The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Dehydration Servicing Periodical Testing And Maintenance Of 11 433v Transformers Installed At Various Substations And Allied Works At Naval Dockyard Visakhapatnam Under Ge (i) Dm Visakhapatnam in Visakhapatnam, Andhra Pradesh, with an estimated contract value of Rs. 47,98,000. The bid opening date for this tender is 29-10-2026 and the last date for bid submission is 19-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - AP Tender
Opening Date29 Oct 2026
Closing Soon19 Nov 2026
Tender Amount₹ 47,98,000
Costs
EMD
₹ 95,960Document Cost
₹ 500Tender Fee
Refer Documents
Description
Dehydration Servicing Periodical Testing And Maintenance Of 11 433v Transformers Installed At Various Substations And Allied Works At Naval Dockyard Visakhapatnam Under Ge (i) Dm Visakhapatnam
Contact
Tender Id
2026_MES_796299_1Tender No
8618/C/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
Supply only transformer porcelain bushing outdoor/indoor type suitable for 11 KV grade complete of transformer capacity 250KVA to 3000 KVA, 11/0.415 KV transformer complete all as specified and directed. (Transformer bushings shall be compitable model with make and model of existing transformer)
6
-
-
... More
M & L for filtration/dehydration transformer oil of transformer voltage grade 11/0.415 KV, capacity 250 KVA to 3000 KVA indoor/outdoor type, floor mounted in situ till achieve dielectric strength minimum 40 KV at 4mm gap all as specified and directed.
20000
-
-
... More
M & L for topping up/replacement of transformer oil with new transformer oil suitable for working voltage 11000 volts grade including necessary dehydration to achieve dielectric strength min 40 KV at 4mm gap complete all as specified and directed.
1500
-
-
... More
Periodical servicing of complete transformer at every alternate 3 month by cleaning of complete outside surface, observing any oil leakage from any point, rectify by replacing with suitable RC 70 C rubberised cork sheet gusket to keep the complete outside surface dry all as specified and directed. Note- (i) replacement of silicon gusket other than at top cover and bushings shall be carried out and rate shall be inclusive of quoted rate. (ii) rectification of leakage from top cover and from bushing shall be measured and paid separately in the schedule (iii) Works under warantee period will not be measured in repitation
210
-
-
... More
M&L for complete painting of transformer outer surface in situ/wksp with one coat of synthetic enamel paint using sprayer for transformer capacity 250-1600 KVA after prliminary preparation of old painted surface . Note : (i) During process of painting, transformer will be under shut down for the period and the rate deemed to be included for running the sprayer machine with alternative arrangement by contractor. (ii) After completion of painting HT/LT outdoor bushing, cable termination joint, Oil inspection glass, meters and name plates to be made clean using volatile cleanner
20
-
-
... More
M&L for testing of transformer 250 KVA to 1600 KVA, 11/0.415 KV at various location by following test for HV & LV complete (a) Insulation Registance (b) Winding resistance (c) Turn ratio (d) Magnetic balance, (e) Oil BD value Note: Required testing equipment for transformer test shall be brought by the contractor and rate shall be inclusive of quoted rate
15
-
-
... More
M&L for replacement of new silica gel blue granives in place of light pink colour in the breather assembly of transfromer complete all as specified and directed.
10
-
-
... More
M & L for replacement of breather assembly made with polycarbonate base and clear acylic glass of size to accommodate 1.0 kg of silica gel for transformer complete all as specified and directed.
5
-
-
... More
M & L for replacement of transformer temperature gauge dial type having temp range 0 to minimum 120 degree celcius complete all as specified and directed.
10
-
-
... More
M & L for replacement of transformer explosion vent gasket complete all as specified and directed.
20
-
-
... More
Supply only transformer porcelain bushing outdoor/indoor type suitable for 1100 volts grade complete of transformer capacity 250KVA to 750 KVA, 11/0.415 KV transformer complete all as specified and directed. (Transformer bushings shall be compitable model with make and model of existing transformer)
10
-
-
... More
All as per item No. 14.00 above, for transformer capacity 1000-1600 KVA,
10
-
-
... More
Supply only brass stud with accessories suitable for HT 11000 volts grade insulator with con & rubber washer, double Brass nuts & brass washer at both end of stud for Tr cap 500-1600 KVA
10
-
-
... More
Supply only brass stud suitable for LT 1100 volts grade insulator with con & rubber washer, double Brass nuts & brass washer at both end of stud for Tr cap 250-750 KVA
10
-
-
... More
All as per item No. 17.00 above, but for Tr 1000-1600 KVA
5
-
-
... More
Taking out manually repairable/ serviceable transformer of capacity 500-2000 KVA from its position upto road n. exc 50 mtr and transportation by vehicle to other location n. exc 2 KM inside Dockyard incl all cable/earth connections all as specified and directed. Note: a) Rates for dismentling of HT/LT cable & earthing and reconnection after installation deemed to be included in the quoted rate, (b) Necessary crane for lifting of transformer and vehicle for transportation shall be arranged by the contractor and deemed to be included in the quoted rate.
