to be included in the Quoted Unit Rate.
140
-
-
... More
S&F MCCB 63 Amp, 4 Pole, 16 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
3
-
-
... More
S&F MCCB 63 Amp, 4 Pole, 25 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
2
-
-
... More
S&F MCCB 100 Amp, 4 Pole, 25 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
4
-
-
... More
S&F MCCB 125 Amp, 4 Pole, 25 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
2
-
-
... More
S&F MCCB 160 Amp, 4 Pole, 25/27 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
2
-
-
... More
S&F MCCB 160 Amp, 4 Pole, 35/36 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
2
-
-
... More
S&F MCCB 200 Amp, 4 Pole, 25/27 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
1
-
-
... More
S&F MCCB 200 Amp, 4 Pole, 35/36 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
1
-
-
... More
S&F MCCB 250 Amp, 4 Pole, 35/36 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
1
-
-
... More
S&F MCCB 400 Amp, 4 Pole, 35/36 kA Breaking Capacity, 415 Volt, 50 Hz, fixed in Panel/ SS Enclosure including any type of Addition/ Alteration and Taking down/ out Unserviceable MCCB from Panel/SS Enclosure, complete all as specified and as directed
1
-
-
... More
S&F Change Over Switch with Open Execution, Current rating 200 Amp, 4 Pole, 415 Volt, Advance Neutral On-load, Front Operated fixed to Panel including any type of Addition/ Alteration and Providing Connection including Taking down/out Unserviceable Change Over Switch, complete all as specified and as directed.
1
-
-
... More
S&F Change Over Switch with MS Enclosure, Current rating 200 Amp, 4 Pole, 415 Volt, 4 Pole with Advance Neutral On-load, Front/ Side Operated, fixed with Walls/ Angle Iron including any type of Addition/ Alteration and Providing Connection including Taking down/out Unserviceable Change Over Switch, complete all as specified and as directed.
1
-
-
... More
S&F Change Over Switch with Open Execution, Current rating 250 Amp, 4 Pole, 415 Volt, Advance Neutral On-load, Front Operated fixed to Panel including any type of Addition/ Alteration and Providing Connection including Taking down/out Unserviceable Change Over Switch, complete all as specified and as directed.
1
-
-
... More
S&F Change Over Switch with MS Enclosure, Current rating 250 Amp, 4 Pole, 415 Volt, 4 Pole with Advance Neutral On-load, Front/ Side Operated, fixed with Walls/ Angle Iron including any type of Addition/ Alteration and Providing Connection including Taking down/out Unserviceable Change Over Switch, complete all as specified and as directed.
1
-
-
... More
S&F Change Over Switch with Open Execution, Current rating 400 Amp, 4 Pole, 415 Volt, Advance Neutral On-load, Front Operated fixed to Panel including any type of Addition/ Alteration and Providing Connection including Taking down/out Unserviceable Change Over Switch, complete all as specified and as directed.
1
-
-
... More
S&F Change Over Switch with MS Enclosure, Current rating 400 Amp, 4 Pole, 415 Volt, 4 Pole with Advance Neutral On-load, Front/ Side Operated, fixed with Walls/ Angle Iron including any type of Addition/ Alteration and Providing Connection including Taking down/out Unserviceable Change Over Switch, complete all as specified and as directed.
1
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 16 Sqmm, 2.0 Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
100
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 16 Sqmm, 4.0 Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
200
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 25 Sqmm, 3½ Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
150
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 35 Sqmm, 3½ Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
110
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 50 Sqmm, 3½ Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
120
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 70 Sqmm, 3½ Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
100
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 95 Sqmm, 3½ Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
160
-
-
... More
M&L XLPE insulated, Armoured, Heavy duty, Electric Cable with Aluminium Stranded Conductor, 1100 Volt grade, Cross Sectional Area 120 Sqmm, 3½ Core including Cable Glands, Lugs, etc. and Providing Electrical Connection, Laid in Trenches or Passing through Pipe or Fixing to Poles, Walls, etc., complete all as specified and as directed. NOTE : Necessary Earth Works, Sand Cushioning, Bricks, GI Pipe, etc. will be Measured and Paid separately under appropriate Items.
