Military Engineer Services Tender

BidAssist is a very user-friendly website that helps us to explore all the new opportunities so as to achieve growth in our business. It helps us to attain all the information with respect to any e-tender the Arunachal Pradesh government has posted on its website in a very hassle-free manner.

Military Engineer Services - MES Tender

Works
Civil And Construction
Civil Works Others
Eprocure
Opening Date10 Oct 2022
Closing Date22 Oct 2022
Tender Amount₹ 14,00,00,000 
Notes
Download

Costs

Summary

Provision Of Perimeter Security Wall And Fence At Likabali

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Rough excavation not exceeding 1.50 m in deep and getting out in soft/loose soil complete all as specified and directed by Engineer-in-Charge.

3457.58

-

-

... More
Rough excavation exceeding 1.5 m but not exc 3.0 meter in deep and getting out in soft/loose soil complete all as specified and directed by Engineer-in-Charge.

2933.7

-

-

... More
Spreading and levelling in layers n exc. 25 cm thick and well ramming including watering as required complete all as specified and directed by Engineer-in-Charge.

5937.25

-

-

... More
Excavation in trenches not exceeding 1.50 m wide and not exceeding 1.50 m in depth for foundations,etc or for shafts, wells, cesspits, manholes, pier holes etc. not exceeding 10 Sqm on plan and not exceeding 1.50 m in depth and getting out in soft/loose soil.

5713.23

-

-

... More
Excavation in trenches not exceeding 1.50 m wide and exceeding 1.50 m in depth and not exc 3.0 m in depth for foundations,etc or for shafts, wells, cesspits, manholes, pier holes etc. not exceeding 10 Sqm on plan and exceeding 1.50 m in depth and not exc 3.0 m in depth and getting out in soft/loose soil.

406.42

-

-

... More
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm watering, and removing surplus soil to a distance n exc 50 m and making good surface

1619.2

-

-

... More
Surface excavation n.exc (not exceeding) 30 cm deep and averaging 15cm deep and getting out in soft / loose soil complete all as specified and directed.

982.94

-

-

... More
Excavating over areas, n exc 1.5 m deep and getting out in soft/loose soil complete all as specified and directed.

780.57

-

-

... More
Excavating over areas, exc 1.5 m but not exc 3.0 m deep and getting out in soft/loose soil complete all as specified and directed.

52.04

-

-

... More
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. as in soft/loose soil complete all as specified and directed.

4356.96

-

-

... More
Removing excavated material (soil) not exceeding 50 m and depositing where directed at a level n. exc. 1.50 m above the starting point complete all as specified and as directed.

2641.15

-

-

... More
Removing excavated material exc. 1.50 km but n exc. 5 km and depositing where directed complete all as specified and directed.

408.63

-

-

... More
M&L Hand packing (any thickness) at back of walls over arches etc. and raising (or lowering) to the required level size of broken aggregate 40 to 60mm complete all as specified and as directed.

108.9

-

-

... More
M&L Hand packing (any thickness) at back of walls over arches etc. and raising (or lowering) to the required level size of broken aggregate 10 to 20mm complete all as specified and as directed.

217.8

-

-

... More
(BOUNDARY WALL, CHAIN LINK FENCING, IRON GRILL ACROSS DRAIN CROSSING & RETAINING WALL) & CIVIL PART OF EXTERNAL ELECTRIFICATION

-

-

-

... More
M&L for cement concrete in foundation filling and mass concrete type D2 1:4:8 (40mm graded aggregate) complete all as specified and as directed.

508.52

-

-

... More
M&L Formwork to sides of concrete ( rough finished flat surfaces ) foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter complete all as specified and as directed.

6419.87

-

-

... More
M&L for RCC M-25 design mix (20mm graded stone Aggregates) in foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concretecomplete all as specified and as directed.

1328.76

-

-

... More
M&L for formwork to sides of pillars, posts, struts, piers, columns and stanchions in rough finished surfaces of concrete (Square, rectangular or polyonal) complete all as specified and directed.

5293.16

-

-

... More
M&L for formwork to sides and soffits of floor or roof beams, beam haunchings, girders, bressummers, lintels, cantilevers, shelves including sup- ports, overhangs, etc. also splays between floors and beams, etc for rough finished surfaces of concrete (flat) complete all as specifed and directed.

629.15

-

-

... More
M&L for RCC M-25 design mix (20mm graded stone Aggregates) in Beams, cantilevers,bressummers, lintels over 1.5m span complete all as specified and as directed.

