Military Engineer Services Tender
BidAssist is a very user-friendly website that helps us to explore all the new opportunities so as to achieve growth in our business. It helps us to attain all the information with respect to any e-tender the Arunachal Pradesh government has posted on its website in a very hassle-free manner.
Military Engineer Services - MES Tender
Eprocure
Opening Date18 Jun 2021
Closing Date15 Jul 2021
Tender Amount₹ 17,16,935 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 41,600Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_MES_452660_1Bid Award Id
ViewTender No
84003E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
170
-
-
... More
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 35 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
300
-
-
... More
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 2 core, nominal cross sectional area of main conductor 10 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
140
-
-
... More
Supplying & laying including taking town in trenches, in road cutting and along pole 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
50
-
-
... More
Supplying & laying including taking down in trenches, in road cutting and along pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
20
-
-
... More
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
167
-
-
... More
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
150
-
-
... More
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
64
-
-
... More
M & L for laying of bricks locally available sub class 'B' bricks (old size) for cable protection cover laid flat and dry in trenches over the cablfCe perpendicular to the direction of cable all as directed.
6870
-
-
... More
Taking down old unserviceable Panel Board and Supply, installation, commissioning and testing cubical type, factory made, CPRI approved, indoor type, LT panel box of suitable size, made of mild steel sheet of 3.15 mm thick, powder coated, dust & vermin proof, front double doors, compartmentalized, general construction confirming to IS: 8623 (Part 1): 1993, locking arrangements, floor mounted, suitable for 3 phase 4 wire 415 V, 50 Hz,with 250 A aluminium bus bar, including necessary foundation works mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed and shall be comprising the followings: - INCOMING: - (a) MCCB 250 Amps rated, 36 kA short circuit protection, 430 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 01 No (b) Off load manual change over switch 250 amps, 4 pole, 415 volts, AC - 02 No (c) Ammeter (0 to 300 Amps), digital type with CTs and selector switch – 1 No (d) Voltmeter (0 to 500 volts), digital type with selector switch, 415 volts, AC- 1No OUTGOING (a) MCCB 63 Amps rated, 35 kA short circuit protection, 415 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 08 Nos
1
-
-
... More
Taking down old unserviceable Panel Board and Supply, installation, commissioning and testing cubical type, factory made, CPRI approved, indoor type, LT panel box of suitable size, made of mild steel sheet of 3.15 mm thick, powder coated, dust & vermin proof, front double doors, compartmentalized, general construction confirming to IS: 8623 (Part 1): 1993, locking arrangements, floor mounted, suitable for 3 phase 4 wire 415 V, 50 Hz,with 250 A aluminium bus bar, including necessary foundation works mounting on angle iron frame made using angle iron 50 mm X 50 mm X 6 mm complete all as specified and as directed and shall be comprising the followings: - INCOMING: - (a) MCCB 250 Amps rated, 36 kA short circuit protection, 430 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 01 No (b) Off load manual change over switch 250 amps, 4 pole, 415 volts, AC - 01 No (c) Ammeter (0 to 300 Amps), digital type with CTs and selector switch – 1 No (d) Voltmeter (0 to 500 volts), digital type with selector switch, 415 volts, AC- 1No OUTGOING (a) MCCB 125 Amps rated, 35 kA short circuit protection, 415 volts, 50 Hz, four pole, adjustable thermal & fixed magnetic setting- 03 Nos
1
-
-
... More
S & F in replacement LT feeder pillar for 415 volt, 4 wire system, cubical type, outdoor type, vermin and dust proof, fabricated with 3.15 mm thick CRCA sheet, factory made, totally enclosed with bus bar chamber & cable allied, weather proof, hinged cover with gasket, power coated comprising the followings complete all as specified and as directed: - i) MCCB 4 pole, 100 Amps, 36 kA, Adjustable Thermal & Adjustable Magnetic setting - 02 No (ii) MCB SPN 63 Amps, 10 kA, C-type, 50 Hz - 08 No iii) Aluminium Bus bar 100 Amp - 01 set OUTGOING iv) MCCB 100A 36 KA, 430 V- 01 no Note: The rate quoted by tenderer also includes to fix the legs of the panel box in PCC 1:3:6 pot hole foundation 30 cm below GL and the box will be kept nearly 45 cm above GL including earthwork and allied services complete. The legs of the box will be of 50 mm X 50 mm X 6 mm of length 750 mm)
8
-
-
... More
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 4.0 mm dia galvanised mild steel wire by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 20 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
20
-
-
... More
Taking down old unserviceable submain wiring 1.5 sqmm or 2.5 sqmm or 4 sqmm or 6 sqmm or 10 sqmm aluminium/copper conductors any number including batten/conduit/ casing capping including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surface to match the existing surface complete all as specified and as directed.
350
-
-
... More
Supply and fix sub main wiring complete with and including two Nos single core PVC insulated, unsheathed flexible conductor FR-LSH cables 6 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through and including medium protection stove enamelling rigid steel conduit as per IS 9537 (Part-II): 1981 of suitable nominal size as required at site dia but not less than 20 mm nominal size including all accessories and fixed on walls and 4 sqmm one No single core copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable for earthing and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. Note - Two runs of 6 sqmm cable, one run of 4 sqmm cable anle and one run of condit including Rate of capping casing shall be measured and paid as one unit length.
250
-
-
... More
Supply and fix sub main wiring complete with and including two Nos single core PVC insulated, unsheathed flexible conductor FR-LSH cables 10 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through and including medium protection stove enamelling rigid steel conduit as per IS 9537 (Part-II): 1981 of suitable nominal size as required at site dia but not less than 20 mm nominal size including all accessories and fixed on walls and 6 sqmm one No single core copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable for earthing and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. Note - Two runs of 10 sqmm cable, one run of 6 sqmm cable and one run of conduit it including Rate of capping casing shall be measured and paid as one unit length.
100
-
-
... More
S & F PVC rectangular block for mounting DBs, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover of size 100 mm X 100 mm and 50 mm deep complete all as specified and as directed.
24
-
-
... More
S & F double door MCB Distribution board of sheet metal enclosure, single pole and neutral, 8 way with 200 Amps rated bus bar, 240 volt, IP42 protection grade and fixed with PVC plug and screws and grouted in wall with M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
24
-
-
... More
S & F double door MCB Distribution board of sheet metal enclosure, single pole and neutral, 4 way with 100 Amps rated bus bar, 240 volt, IP42 protection grade and fixed with PVC plug and screws and grouted in wall with M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
16
-
-
... More
S & F circuit breakers (MCB), two pole with one protected pole (SPN), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 40 A, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.
40
-
-
... More
S & F circuit breakers (MCB), single pole (SP), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 6A to 40 A, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.
184
-
-
... More
Supply and laying or fixing or passing through pipe PVC insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 2 core, nominal cross sectional area of main conductor 10 sqmm, solid aluminium conductor, ISI marked as per IS 1554(Part-I): 1988 including cable glands, lugs etc. to suit the cable size in service connections complete all as specified and as directed.
140
-
-
... More
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 25 mm X 4 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
24
-
-
... More
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point