2
-
-
... More
M&L for replacement of off load Tap changer assy incl rotating wheel having 7 position of transformer including dismentling and taking out old unserviceable one and dismentling all winding terminal connections and reconnection after replecement complete upto transformer cap 2000 KVA 11/0.415 KV all as specified and directed.
3
-
-
... More
M&L for replacement of buchholz relay incl necessary electric connection to siren/panel complete upto transformer cap 750 to 2000 KVA 11/0.415 KV all as specified and directed.
5
-
-
... More
M&L for replacement of winding temperature meter and oil temperature meter dial type including connection cable from transformer and buchholz relay all as specified and directed.
5
-
-
... More
M&L for dismantling and taking out buchholz relay, overhauling, servicing, cleaning and refixing to transformer original position and testing for proper functioning including complete connection with temperature sensor cable and electric connection all as specified and directed.
25
-
-
... More
M&L for cleaning & painting of HV terminal box by dismentling of HT 3 core cable connection from transformer HT 11 KV side, cleaning & painting with one coat of synthetic enamel paint of complete HT cable box inside, cleaning of HT cable kit with suitable cleaning agent, Checking for any loose cable end terminals and replace as necessary and crimping with suitable tools, refixing to transformer, sealing of space between cable and cable box hole using suitable packing material, connection of cable earth terminal to specified point incl testing all as specified and directed.
10
-
-
... More
M&L for cleaning & painting of LV terminal box by dismentling of LT 4 core cable connection from transformer LV side, cleaning & painting with one coat of synthetic enamel paint of complete LV cable box inside, cleaning of all LV cable kit with suitable cleaning agent, Checking for any loose cable end terminals and replace as necessary and crimping with suitable tools, refixing to transformer, sealing of space between cable and cable box hole using suitable media, connection of cable earth terminal to specified point including fixing of required copper strip for LT cable connection testing all as specified and directed Note :- Copper strip shall be measured as supply only.
10
-
-
... More
S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe/duct or fixed to poles or any other indicated situation for loop earthing etc. using required nut, bolt & washers as per site requirement of size 32x6mm galvanised iron strip including taking down unserviceable one from conduit/pipe/duct complete all as specified and directed.
500
-
-
... More
M & L for Earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised iron strip 32 x 6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical Plate No. 2, connected to the earthing test point, concrete pit in PCC 1:3:6 type C-2 with RCC precast pit cover slab 80mm thick with handle for lifting made out of 8mm dia MS rod, Funnel with watering pipe, wiremesh, charcoal and salt in alternate 150mm thick layers around earth plate including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including testing to achieve earth resistance value as per IS specification on completion after dismentling taking out unserviceable one complete all as specified and directed.
30
-
-
... More
M&L for by Weekly cleaning of entire substation building inside wall, ceiling, floor and outside wall, plith protection with suitable brush / broom & wiper, removing wild vegitation around entire substation all as specified and directed.
Note: (i) Recovery shall be made double the quotaed rate if timely cleaning is not carried out) (ii) Each sub station cleaning measured as one job.
1300
-
-
... More
Supply & Fix adhetive compurised cut sticker blue back ground with white letter of sticker size 100x400 mm on body of transformer showing Capacity of Transformer in KVA and M/C No. complete all as specified and directed.
5
-
-
... More
Supply and lay in trenches or in duct or passing through pipe XLPE insulated, screened, PVC bedded, galvanised steel strip armoured, overall PVC sheathed electric power cables (heavy duty) with aluminium conductor, 11000 volts grade (Earthed) cross sectional area 185 sq. mm 3 core incl dismantling / taking down unserviceable one complete all as specified and directed.
100
-
-
... More
All as per item No. 30.00 above, but of size 240 sq. mm 3 core incl dismentling / taking down unserviceable one.
100
-
-
... More
S&F Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm after opening VCB panel back side cable cover and bottom cable entry plate after disconneting unsv cable kit from busbar/CT, taking out from VCB cable chamber and fixing the same to original position, with new or old nuts, bolts & washers, bottom plate, back cover and making cable entry point totally sealed with putty complete all as specified and directed.
2
-
-
... More
All as per item No. 32.00 above, (indoor termination) but for cable of size 240sqmm to 300 sqmm incl dismentling / taking down unserviceable one.
2
-
-
... More
Supply and laying in trenches XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 Volts grade cross section area 300 Sqmm 3.5 core and connection complete with aluminium cable lugs incl dismantling taking down unsv one all as specified and directed.
50
-
-
... More
All as per ser No. 34.00 above, but of Size 400 Sqmm 3.5 core
50
-
-
... More
S&F of LT heat shrink cable end termination for cable sizes 240 to 300 Sqmm, 3.5 core, 1100 volts grade by cutting out damaged portion of XLPE insulated cable ends including disconnection cable from ACB/MCCB/Bus bar and reconnection with existing/new stainless steel bolts of size not less than 16mm dia and 40mm long. complete all as specified and directed.
Make - 3M Cat No. MHI/Ox1.1KV (HESL-5/4C) or equivalent of Denson/M seal/RPG.
1
-
-
... More
All as per item No. 36.00 above, but for cable sizes 400 Sqmm. Make - 3M Cat No. MHI/Ox1.1KV (HESL-5/4C) or equivalent of Denson/M seal/RPG
1
-
-