200
-
-
... More
M&L Sand Cushioning (Dry) in Trenches/Ducts for protection of UG Cables (below, above & around the UG Cable laid) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180mm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only will be Measured.
83
-
-
... More
Supply & laying Sub-class ‘B’ Bricks of Size 230x115x75 mm, Kiln burnt, for Covering to UG Cable as Mechanical Protection, laid Flat, Transversally Width Equal to the Length of the Cable, complete all as specified and as directed.
74.88
-
-
... More
M&L Galvanised Steel Tubing Pipe 40mm bore (dia), Light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts, etc., complete all as specified and as directed. NOTE : Necessary Earth Works will be Measured and Paid separately under appropriate Items.
15
-
-
... More
M&L Galvanised Steel Tubing Pipe 40mm bore (dia), Light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts and/or fixing to Electric Poles with and including suitable Size Mild Steel Flat Iron 40x4.0mm Clamps, Bolts, Nuts, Washers, etc., complete all as specified and as directed.
NOTE : Cost of Clamps, Bolts, Nuts, Washers, etc. will deem to be included in the Quoted Unit Rate.
15
-
-
... More
M&L Galvanised Steel Tubing Pipe 50mm bore (dia), Light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts, etc., complete all as specified and as directed.
NOTE : Necessary Earth Works will be Measured and Paid separately under appropriate Items.
6
-
-
... More
M&L Galvanised Steel Tubing Pipe 50mm bore (dia), Light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts and/or fixing to Electric Poles with and including suitable Size Mild Steel Flat Iron 40x4.0mm Clamps, Bolts, Nuts, Washers, etc., complete all as specified and as directed.
NOTE : Cost of Clamps, Bolts, Nuts, Washers, etc. will deem to be included in the Quoted Unit Rate.
6
-
-
... More
M&L Galvanised Steel Tubing Pipe 80mm bore (dia), Light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts, etc., complete all as specified and as directed. NOTE : Necessary Earth Works will be Measured and Paid separately under appropriate Items.
12
-
-
... More
M&L Cable Jointing Kit for 11 KV (Earthed) Grade Cable, INDOOR TERMINATION, Heat Shrink type complete with Jointing Materials and Accessories suitable for XLPE Armoured Aluminium Conductor Cable, Cross sectional Area 50 Sqmm to 95 Sqmm, 3 Core, Providing Connection and Testing, complete all as specified and as directed.
1
-
-
... More
M&L Cable Jointing Kit for 11 KV (Earthed) Grade Cable, OUTDOOR TERMINA-TION, Heat Shrink type complete with Jointing Materials and Accessories suitable for XLPE Armoured Aluminium Conductor Cable, Cross sectional Area 50 Sqmm to 95 Sqmm, 3 Core, Providing Connection and Testing, complete all as specified and as directed
1
-
-
... More
M&L Rectifying the any Leakage in Neutral/ EN Voltage by Checking Overhead Line, Jumpers, Underground Cable, MCB, MCCB with required Manpower to Reducing the Leakage in Permissible Limit and Balancing the 3 Phase Supply, complete all as specified and as directed.
20
-
-
... More
M&L Taking down HT Switch Gear (Vacuum Circuit Breaker) of Capacity 11 KV 250/ 350 MVA, Comprising of following Repairs, Overhauling, Servicing and Re-fixing the same after Repairs/Overhauling:-
(a) Tripping Off the Breaker, Lowering the Breaker with Raising/ Lowering Handle and Pulling Out the Breaker complete from the Panel alongwith the Trolley for Servicing/ Inspection/ Overhauling.
(b) Servicing/ Inspecting/ Checking of Automatic Safety Shutter Operation for Serviceability and Replacement of Spares if required.
(c) Servicing/ Inspecting/ Checking of Circuit Spout and Circuit Spout Connections for RYB Phases and Replacement of Spares if required.