56.23

-

-

... More
M&L for RCC M-25 design mix (20mm graded stone Aggregates) in Columns, pillars, piers, posts and struts, etc.; complete all as specified and as directed.

616.43

-

-

... More
M&L for RCC M-25 design mix (20mm graded stone Aggregates) in Walls, retaining walls, basement walls, ballast walls and the like; any thickness; above top of footings; including attached pilasters and buttresses complete all as specified and as directed.

181.5

-

-

... More
M&L formwork to faces of walls,retaining walls, abutments,parapets and staircase railings and similar work including attached pillasters, buttresses, etc.; vertical or to batter complete all as specified and as directed.

1104.84

-

-

... More
M&L mild steel TMT bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed

148650.23

-

-

... More
M&L for Mild steel TMT bars 6 to 8mm dia , cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed

120251.17

-

-

... More
M&L for Mild steel TMT bars 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders , cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed

39551.37

-

-

... More
M&L rendering 10mm thick in CM(1:4) on fair faces of brick work or concrete surfaces finished even and smooth without using extra cement complete all as specified and directedd

31141.44

-

-

... More
M&L for Precast RCC M-25(design mix) wall panel. Joining with other panels with cement mortar 1:3 and finished all as specified and as directed.

1005.67

-

-

... More
M&L for RCC Precast Cement Concrete Block type B-1 (1:2:4) (20mm graded aggregate) masonry with solid blocks, exc. 10 cm in width and setting in cement mortar 1:4 , completeall as specified and as directed.

79.2

-

-

... More
M&L for prepration of new plastered surfaces of wall & applying two coats cement base paint over a coat of primer complete all as specified and as directed.

20949.47

-

-

... More
M&L MS work as in post and struts in fencing, including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, welding etc. and similar work conforming to Fe-290 Gde E-165complete all as specified and as directed.

16797.66

-

-

... More
M&L for Galvanised 2 strand, steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails strain- ing bolts, including, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc. as directed (each line wire to be measured)

646.87

-

-

... More
M&L for prepration of new or previously untreated steel surface of any description, over 10cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed.

2459.23

-

-

... More
M&L for prepration of new or previously untreated steel surface of any description, not exc 10cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed.

245.4

-

-

... More
S&F Concertina coil size 600 mm, 2.50 mm dia with five Nos clip and pitch between the barbs etc as approved by Engineer-in-Charge.

8098

-

-

... More
M&L for PCC 1:3:6 type-C-2(using 40mm graded aggregate) in foundation filling, complete all as specified and as directed

301.73

-

-

... More
M&L for cement concrete type B-1 1:2:4, 20 mm graded aggregate as in coping of electric pole, including weathering slightly rounded or chamfered angles and throating as complete all as specified and as directed.

14

-

-

... More
M&L mild steel 75 x 75 x 6mm angle iron as in fencing post, incl cutting tops to shape as directed, drilling holes, notching for wire etc, flat iron fillets(for securing wire mess) incl all necessary drilling, bolting or reveting etc.

44501.01

-

-

... More
Supply only chain link MS galvanisd fencing, any size or type complete all as specified and as directed.

28676.03

-

-

... More
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc. including provision of binding wire (Size of mess 100 x 100mm, 4mm dia bar or size as decided by GE) complete all as specified and as directed.

9310.4

-

-

... More
M&L for Mild steel round bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specifed and directed

12798.72

-

-

... More
Material & labour for 40 x 6mm flat iron as in tie, incl cutting tops to shape as directed, drilling holes, notching for wires etc complete all as specifed and directed

6318.52

-

-

... More
Material & labour for MS bolts machine made with hexagonal or square head one end screwed the other or screwed both ends not exc 5 cm long and 12mm dia complete all as specifed and directed

1580.74

-

-

... More
M&L for framed work such as grills, gratings, etc. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete all as specified and as directed.

4294.62

-

-

... More
Supplying and laying dranaige composite Non woven geotextile(in two layers with polypropelene geonet in between) filter media behind retaining wall as per MORTH 700 TYPE I geoltextile made of poly propylene or similar fiber manufactured through machine made process of heat bending or needle punching technique and tensile strength 7 KN/M, weight not less than 150 gm/sqm as per manufaturer specification complete all as specified and directed. Makes : M/s Maccaferi Environmental solution Pvt Ltd./M/s Gabion Technologies India Pvt Ltd/M/s Techfab India Industries Ltd./M/s SVN Non Wovens Pvt Ltd./M/s Manas Geotech India Pvt Ltd

1096.92

-

-

... More
M&L 75mm PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors complete all as specifed and directed

99

-

-

... More
STEEL GATE (5.5 M WIDE) AND WICKET GATE (1.2 M WIDE)

-

-

-

... More
M & L for construction of MS steel gate with RCC piller 5.50 m wide as per Drg No CESZ/2017/TD/34 Sheet 1/3 to 3/3 incl painting, complete all as specifed and directed. Note:- Rate for earthwork and PCC are deemed to be included in quoted rate.

