Military Engineer Services Tender
BidAssist is a very user-friendly website which helps in finding the specific Assam e-tender that one is looking for. For getting any information or detail about any e-tender the Assam government must have posted, BidAssist is designed in such a manner so as to provide information on all government tenders in one place without any inconvenience.
Costs
EMD
₹ 1,00,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_685863_1Bid Award Id
ViewTender No
8842/E8/2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://defproc.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply only indicator lamp suitable for APFC panel of any capacity as per existing, complete all as specified and as directed by Engineer-in-charge.
2
-
-
... More
Supply only power contractor for capacitor suitable for APFC panel of any capacity as per existing, complete all as specified and as directed by Engineer-in-charge.
3
-
-
... More
M&L for rack out of unserviceble ACB (Air circuit breaker) 800 amp, 415 volt , 50 Hz rating from the panel and servicing, repair/ replacement of unserviceble spare parts and rack in at the same position after repair including testing the ACB upto full satisfaction complete all as specified and as directed by engr-in-charge. Note :- worn out spare parts measured and paid separetely
2
-
-
... More
Supply only UV released suitable for air circuit braker (ACB) of 800 Amps rating, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
Supply only Shunt coil suitable for air circuit braker (ACB) of 800 Amps rating, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
Supply only Closing coil suitable for air circuit braker (ACB) of 800 Amps rating, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
Supply only normal type relay suitable for air circuit braker (ACB) of 800 Amps rating, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
M&L for scratching of rust with sand paper, cleaning of dust and making proper eletric connections in old existing LT panels and painting the same with synthetic enamel paint as per existing colour with the help of spray gun complete all as specified and as directed by engr-in-charge.
10
-
-
... More
S&F in-repair of digital type VAF meter 3 ph including all necessary connections complete all as specified and as directed by engineer-in-charge.
4
-
-
... More
Overhauling compressor set of capacity upto 3 HP with dismentling air line,motor, electric connectons, belt,etc. Replacing belts,replacement of bearings, replacement of compressor oil,oil seal, sevicing of sefty valves, servicing of cylinder. Reconnection of the motor and painting cylenders, air tank and pipe line with one coat of paint with spray painting also connecting the existing cable etc. including testing the compressor set for full satisfaction of in-charge complete all as specified and directed.
2
-
-
... More
M&L for laying 25mm dia (Outer) 3- layer PP-R (Polypropylene random copolymer) pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply with all PP-R plain & brass threaded fittings laid in trenches/ fixed to wall including taking down the existing old unserviceable CI/GI/PP-R pipe and testing, complete all as specified and as directed by Engineer-in-charge.
24
-
-
... More
S&F in-repair of fan belt for air compressor complete all as specified and as directed by engr-in-charge
2
-
-
... More
S&F in-repair of pressure switch, range between 35.5-135 PSI for air compressor complete all as specified and as directed by engr-in-charge
2
-
-
... More
Supply & laying of LT XLPE insulated cable, sheathed, screened, PVC bedded, Galvanised Steel Strip or Wire armoured, Electic Power Cable (heavy duty) with Aluminium Conductor, 1100 Volts grade, cross-sectional area 400 Sqmm 3.5 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/ under Road/ fixing on pole/ above floor including Testing and taking down the existing old unserviceable cable, complete all as specified and as directed by Engineer-in-charge. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.
100
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 240 Sqmm 3.5 Core, complete all as specified and as directed by Engineer-in-charge.
196
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 185 Sqmm 3.5 Core, complete all as specified and as directed by Engineer-in-charge.
380
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 95 Sqmm 3.5 Core, complete all as specified and as directed by Engineer-in-charge.
65
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 70 Sqmm 3.5 Core, complete all as specified and as directed by Engineer-in-charge.
515
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 50 Sqmm 3.5 Core, complete all as specified and as directed by Engineer-in-charge.
250
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 35 Sqmm 3.5 Core, complete all as specified and as directed by Engineer-in-charge.
325
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 25 Sqmm 3.5 Core, complete all as specified and as directed by Engineer-in-charge.
270
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 25 Sqmm 4.0 Core, complete all as specified and as directed by Engineer-in-charge.
390
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 16 Sqmm 4.0 Core, complete all as specified and as directed by Engineer-in-charge.
315
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 16 Sqmm 2.0 Core, complete all as specified and as directed by Engineer-in-charge.
610
-
-
... More
All as per Item No. 17 here-in-above, but for cross-sectional area 10 Sqmm 2.0 Core, complete all as specified and as directed by Engineer-in-charge.
130
-
-
... More
M& L for Excavation in trenches n.exc 1.5m wide and n.exc 1.5 m in depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc. and getting out in soft/loose soil complete all as per specified and as directed by Engineer-in-charge.