(d) Dismantling & Checking of Cross Bar Assembly, Fixed Contacts and Current Carrying Parts of the Breaker, Trolley, Insulated Assembly and Checking Lamination with Clamps, Epoxy Spout, Isolator Assembly, etc.
(e) Setting, Re-assembling, Cleaning, Adjustment of Fixed Contacts, Main Contact, Arcing Contacts and Chamber Baffle Pot Assembly, Moving Contact for Proper Setting of Auxiliary Contacts Operating Mechanism.
(f) Servicing/ Inspecting/ Checking of Secondary Sockets/ Bus-bar, Earthing Plugs/ Earthing Sockets and Replacement of Spares if required.
(g) Checking, Setting and Adjustment of Lowering and Raising Operation of the Breaker Trolley.
(h) Lubrication & Greasing of All Moving Parts of the Trolley, Stopper Bolt for Proper Operating and Closing of Shutter Gear, Isolation Resistance of Trolley of with Vacuum Interrupter Assembly.
2
-
-
... More
(j) The Inspection of HT Switch Gear shall involve:- (i) Inspection of Truck & Hoist Assembly. (ii) Inspection of Tank Assembly & Barriers. (iii) Inspection of Assembly & Components of Solenoid Assembly. (iv) Inspection of Assembly & Components of Dependent Mechanism. (v) Inspection of Assembly & Components of Spring Box Mechanism. (vi) Inspection of Motor Mechanism Spring Charge Assembly. (vii) Inspection of Assembly of Trip Unit & Related Components.
NOTES :- (a) The Quoted Unit Rate will deem to be included for necessary T&P, Nuts, Bolts, Washers, Gasket, Insulation Tape, Compound, Two Coats Painting of VCB Panels with Approved Colour all as per existing, etc. to Put in to the VCBs and Panels in Serviceable Condition, Testing and Commissioning all as directed.
(b) Major Spares like Breaker Bushings, Vacuum Interrupter Assembly, Bus-bar Spout, Bus-bar Spout Connections, Circuit Spout/Circuit Spout Connections/ Buffer Fixed Contacts, Moving Contacts, Tank Assembly/ Barriers, Solenoid Spares, Dependent/ Spring Mechanism/ Motor Mechanism, Trip Unit, etc. will be Measured and Paid separately under appropriate Items of the SCHEDULE 'A' (BOQ/ PRICE SCHEDULE). However, the Quoted Unit Rate will deem to be included for any Other Minor Spares required for Replacement and Taking out of Unserviceable Parts from the HT Switch Gear (Vacuum Circuit Breaker).
-
-
-
... More
Supply only 110 Volt DC Tripping Coil for 11 KV HT Panel for Protection system, complete all as specified and as directed.
1
-
-
... More
Supply only 110 Volt Master Tripping Closing Coil suitable for 11 KV HT Panel, complete all as specified and as directed.
1
-
-
... More
Supply only Master Trip Relay suitable for 11 KV HT Panel for Protection System, complete all as specified and as directed.
1
-
-
... More
Supply only Maximum Demand Controller for LT/HT Supply with Parameters of V, A, F, KW, KVA, kVAr, kWh, kVAh, PF, Phase Angle Neutral Current, Max Demand, complete all as specified and as directed.
1
-
-
... More
Supply only LED Indication Lamps for VCB/ACB/LT Panel, complete all as specified and as directed.
5
-
-
... More
Supply only Spring Charging Motor with Gear Assembly for VCB, complete all as specified and as directed.
1
-
-
... More
Supply only Single Unit Resin Cast Type Current Transformer of Rating 11 KV, Ratio 30-15/5-5A, Burden 5P10 for Protection an 10VA for Metering, complete all as specified and as directed.
1
-
-
... More
Supply only Single Unit Resin Cast Type Potential Transformer of Rating 11 KV, Ratio 11KV/ √3/110V/√3 Burden 100VA, Pistol Type, complete all as specified and as directed.