1

-

-

... More
M & L for construction MS of wicket gate 1.20 m wide as per Drg No CESZ/2017/TD/34 Sheet 1/3 to 3/3 incl painting, complete all as specifed and directed. Note:- Rate for earthwork and PCC are deemed to be included in quoted rate.

1

-

-

... More
( EXTERNAL ELECTRIFICATION INCL DG SET )

-

-

-

... More
M&L for Steel Tubular Swaged Poles Type 410-SP-31 (09 Metre long) including cast iron base plate, finial taper plug, cap, mild steel bolts, screws, etc. including applying two coats of black bituminous paint internally and externally upto planting depth and applying two coats of aluminium paint over a coat of aluminium primer (externally from top of RCC copping) including painting of black & white alternate strip of 30cm each externally from ground level upto 1.2m and writing MES Pole No. with synthetic enamel paint (first grade quality) complete all as specified directed by Engr-in-Charge. Note:- (a) Earthwork and PCC will be measured and paid separately (b) Volume occupied by Steel Pole shall be deducted to derive the quantity of PCC.

140

-

-

... More
M&L Aluminium conductor of any size, steel reinforced for LT over head line including stringing conductor fixed on pole and binding with aluminium binding wire etc. complete all as specified and as directed. NOTE: Size of conductor will be as per site requirement as specified and directed.

140

-

-

... More
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.

29

-

-

... More
M&L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade complete all as specified and as directed.

672

-

-

... More
M&L Insulator Shackle Type, Porcelain, vitreous, white, brown or green of size 100mm high & 115mm dia including galvanised mild steel straps of section 31 x 5 mm, 14mm dia insulator bolts, nuts, washers etc for working pressure 1100 Volts grade complete all as specified and as directed.

168

-

-

... More
Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum housing toughened glass cover and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection with CCT ≥ 5700k, electrical insulation – Class 1, efficiency – 115 Lm/W(min), THD ≤ 10% and 10 KV rated SPD and complete all as specified and directed.

400

-

-

... More
Supply & Fix new generation 35 Watt, Post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source IP65 including 50mm light grade GI pipe upto 2.0 m and PCC foundation complete all as specified and as directed.

10

-

-

... More
M&L for for GI Bracket fabricated out of light grade GI tubing 32mm dia, 1.5 mtr long and along with 02 sets of suitable size of clamps and nut and bolts to fix the bracket on steel tubular pole and existing PCC pole and inclusive of one primer coat, one under coat and one finishing coat of paint(Synthetic enamel) complete all as specified directed by Engr-in-Charge.

400

-

-

... More
M&L Stay assembly complete with accessories with 16mm dia stay rod as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and as directed.

15

-

-

... More
M&L Galvanised stay strand, 7/4mm complete all as specified and as directed.

2

-

-

... More
M&L Insulator loop type, Small size, vitreous Porcelain, white, brown or green with overall dimensions 65 x 90mm, clearance of hole 16mmcomplete all as specified and as directed.

15

-

-

... More
Supply, laying & testing cable XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq. mm 3.5 core complete all as specified and as directed.

520

-

-

... More
All as per Srl Item No 4.12 here-in-before but size 95 Sqm 3.5 core.

80

-

-

... More
All as per Srl Item No 4.12 here-in-before but size 10 Sqm 2 core.

200

-

-

... More
M&L Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm sizecomplete all as specified and as directed.

140

-

-

... More
Supply, install , testing and commissioning of outdoor LT distribution feeder pillar box (CPRI approved and with certification by ERDA for IP 65) of suitable size, factory made (tested as per IS) totally enclosed, dust and vermin proof, double leaf shutter in front and single leaf shutter in rear, made out of 3.15mm thick CRCA sheet duly fabricated and having proper front and rear locking arrangement duly powder coated and aluminium bus bar of suitable Amps, 415 volts, 50 Hz, 3 phase and 4 wired system with the following items including supply and fixing with MS channel 75mm x 40mm x 5mm duly painted with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer for fixing the feeder piller box to PCC foundation complete all as specified and directed :- In coming :- (i)MCCB 4 Pole, 50-63 Amps, 16 kA- 1 No (ii) On load Change over switch 63A, AC 415 Volts, 50Hz, 4-Pole, 200 Amps current rating, 16 KA rupturing capacity-01 Nos (iii) Multi function meter -1 No (iv) Phase indicator lamps (RYB)-1 set Out going :- (i)MCCB TPN, 16-20 Amps, 16 kA-02 Nos (ii) Bus bar 4 strip copper of capacity 100 Amps strip TPN of suitable size-01 Set (iii) Astronomical time switch with TP power contactor, 16A rated with coil voltage 230V AC -01 set Note :- PCC for foundation and earthwork included in quoted rate.