552
-
-
... More
M&L for Returning, filling in, including spreading, leveling, watering and well ramming in layers n exc 25cm complete all as per specified and as directed by Engineer-in-charge.
346
-
-
... More
M&L for Removing excavated material not exc. 50 m & depositing where directed at a level not exc. 1.5 m above starting point complete all as per specified and as directed by Engineer-in-charge.
206
-
-
... More
M&L for Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 230mm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180mm thickness, complete all as per specified and as directed by Engineer-in-charge. NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only will be measured and paid for.
166
-
-
... More
Supply & Laying Fly Ash Bricks, laid breadth wise along the length of cable laid in trenches over sand cushion laid for UG cable protection, complete all as specified and as directed by Engineer-in-charge.
16.56
-
-
... More
S&F in-repair of Galvanised Iron Pipe 40mm bore (dia) ‘light grade’ for protection of UG Cable, laid under Floors or Road Crossing, fixing to Pole with and including Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and as directed by Engineer-in-charge. NOTE- Cost of Mild Steel Clamps, Nuts, Bolts, etc. shall deemed to be included in unit quoted rate.
56
-
-
... More
All as per Item No. 34 here-in-above, but for 50mm bore (dia) GI Pipe, complete all as specified and as directed by Engineer-in-charge.
54
-
-
... More
All as per Item No. 34 here-in-above, but for 80mm bore (dia) GI Pipe, complete all as specified and as directed by Engineer-in-charge.
54
-
-
... More
M&L for boring holes horizontally under road without damaging the road surface with the help of GI tubing not exc. 80mm bore dia for passing of UG cable, complete all as specified and directed by Engineer-in-charge. NOTE: GI Pipe will be measured and paid separately.
24
-
-
... More
M&L for Aluminium conductor steel reinforced (ACSR) (size and type as required at site) drawn for overhead lines with permissible sags and providing jumper with and including copper binding wire or aluminium tapes, including stringing, tightening, etc., including dismantling the existing old unserviceable ACSR, complete all as specified and directed by Engineer-in-charge. NOTE:- Cost of binding wire is deemed to be included in unit quoted rate.
2
-
-
... More
Labour only for releasing Aluminium conductor steel reinforced (ACSR) (any size and type) of existing OH lines by un-binding from insulator of any description, re-fixing after stretching, re-stringing the conductor, removing excess sag, maintaining proper distance between conductors as ordered and binding with insulator with aluminium binding wire, complete all as specified and directed by Engineer-in-charge. NOTE:- Cost of binding wire is deemed to be included in unit quoted rate.
0.8
-
-
... More
S&F in-repair of Stay assembly of 16mm dia 1.18m long stay rod complete with all accessories as shown in electrical plate No. 1, size of plate 230x230x6mm, complete all as specified and directed by Engineer-in-charge. Note:- Cost of 01 no 65 x 90mm porcelain, vitreous, white, brown or green Loop type insulator, Galvanised stay strand of 7/3.15mm size upto 7.50m long stay strands with clamps and bolts, excavation and concrete shall deemed to be included in unit quoted rate.
2
-
-
... More
S&F in-repair of MCCB 4 Pole, 415 Volts, 630 Amps, 50 Hz, conforming to IS/IEC 60898, with Thermal Magnetic release, overload, short circuit fault protection 3 phase, breaking capacity 50 KA, Ics=100% of Icu, with Spreader terminal of both ends, connecting and testing, complete all as specified and as directed by Engineer-in-charge.
3
-
-
... More
All as per Item No. 41 here-in-above, but for 400 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
All as per Item No. 41 here-in-above, but for 350 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
All as per Item No. 41 here-in-above, but for 250 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
3
-
-
... More
All as per Item No. 41 here-in-above, but for 200 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
All as per Item No. 41 here-in-above, but for 160 Amp capacity MCCB, breaking capacity 36 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
All as per Item No. 41 here-in-above, but for 125 Amp capacity MCCB, breaking capacity 25 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
All as per Item No. 41 here-in-above, but for 100 Amp capacity MCCB, breaking capacity 25 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
2
-
-
... More
All as per Item No. 41 here-in-above, but for 63 Amp capacity MCCB, breaking capacity 25 KA, Ics=100% of Icu, complete all as specified and as directed by Engineer-in-charge.
2
-
-
... More
S&F in-repair of open execution On load Changeover Switch with advanced neutral switch, Four Pole (FP), 63 Amps, 415 Volts, conforming to IS/IEC 60947-3 with and including all accessories, connecting up and re-fixing of cables with proper lugs, complete all as specified and as directed by Engineer-in-charge.