1
-
-
... More
M&L Dismantling Cable Connections of 3 Pole/ 4 Pole Air Circuit Breaker of Capacity 800 Amp to 1250 Amp, 415 Volt, 50 Hz of Make : ABB/ C&S/ GE/ L&T, Strip Opening the Air Circuit Breaker, Inspecting the Parts for Serviceability/ Overhauling complete and Carrying out the following Repairs/ Maintenance Works :-
(a) Cleaning the Insulation Parts including Bushings with CTC Solution.
(b) Checking the Alignment and Condition of Movable & Stationary Contacts and Adjust them all as per Manufacturer's Instructional Manual.
(c) Check the Bolts, Nuts, Washers, Cotter Pins and All Terminal Connections are in Place and Tights. Replace the Worn-out Parts.
(d) Check Arching Contact for Damage.
(e) Clean and Lubricate the Operating Mechanism with a Light Machine Oil for Pins and Bearings and with a Non-Hardening Grease for the Wearing Surfaces. Adjust Breaker Operating Mechanism all as per Manufacturer's Instructional Manual.
(f) Checking/ Inspecting Shunt Trip Coil for Serviceability and Replacing the same if required. (g) Checking Control Device Free for Operation.
(h) Check after Servicing the Circuit Breaker to Verify the Contacts Move to the Fully Opened and Fully Closed Positions, that there is an Absence of Friction and that the Electrical Operation is Functional.
NOTE : The Quoted Unit Rate shall deem to be inclusive of T&P and Minor Spares like Lubricants, Bolts, Nuts, Washers, Pins, etc. Major Spares like Shunt Release & Trip Coil, etc. will be Measured & Paid separately under appropriate Items of the SCHEDULE 'A' (BOQ/ PRICE SCHEDULE). However, the Quoted Unit Rate will deem to be included for any Other Minor Spares required for Replacement and Taking out of Unserviceable Parts from the Air Circuit Breaker.
2
-
-
... More
Supply only Drawout Breaker suitable for Air Circuit Breaker of Capacity 800 Amp to 1250 Amp, complete all as specified and as directed.
1
-
-
... More
Supply only Fixed Arching Contact suitable for Air Circuit Breaker of Capacity 800 Amp to 1250 Amp, complete all as specified and as directed.
2
-
-
... More
Supply only Moving Arching Contact suitable for Air Circuit Breaker of Capacity 800 Amp to 1250 Amp, complete all as specified and as directed.
2
-
-
... More
Supply only Motor 240 V AC suitable for Air Circuit Breaker of Capacity 800 Amp to 1250 Amp, complete all as specified and as directed.
1
-
-
... More
Supply only Shunt Release (110/ 220 V DC or 240 V/ 415 V AC) suitable for Air Circuit Breaker of Capacity 800 Amp to 1250 Amp (all per existing Make), complete all as specified and as directed.
1
-
-
... More
Supply only Trip Coil suitable for Air Circuit Breaker of Capacity 800 Amp to 1250 Amp, complete all as specified and as directed.
1
-
-
... More
Supply only Under Voltage Release 240 V AC suitable for Air Circuit Breakers of Capacity 800 Amp to 1250 Amp (all per existing Make), complete all as specified and as directed.
1
-
-
... More
M&L Attending of 33/11 KV HT Breakdown and Finding the Fault in Transformers, VCBs, HT UG Cables, CTs, PTs, Lighting Arrestor, Insulator, etc. by Highly Skilled Mechanic to Replace any Spares related Breakdown, complete all as specified and as directed.
NOTE : Spares will be Measured & Paid separately under appropriate Items of the SCHEDULE 'A' (BOQ/ PRICE SCHEDULE).
4
-
-
... More
M&L Balancing Load on 3 Phases & Neutral of Transformer by Applying necessary Engineering efforts like Inter-changing of Jumpers, Inter-changing of Service Connections on Over Head Conductors in LT Feeder Pillar Boxes or any other such efforts to make a Balanced Distributions of Electrical Load on Transformer, required as per Site Conditions including Submission of Corrected Readings of Meters, complete all as specified and as directed.