4

-

-

... More
M&L for laying clean river sand in trenches for cable protection including spreading, levelling, punning complete all as specified and as directed. Note : Punned thickness shall be measured and paid.

46

-

-

... More
M&L for Sub class ‘B’ old size well burnt brick laid flat in trenches over the cable for protection of LT cable complete all as specified and as directed.

5050

-

-

... More
Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI or steel wire 4 mm dia as earthing lead as shown in electrical plate No.3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel,20mm dia GI medium grade watering pipe, 15mm dia GI light grade earth lead protection pipe, RCC pit cover made out of 1:2:4 concrete and 8mm dia TMT bar, 100mm centre to centre with lifting handle of 10mm dia TMT bar, wire, copper lugs etc mesh, chorcoal and common salt in alternatee layer complete all as specified and directed.

28

-

-

... More
Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI strip 32x6mm as earthing lead as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI medium grade watering pipe, 40mm dia GI light grade earth lead protection pipe, RCC pit cover made out of 1:2:4 concrete and 8mm dia TMT bar, 100mm centre to centre with lifting handle of 10mm dia TMT bar, wire, copper lugs etc mesh, chorcoal and common salt in alternatee layer complete all as specified and directed by Engr-in-Charge.

16

-

-

... More
Supply, installation, testing and commissioning of silent type Diesel Engine driven Generating set with sound proof acoustic enclosure (canopy CRCA sheet of 2mm thickness and noise level below 75 decival/M) and provison of exhaust fan inside the canopy to control the noise level as per limit of central pollution control board and including AMF panel 5 KVA, 3 phase , 415 Volts, 1500 RPM, 4 wire, 50 Cycle and power factor 0.8 complete all as specified and comprising of the following with set of tools and two years maintenance spares as recommended by the manufacturer. (a) Prime Mover (Engine):- As per IS:10001,suitable for driving 5 KVA alternator, brushless self excited and 4-Cylinder engine turbo charged water cooled complete under NTP condition with provision for 10% overload for 1hr on continious 12hr (Total 13 hour) running and common base plate frame engine standard instrumental panel, self exciting and self regulating control panel with accessories , self starter 12 volts dry battery, 35 AH capacity and battery charging unit SCR type, battery cable leads , exhaust pipe with cladding by asbestos rope, sound proof canopy as per CPCB norms etc. Diesel engine set as per IS 10001 with inbuilt electronic speed governer with relay with inhouse canopy mounted fuel tank not less than 12 hours running capacity confirming to BSS frame pedestal support with anti vibration pad including RCC foundation with min hieght 45cm for DG set alongwith the following standard accessories:- (i) Conical shaft closed coupled to suit coupling (ii) Flexible coupling with guard, bolts and nuts,etc.for exhaust system (iii) Dry type air cleaner filters (iv) -Blank- (v) Fuel pump complete with fuel injection systems (vi) Electronic speed governor (vii) Fuel filter (viii) Lub oil filter (ix) Self starter 12 Volts DC (x) Exhaust silencer industrial type with pipe 3 m long Contd to item No 4.22

2

-

-

... More
Contd of item No 4.21.... (xi) Instrumental panel with the following:- (aa) Self starting key / switch on relay control panel (ab) Lubricating oil pressure guage (ac) Battery charging ammeter. (ad) Hour meter and RPM indicator (ae) Lub oil temp guage (af) Water temp guage (xii) Turbo charger (xiii) Lub oil pump (xiv) Lub oil cooler assembly (xv) Dynamo 12 V for charging of battery (xvi) Control including charging system panel with 10 Amps rated DC charging system -01 No. (xvii) Provison of light inside the canopy. (xviii) Emergency stop push button outside the container. (xix) Low oil pressure protection cutoff. (xx) High temperature protection cutoff. (xxi) Overload protection cutoff. (b) Alternator:- As per IS:13364, self exited, self generated balanced 415 volts, 3 phase, 50 Cycles per second, 5 KVA at 0.8 PF or nearest in higher capacity, 3000 RPM, star connected, 4 wire, drip proof enclosure, air cool with radial fan mounted on rotor, screen peotected, self ventilated enclosure as per IS 4722/IS 2613 with drip proof enclosure with damper winding on pole faces, static automatic voltage regulator to provide voltage regulation 1% and harmonic factor bettr than 2% from no load to full load from 0.8 to unity power factor and insulation of H-class and above as per standard practice. (c) AMF Panel:- In-Built with DG Set AMF Panel suitable for desired operation. Note :- Cost for foundation for installation & Shead with four No GI Pipe and Gi sheet with truss of DG Set as per OEM Instruction deemed to be included in quoted rate.