2
-
-
... More
All as per Item No. 50 here-in-above, but for 100 Amp capacity Changeover Switch, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
S&F in-repair of aluminium lug suitable for making connection of aluminium armoured xlpe cable of size upto 25 Sqmm, complete all as specified and as directed by Engineer-in-charge.
450
-
-
... More
All as per Item No. 52 here-in-above, but for cable size 35-95 Sqmm, complete all as specified and as directed by Engineer-in-charge.
40
-
-
... More
All as per Item No. 52 here-in-above, but for cable size 120-185 Sqmm, complete all as specified and as directed by Engineer-in-charge.
40
-
-
... More
All as per Item No. 52 here-in-above, but for cable size 240-400 Sqmm, complete all as specified and as directed by Engineer-in-charge.
30
-
-
... More
S&F in-repair of straight through joint comes with cold applied unique mastic coated insulating tape and heat shrinkable wrap around sleeve suitable for voltage up to 1.1 KV 16 to 50 sqmm 3.5 core XLPE cable size complete all as specified and as directed by engr-in-charge. Make - Denson/3-M/ Raychem/ Seimens
1
-
-
... More
All as per Item No. 56 here-in-above, but for cable size 70-185 Sqmm, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
S&F in-repair of Cable end termination kit for 1.1 KV (Earthed) graded cable for Indoor/Outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 16 sqmm to 50 sqmm, complete all as specified and as directed. Make - Denson/3-M/ Raychem/ Seimens
1
-
-
... More
All as per Item No. 58 here-in-above, but for cable size 70-185 Sqmm, complete all as specified and as directed by Engineer-in-charge.
1
-
-
... More
M&L for PCC 1:3:6 type C-2 (40mm graded stone aggregate) as in foundations, fillings and mass concrete with and including necessary formworks, complete all as per specified and as directed by Engineer-in-charge.
5
-
-
... More
M&L for earthing complete with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead of 32x6 mm by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 40 mm bore( light grade) and watering pipe 20 mm bore GI pipe (medium grade) and chamber and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg. 50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excvation and earth work and removal of surplus soil complete all as shown in electrical plate no 3 of SSR PT 1, 2009 with charcoal dust and salt complete and earth lead connected to earthing test point (up to main switches, DBs) including taking down old damaged earthing, complete all as specified & testing on completion. NOTE:- (i) item includes the cost of 1.5 mtr length GI pipe for protection for GI earth lead. (ii) item rates includes the cost of 7.5 mtr GI earth lead.
19
-
-
... More
All as per Item No. 61 here-in-above, but for 4mm dia GI earth lead protected by 15mm dia GI pipe (light grade), complete all as specified and as directed by Engineer-in-charge.
4
-
-
... More
Supply, installation, testing and commissioning in-replacement of Factory made (CPRI Approved) floor mounted Outdoor cubical type LT Panel Board of size 1300 X 900 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 5 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry and exit from bottom with cable glands and gaskets, earth strip connections, Digital VAF Meter- 01 Set (Make- L&T/ Schneider/ Legrand/ Siemens), including LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN aluminium bus bars of capacity 600 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internally including necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-
(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 600 Amps with colour coding for RYB & N - 01 Set
INCOMING
(d) MCCB 450 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
OUT GOING
(e) MCCB 250 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
(f) MCCB 100 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos. (g) MCCB 63 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No. (h) MCCB 40 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication).
1
-
-
... More
Supply, installation, testing and commissioning in-replacement of Factory made (CPRI Approved) floor mounted Outdoor cubical type LT Panel Board of size 1300 X 900 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 5 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry and exit from bottom with cable glands and gaskets, earth strip connections, Digital VAF Meter- 01 Set (Make- L&T/ Schneider/ Legrand/ Siemens), including LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN aluminium bus bars of capacity 600 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internally including necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-
(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 600 Amps with colour coding for RYB & N - 01 Set
INCOMING
(d) MCCB 450 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
OUT GOING
(e) MCCB 250 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
(f) MCCB 160 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No. (g) MCCB 100 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No. (h) MCCB 63 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication).
1
-
-
... More
Supply, installation, testing and commissioning in-replacement of Factory made (CPRI Approved) platform mounted indoor cubical type LT Panel Board of size 1000 X 800 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 5 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry and exit from bottom with cable glands and gaskets, earth strip connections, Digital VAF Meter- 01 Set (Make- L&T/ Schneider/ Legrand/ Siemens), including LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN aluminium bus bars of capacity 630 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internally including necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-
(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 630 Amps with colour coding for RYB & N - 01 Set
INCOMING
(d) MCCB 320 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 50KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
OUT GOING
(e) MCCB 250 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
(f) MCCB 125 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos. (g) Manual type on load Changeover switch of 125 Amp, 4 Pole, 415 Volts-01 No (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication).