NOTE : The Quoted Unit Rate will deem to be included the Cost of necessary Tools, Safety Devices and Plants required for the purpose.
15
-
-
... More
M&L Rewinding 433 Volt LV Coils of Voltage Stabilizer/ Isolation Transformer using Proper Size Super Enameled Copper Wire suitable for Working Voltage 1.1 KV including 3 Layer insulated Materials as per existing Size of Core including Testing and Commissioning, complete all as specified and as directed.
NOTE :-
(a) Oil Filtration, Supply of New Oil will be Measured & Paid separately under appropriate Items.
(b) All Petty Parts including Bolts, Nut, Gasket, Minor welding will deem to be included in the Quoted Unit Rate.
(c) Cost of Taking Out Unserviceable Parts/ Spares, Re-fixing after Repaired, Both Side Transportation, Lifting/ Unloading of Voltage Stabilizer/ Isolation Transformer by Crane/ Manual will deem to be included in the Quoted Unit Rate.
40
-
-
... More
Supply only Breather Assembly, Heavy Duty of Capacity 0.50 KG with Silica Gel Crystal, complete all as specified and as directed.
1
-
-
... More
Supply only Bushing with Insulator, Packing, Nut, Washers, etc. on HT Side suitable for 750 KVA Transformer, complete all as specified and as directed.
1
-
-
... More
Supply only Bushing with Insulator, Packing, Nut, Washers, etc. on LT Side suitable for 750 KVA Transformer, complete all as specified and as directed.
1
-
-
... More
Supply only Control Wiring of Voltage Stabilizer with suitable Size Wires, complete all as specified and as directed.
MAKE : AS PER OEM
1
-
-
... More
Supply only Connector 12 Pin suitable for Voltage Stabilizer, complete all as specified and as directed.
MAKE : AS PER OEM
1
-
-
... More
Supply only Dimmer suitable for 50 to 60 KVA Servo Voltage Stabilizer, complete all as specified and as directed.
1
-
-
... More
Supply only High Low Voltage Cut Off Circuit suitable for Voltage Stabilizer, complete all as specified and as directed.
MAKE : AS PER OEM
1
-
-
... More
Supply only Main Big Gear suitable for Voltage Stabilizer, complete all as specified and as directed.
MAKE : AS PER OEM
1
-
-
... More
M&L Reversible Servo Motor (3.0 KG) with RC, Single Phase, 230 Volts including Taking out Old Unserviceable/ Worn out Motor from the Voltage Stablizer, complete all as specified and as directed.
1
-
-
... More
M&L Servo Circuit Card (PCB) suitable for 50/60 KVA Voltage Stabilizer including Taking out Old Unserviceable/ Worn out Servo Circuit Card from the Voltage Stablizer, complete all as specified and as directed.
1
-
-
... More
Supply only Tap Changer Assembly suitable for 11/0.433 KV Transformer of Capacity 750 KVA including Replacing Worn out Connection Sleeves, Insulated Plates, Bolts, Nut, Washers including Testing after fixed, complete all as specified and as directed.
1
-
-
... More
Supply only Top Cover Gasket/ Cock Sheet suitable for 750 KVA Transformer, complete all as specified and as directed.
1
-
-
... More
Supply only Transformer suitable for 60/63 KVA Servo Voltage Stabilizer, complete all as specified and as directed.
1
-
-
... More
M&L Dehydration & Filtration of Transformer/ Stabilizer Oil to achieved 40 KV to 60 KV at 2.5mm Gap by Dehydration Plant (Transporting of Plant to Site of Work) including Testing of Sample before and after Dehydration, complete all as specified and as directed
NOTE :-
(a) Filtration of the Voltage Stabilizer/ Isolation Transformer Oil will be Carried out at Different Locations of the AF STN CHABUA.
(b) Reports Before Filtration & After Filtration to be submitted by Contractor.
(c) Oil for Topping Up will be Measured & Paid separately under appropriate Items of the SCHEDULE 'A' (BOQ/ PRICE SCHEDULE).
(d) Centrifuging Machine with all T&P and Testing Equipments required for Dehydration to be arranged by Contractor at his Own Arrangements and Cost.
600
-
-
... More
Supply & Toping Up Voltage Stabilizer/ Transformer with New Transformer Oil (in Sealed Barrel), Conforming to IS:335 Standard having Dielectric Strength 40 KV at 2.5mm Gap after Initial Dehydration, complete all as specified and as directed.
MAKE : CASTROL/ POWER TRUE/ SAVITA/ TRUOIL
250
-
-
... More
M&L Disconnecting & Taking out the Numeric/ Microprocessor Based Relay of any description from 11 KV HT Panel, Cleaning the Contacts, Calibrating the Relay by Conducting Secondary Injection Tests, Checking of Current Transformer, Rectification of Defects in Control Wiring for Proper Tripping of Circuit Breakers through CTs and Relay and Tripping Coils, Adjustment/ Setting to Plug and Time Multiplier Settings of the Relay to Achieve the Discrimination in Tripping, Tune/ Synchronise Upstream Breaker Relay Settings, Re-installation of Relay, Testing & Commissioning, complete all as specified and as directed.
1
-
-
... More
M&L Servicing & Repair/ Maintenance of Indoor type 100 KVAR APFC Panel Board, Checking Connections between Load Devices and Sensing Devices elsewhere located in separate Panel to Check Sequence of Supply and Set in Proper Condition including Removal of Defective Device such as CT Sensing Cable and Power Cable, Repair/ Replacement of Fuses, Fuse Link, Control Fuses, Push Button, LED Indicators, Auto Manual Selector Switch, Current Transformers, Checking/ Replacing of Defective Cable Lugs, Patch Work Welding, Replacement of Defective Door Hinges, Testing of Capacitor Panel obtaining in Board Power Factor to 0.95 to 0.98 Capacitor Panel, complete all as specified and as directed.
NOTE : Replacement of Major Items will be Measured & Paid separately under appropriate Items of the SCHEDULE 'A' (BOQ/ PRICE SCHEDULE). However, the Quoted Unit Rate will deem to be included for any Other Minor Spares required for Replacement and Taking out of Unserviceable Parts from the APFC Panel Board.
1
-
-
... More
Supply only HRC Fuse 160 Amp, complete all as specified and as directed.
3
-
-
... More
Supply only HRC Fuse 200 Amp, complete all as specified and as directed.
2
-
-
... More
Supply only HRC Fuse 250 Amp, complete all as specified and as directed.
7
-
-
... More
Supply only Power Factor Improvement Static Condenser of Size 5 KVR (Capacitors) of required Capacity, complete all as specified and as directed.
2
-
-
... More
M&L Disconnecting Electrically Switch Boards/ Electric Panels/ Distribution Boards of any Size by Taking Proper Electric Shut Down, Opening Cables from MCCBs/ DBs/ Main Switches/ Panels, Cutting of Unserviceable/ Over-heated Cable Ends/ Thimbles, etc. and Providing New Aluminium Lugs/ Copper Lugs of any Size up to 630 Sqmm as per requirement at Site of Work, Insulation of all Necked Wires as per Existing Colour Code, Re-fixing/ Re-assembling as per Existing System complete all as specified and as directed.
NOTE :-
(a) Any Addition/ Alteration required for Fixing of Parts will deem to be included in the Quoted Unit Rate.
(b) Cost of all Consumable Items such as Thimbles, Lugs, Control Wire up to 10.00 RM will deem to be included in the Quoted Unit Rate.
5
-
-
... More
Supply only Power Contactor MCX-31, 4 Pole (as per existing/ as approved), complete all as specified and as directed.
1
-
-
... More
Supply only Power Contactor MCX-32, 3/ 4 Pole (as per existing/ as approved), complete all as specified and as directed.
2
-
-
... More
Supply only Power Contactor MCX-32, 4 Pole (as per existing/ as approved), complete all as specified and as directed.
1
-
-
... More
Supply only Power Contactor MCX-34, 4 Pole (as per existing/ as approved), complete all as specified and as directed.
2
-
-
... More
Supply only Digital Ammeter 0-400 Amp (with CT of suitable Ratio) including Providing necessary Electrical Connections (to accommodate in Panel Board), complete all as specified and as directed.
4
-
-
... More
Supply only Digital Voltmeter 0-500 Volt including Providing necessary Electrical Connections (to accommodate in Panel Board), complete all as specified and as directed.
4
-
-
... More
Supply, Installation, Testing & Commissioning LT Panel, Factory Made (CPRI Tested / Certified/Approved Manufacturer), Outdoor type, made out of 3.15mm thick Mild Steel Sheet and suitable Size Mild Stee Angle Iron Frame Work, Floor mounted Indoor, Cubical type suitable for 415 Volt, 3 Phase 4-Wire, 50 Hz AC Supply system, Dust and Vermin Proof, IP-65 Protection having suitable Bus-bar Chamber with suitable insulated Aluminium Bus-bars installed on Porcelain Insulators, Powder Coated Finish over One Coat of Red Oxide Zinc Chrome Primer on Outside and Two Coats of Red Oxide Zinc Chrome Primer on Inside, both Front & Rear Opening type with Aprons for Cable Entry with Double Door Shutter having Locking Arrangement, Internally Wiring with PVC insulated Solid Copper Conductor FRLSH Cable of adequate Size including Taking down/ out Unserviceable Panel, Comprising with the followings, complete all as specified and as directed :-
1
-
-
... More
INCOMING :
(a) Aluminium Bus-bar 300 Amp rating suitable for Incomer & Outgoing - 01 Set MCCBs/ Change Over Switch
(b) MCCB 160 Amp, 4 Pole, 415 Volt, 35/36 kA Breaking capacity, with - 01 No. (Ics=100 % of Icu) (c) Onload Change Over Switch, 160 Amp, 440 Volt, 3 Phase, 4 Pole, - 01 No. 50 Cycle with Allied Accessories (Panel Execution type)
(d) Multi-Function Panel Meter, Square type to Measure Three/Single Voltage - 01 Job Phase, Load Current, Frequency, Power Factor kWh including CT/PT of suitable ratio
(e) LED Indicator Lamp (R-Y-B) of Set of Three - 01 Set
OUTGOING :
(f) MCCB 100 Amp, 4 Pole, 415 Volt, 25/27 kA, (Ics=100 % of Icu) - 01 No.
(g) MCCB 63 Amp, 4 Pole, 415 Volt, 25/27 kA, (Ics=100 % of Icu) - 02 No.
(h) MCCB 40 Amp, 4 Pole, 415 Volt, 25/27 kA, (Ics=100 % of Icu) - 02 No.
(j) MCB 32 Amp, 4 Pole, 415 Volt, 'C' Curve, 10 kA - 02 No.
(k) MCB 32 Amp, DP, 240 Volt, 'C' Curve, 10 kA - 02 No.
-
-
-
... More
Supply & Laying Synthetic Rubber Insulated Mat 2000x1000x2.5mm thick suitable for Voltage upto 11 KV for Electrical Purpose as per IS:15652-2006, (Superseding IS:5424) suitable for Electrical Shock Safety, complete all as specified and as directed.
2
-
-
... More
M&L Earthing Complete with Galvanised Earth Plate Electrode 600x600x6.0mm thick buried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, Connected with and including Galvanised Earth Strip of Size 32x6.0mm by means of Bolts, Nuts, Check nuts and Washers of GI or Steel and connected Earthing Testing Point/Bus-bar with GI 40mm bore (dia) ‘Light’ grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregates) and Pre-cast RCC 1:2:4 (20mm graded stone aggregates) Cover Slab of Size 450x450x50mm, Reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, PGI Funnel with GI Watering Pipe 20mm bore (dia) ‘Medium’ grade including necessary Excavation in Soft/Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including Taking down/ out Unserviceable Earthing of any description, complete all as per specified and as directed. NOTE :-
(a) All Joints should be joined by Exothermic Welding or Brazing.
(b) Earthing Strip upto 7.5 RM will deem to be included in Quoted Unit Rate. However Earthing Strip beyond 7.5 RM will be Measured & Paid separately.
(c) Quoted Unit Rate by the Tenderer will deem to be included Salt & Charcoal upto and above 450mm Top of Earth Plate. (d) Earth Resistance of Earth Pit should be less than 5.0 Ohm. On Testing after Completion if the desired Earth Resistance is not obtained the Earthing will be redone at no Extra Cost.
8
-
-
... More
M&L Earthing Complete with Copper Earth Plate Electrode 600x600x6.0mm thick buried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, Connected with and including Copper Earth Strip of Size 32x6.0mm by means of Bolts, Nuts, Check nuts and Washers of Copper and connected Earthing Testing Point/Bus-bar with GI 40mm bore (dia) ‘Light’ grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt in alternate layers of not exc. 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregates) and Pre-cast RCC 1:2:4 (20mm graded stone aggregates) Cover Slab of Size 450x450x50mm, Reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, PGI Funnel with GI Watering Pipe 20mm bore (dia) ‘Medium’ grade including necessary Excavation in Soft/Loose Soil, Returning, Filling in and Removal of surplus Spoil upto a distance of 50.00 Metre and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including Taking down/ out Unserviceable Earthing of any description, complete all as per specified and as directed. NOTE :-
(a) All Joints should be joined by Exothermic Welding or Brazing.
(b) Earthing Strip upto 7.5 RM will deem to be included in Quoted Unit Rate. However Earthing Strip beyond 7.5 RM will be Measured & Paid separately.
(c) Quoted Unit Rate by the Tenderer will deem to be included Salt & Charcoal upto and above 450mm Top of Earth Plate. (d) Earth Resistance of Earth Pit should be less than 2.0 Ohm. On Testing after Completion if the desired Earth Resistance is not obtained the Earthing will be redone at no Extra Cost.
2
-
-
... More
S&F Galvanised Iron Strip 32x6.0mm with Saddles and Fixing Screws for Conductors/ Earth Lead including Brazing/ Welding and Bolts, Nuts & Washers, Bolt Jointing at all Joints for Building/ Equipments, laid through Pipe/ Trench/ Surface, complete all as specified and as directed.
20
-
-
... More
S&F Copper Strip 32x6.0mm with Saddles and Fixing Screws for Conductors/ Earth Lead including Brazing/ Welding and Bolts, Nuts & Washers, Bolt Jointing at all Joints for Building/ Equipments, laid through Pipe/ Trench/ Surface, complete all as specified and as directed.
15
-
-
... More
M&L Recharging Earthing by Filling of Common Salt in Earthing Pit complete all as specified and as directed.
NOTE : Recharging Materials will be Soluble in Water and to be Filled/ Poured in Earth Pit after Mixing with Water in Appropriate Quantity.
30
-
-
... More
M&L Recharging Earthing by Filling of Magnesium Sulphate, 100% Water Soluble Fertilizer Type in Earthing Pit complete all as specified and as directed.
NOTE : Recharging Materials will be Soluble in Water and to be Filled/ Poured in Earth Pit after Mixing with Water in Appropriate Quantity.
15
-
-
... More
DEDUCTION AGAINST SCHEDULE OF CREDIT
Bidder(s) shall/ will Quote the EQUAL AMOUNT as per SCHEDULE OF CREDIT catered at SERIAL PAGE No. 26 in the Tender Documents under Column 5 i.e. 'UNIT RATE' (M) against Row No. 138 .
1
-
-142450
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%