-

-

-

... More
Supply, installation, testing and commissioning of silent type Diesel Engine driven Generating set with sound proof acoustic enclosure (canopy CRCA sheet of 2mm thickness and noise level below 75 decimal/M) and provison of exhaust fan inside the canopy to control the noise level as per limit of central pollution control board and including AMF panel 10 KVA, 3 phase , 415 Volts, 1500 RPM, 4 wire, 50 Cycle and power factor 0.8 complete all as specified and comprising of the following with set of tools and two years maintenance spares as recommended by the manufacturer. (a) Prime Mover (Engine):- As per IS:10001,suitable for driving 10 KVA alternator, brushless self excited and 2-Cylinder engine turbo charged water cooled complete under NTP condition with provision for 10% overload for 1hr on continious 12hr (Total 13 hour) running and common base plate frame engine standard instrumental panel, self exciting and self regulating control panel with accessories , self starter 12 volts with battery 88 AH and battery charging unit SCR type, battery cable leads , exhaust pipe with cladding by asbestos rope, sound proof canopy as per CPCB norms etc. Diesel engine set as per IS 10001 with inbuilt electronic speed governer with relay with inhouse canopy mounted fuel tank not less than 12 hours running capacity confirming to BSS frame pedestal support with anti vibration pad including RCC foundation with min hieght 45cm for DG set alongwith the following standard accessories:- (i) Flexible disc, closed coupled coupling, (ii) Flexible coupling with guard, bolts and nuts,etc.for exhaust system, (iii) Dry type air cleaner filters (iv) Radiator with guard and radiator fan (v) Fuel pump complete with fuel injection systems (vi) Electronic speed governor (vii) Fuel filter (viii) Lub oil filter (ix) Self starter 12 Volts DC Contd to Srl Item No 4.24

1

-

-

... More
Contd of Srl Item No 4.23...... (x) Exhaust silencer industrial type with pipe 3 m long (xi) Instrumental panel with the following:- (aa) Self starting key / switch on relay control panel (ab) Lubricating oil pressure guage (ac) Battery charging ammeter. (ad) Hour meter and RPM indicator (ae) Lub oil temp guage (af) Water temp guage (xii) Turbo charger (xiii) Lub oil pump (xiv) Lub oil cooler assembly (xv) Dynamo 12 V for charging of battery (xvi) Control including charging system panel with 35 Amps rated DC charging system. (xvii) Provison of light inside the canopy. (xviii) Emergency stop push button outside the container. (xix) Low oil pressure protection cutoff. (xx) High temperature protection cutoff. (xxi) Overload protection cutoff. (b) Alternator:- As per IS:13364, self exited, self generated balanced 415 volts, 3 phase, 50 Cycles per second, 10 KVA at 0.8 PF or nearest in higher capacity, 1500 RPM, star connected, 4 wire, drip proof enclosure, air cool with radial fan mounted on rotor, screen peotected, self ventilated enclosure as per IS 4722/IS 2613 with drip proof enclosure with damper winding on pole faces, static automatic voltage regulator to provide voltage regulation 1% and harmonic factor bettr than 2% from no load to full load from 0.8 to unity power factor and insulation of H-class and above as per standard practice. (c) AMF Panel:- In-Built with DG Set AMF Panel suitable for desired operation. Note :- Cost for foundation for installation & Shead with four No of GI Pipe and GI sheet with truss structure of DG Set as per OEM Instruction deemed to be included in quoted rate.

-

-

-

... More
All as per Srl item No 4.23 & 4.24 here-in-before but capacity of Diesel Engine driven Generating set (DG) Set 15 KVA.

1

-

-

... More
Supply and laying of Galvanized steel tube light grade 40mm bore in trenches/alongwith pole, complete all as specified and directed.

50

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.