1
-
-
... More
Supply, installation, testing and commissioning in-replacement of Factory made (CPRI Approved) platform mounted outdoor cubical type LT Panel Board of size 900 X 700 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 5 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry and exit from bottom with cable glands and gaskets, earth strip connections, Digital VAF Meter- 01 Set (Make- L&T/ Schneider/ Legrand/ Siemens), including LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN aluminium bus bars of capacity 400 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internally including necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-
(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 400 Amps with colour coding for RYB & N - 01 Set
INCOMING
(d) MCCB 125 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos.
OUT GOING
(e) MCCB 63 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 30KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos.
(f) MCCB 20 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 30KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos. (g) MCB Triple Pole & Neutral (TPN) 40 Amp, C Curve, 415 Volts rating specially fixed out going supply (Breaking capacity 10KA)-01 No. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication).
1
-
-
... More
Supply, installation, testing and commissioning in-replacement of Factory made (CPRI Approved) platform mounted outdoor cubical type LT Panel Board of size 900 X 700 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 5 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry and exit from bottom with cable glands and gaskets, earth strip connections, Digital VAF Meter- 01 Set (Make- L&T/ Schneider/ Legrand/ Siemens), including LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN aluminium bus bars of capacity 200 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internally including necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-
(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 200 Amps with colour coding for RYB & N - 01 Set
INCOMING
(d) MCCB 125 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
OUT GOING
(e) MCCB 63 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
(f) MCB Single Pole & Neutral (SPN) 63 Amp, C Curve, 240 Volts rating specially fixed out going supply (Breaking capacity 10KA)-04 Nos. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication).
1
-
-
... More
Supply, installation, testing and commissioning in-replacement of Factory made (CPRI Approved) floor mounted Outdoor cubical type LT Panel Board of size 1300 X 900 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 5 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry and exit from bottom with cable glands and gaskets, earth strip connections, Digital ammeter 0-500 Amps with selector switch (Make- L&T/ Siemens/ Schneider/ Legrand), digital voltmeter of 500Volts with selector switch (Make- L&T/ Siemens/ Schneider/ Legrand) and LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN aluminium bus bars of capacity 400 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internally including necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-
(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 400 Amps with colour coding for RYB & N - 01 Set
INCOMING
(d) MCCB 250 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
OUT GOING
(e) MCCB 160 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
(f) MCCB 100 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos. (g) MCCB 40 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
(h) MCB Single Pole & Neutral (SPN) 16-32 Amp, C Curve, 240 Volts rating specially fixed out going supply (Breaking capacity 10KA)-06 Nos. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication).
1
-
-
... More
Supply, installation, testing and commissioning in-replacement of Factory made (CPRI Approved) floor mounted Outdoor cubical type LT Panel Board of size 1000 X 800 X 450 MM fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 5 mm frame totally enclosed dust and vermin proof both side hinge opening arrangement on front and back, centre openable double door with locking arrangements, cable entry and exit from bottom with cable glands and gaskets, earth strip connections, Digital ammeter 0-500 Amps with selector switch (Make- L&T/ Siemens/ Schneider/ Legrand), digital voltmeter of 500Volts with selector switch (Make- L&T/ Siemens/ Schneider/ Legrand) and LED indicating lamps- 03 Nos (Make- L&T/ Schneider/ Legrand/ Siemens), internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN aluminium bus bars of capacity 400 Amps shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including powder coat painting (RAL-7032) on the surfaces externally & internally including necessary preparation of surfaces and providing PCC (1 : 3 : 6) type C-2 as in foundation all as specified and as directed, comprising of the following :-
(a) Internal wiring with single core copper conductor cable/ PVC Insulated Copper Strip of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(b) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job. (c) Bus bar chamber comprising 04 Nos aluminium strip bus bar mounted on DMC ( Dough Moulding Compound) insulator and PVC sheathed of capacity 400 Amps with colour coding for RYB & N - 01 Set
INCOMING
(d) MCCB 250 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed incoming supply (Breaking capacity 36KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
OUT GOING
(e) MCCB 125 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-01 No.
(f) MCCB 63 Amp, 4 Pole , 415 Volts rating with, overload, short circuit fault protection 3 phase with neutral link specially fixed out going supply (Breaking capacity 25KA)Ics=100% of Icu, with Spreader terminal of both side-02 Nos. (g) MCB Triple Pole & Neutral (TPN) 32 Amp, C Curve, 240 Volts rating specially fixed out going supply (Breaking capacity 10KA)-01 No. (Note-Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication).