Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Servicing Maintenance Of Chlorine Agitators Flocculators And Clarifier System And Allied Works At Naval Dockyard Visakhapatnam Under Ge(i) Dm Visakhapatnam in Visakhapatnam, Andhra Pradesh, with an estimated contract value of Rs. 45,00,000. The bid opening date for this tender is 23-10-2026 and the last date for bid submission is 20-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - AP Tender
Opening Date23 Oct 2026
Closing Soon20 Nov 2026
Tender Amount₹ 45,00,000
Costs
EMD
₹ 90,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Servicing Maintenance Of Chlorine Agitators Flocculators And Clarifier System And Allied Works At Naval Dockyard Visakhapatnam Under Ge(i) Dm Visakhapatnam
Contact
Tender Id
2026_MES_795426_1Tender No
8650/C/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
(Note:(i) If dozing pump is found non- functional more than 03 hours, recovery shall be made @ twice the quoted rate for every hour of non - functional period.(ii) spares will be measured and paid separately)(iii) Quoted rate will include transportation cost if repair is carried out by taking out pump to civil workshop
-
-
-
... More
Weekly maintenance & repair including breadown repair as require of chlorine mixing agitator 3ph/1ph motor 3.75 kw, Make- CG, by removing motor from base, cleaning/ greasing rorating gears, chekcing for any defects in gear system and rectification by replacing required item, cleanding of rod nd blade, checking for any damaged to rod and blade and replacing required item, checking serviceability of level indicator and rectify by replacing required item, cleaning of complete agiator FRP chamber by removing all sludge and cleaning with clean water, cleaning of outside are around agitator chamber and pump complete all as specified and directed.
Total agitator-01No.
Note : if agitator is found non-funcitonal more than 03 hours, recovery shall be made @ twice the quoted rate for every hour of non- functional period
48
-
-
... More
Weekly maintenance & repair including breadown repair as require of Alum mixing agitator 3ph/1ph motor 1.11 kw, Make- CG, by removing motor from base, cleaning/ greasing rorating gears, chekcing for any defects in gear system and rectification by replacing required item, cleanding of rod nd blade, checking for any damaged to rod and blade and replacing required item, checking serviceability of level indicator and rectify by replacing required item, cleaning of complete agiator FRP chamber by removing all sludge and cleaning with clean water, cleaning of outside are around agitator chamber and pump complete all as specified and directed.
Total agitator-01No.
Note: if agitator is found non-functional more than 03 hours, recovery shall be made @ twice the quoted rate for every hour of non- functional period.
48
-
-
... More
Weekly maintenance & repair including breadown repair as require of Alum mixing agitator in Tank1 and Tank 2 3ph/1ph motor 1.5 kw, Make- CG, by removing motor from base, cleaning/ greasing rorating gears, chekcing for any defects in gear system and rectification by replacing required item, cleanding of rod nd blade, checking for any damaged to rod and blade and replacing required item, checking serviceability of level indicator and rectify by replacing required item, cleaning of complete agiator FRP chamber by removing all sludge and cleaning with clean water, cleaning of outside are around agitator chamber and pump complete all as specified and directed.
Total agitator-02Nos
Note: if agitator is found non-funcitonal more than 03 hours, recovery shall be made @ twice the quoted rate for every hour of non- functional period.
48
-
-
... More
Weekly maintenance & repair including breadown repair as require of Clarifier flocculator 3ph/1ph motor 3.75 kw, Make- CG, by removing motor from base, cleaning/ greasing rorating gears, chekcing for any defects in gear system and rectification by replacing required item, cleanding of rod nd blade, checking for any damaged to rod and blade and replacing required item, checking serviceability of level indicator and rectify by replacing required item, cleaning of complete agiator FRP chamber by removing all sludge and cleaning with clean water, cleaning of outside are around agitator chamber and pump complete all as specified and directed.
Total agitator-01Nos
Note: if agitator is found non-funcitonal more than 03 hours, recovery shall be made @ twice the quoted rate for every hour of non- functional period
48
-
-
... More
Weekly maintenance & repair including breadown repair as require of Clarifier flocculator 3ph/1ph motor 0.375 kw, Make- CG, by removing motor from base, cleaning/ greasing rorating gears, chekcing for any defects in gear system and rectification by replacing required item, cleanding of rod nd blade, checking for any damaged to rod and blade and replacing required item, checking serviceability of level indicator and rectify by replacing required item, cleaning of complete agiator FRP chamber by removing all sludge and cleaning with clean water, cleaning of outside are around agitator chamber and pump complete all as specified and directed.
Total agitator-04Nos
Note: if agitator is found non-funcitonal more than 03 hours, recovery shall be made @ twice the quoted rate for every hour of non- functional period
48
-
-
... More
M&L for rewinding of Motor upto 3.75kw after dismatling taking out from pump set base, transportation to civil workshop outside ND(V), opening of complete motor, dismatling stator/rotor, rewinding the complete stator of motor with existing size of super enameled copper wire as per existing turn, heating, vernishing, replacement of both end bearing, Connecton plate, Connection terminals with new copper lugs for all 06 terminal, re-assemble, transport back to ND (V), reinstall at pump base, connection with pump coupling, making proper alignment , testing for satisfactory run complete all as specified and directed . Motor Make- Kirloskar
4
-
-
... More
All as per item No. 09 above, but of size 0.37kw
3
-
-
... More
Supply only for following spare parts for floculator/agiators and dozing systems
-
-
-
... More
Stainless steel shaft as per existing make and size
2
-
-
... More
Mixer (Set of Rod and blade) as per existing make
5
-
-
... More
Bearing as per existing size and make
5
-
-
... More
Gear box as per existing size and make
5
-
-
... More
Complete Gear Motor assembly
3
-
-
... More
Rotor Assembly with bearings bracket & Tolerance rings
3
-
-
... More
Coil 250V 50HZ
3
-
-
... More
Single Head Feed Rate Control With Shaft
3
-
-
... More
Pump Head (FERRULES 1/4" & DUCKBILL Included)
3
-
-
... More
Roller Assembly (PK of 04)
3
-
-
... More
Pump Tube (PK OF 05)
3
-
-
... More
Injection Check Valve (PK OF 05)
3
-
-
... More
White Suction/Discharge Tube as per sample
20
-
-
... More
Check Valve Duckbill Only (PK OF 05)
3
-
-
... More
Connecting Nut with adapter (PK OF 05)
3
-
-
... More
Connecting Nut as per sample
5
-
-
... More
Ferrule (PK of 24)
3
-
-
... More
PVC flange assembly of dozing pump as per sample
3
-
-
... More
Material and labour for dismantling the clarifier flocculator and making it completely serviceable after making necessary repairs and replacements such as making proper alignment , testing for satisfactory run complete all as specified and directed .
Note :- The quoted rate is inclusive of the following works including spares a) shaft drive assembly including bearing 7409B for worm shaft -01nos b)gear box assembly alongwith spares Bonfiglioli gear box AS 35 DP 99.3 080 B55 B3 /equivalent suitable at site -01nos c)motor 0.75hp flange mounted -01nos d)Drive sprocket 13 teeth 3/4'' pitch-01nos e)Drive sprocket 36 teeth 3/4'' pitch -01nos f),chain ASA 3/4'' pitch single strand 62 pitches with one connecting link-01nos g)LH drive control unit-01nos h)Adopter shaft -BM 560 shaft drive -01nos Any additional spares required is deemed to be inclusive of quoted rate required to make the unit functional.
1
-
-
... More
Supply and laying of CPVC pipes of size 25mm outer dia , SDR 11 and plain UPVC SDR 11 fittingss on wall / floor including taking down unsv one complete all as specified and directed.
19
-
-
... More
Supply and laying of CPVC pipes of size 40mm outer dia , SDR 11 and plain UPVC SDR 11 fittingss on wall / floor including taking down unsv pipe complete all as specified and directed.
19
-
-
... More
Supply and fix UPVC Y- strainer size 25 mm outer dia including taking down unsv pipe all as specified and directed.
5
-
-
... More
Supply and fix UPVC Y- strainer size 40 mm outer dia including taking down unsv pipe all as specified and directed.
5
-
-
... More
Supply only single use PVC hand gloves free size for use by DEL for chlorine/ alum mixing complete all as specified and directed.
1000
-
-
... More
Cutting/Cleaning of wild vegetation etc in and around water supply installation/hill top reservoir premises and location including disposal of spoil NOTE-A distance not exceeding 50m outside the installation all as specified and directed.
5000
-
-
... More
Supply only acrylic goggle full cover protection for use with chlorine handling all as specified and directed.
22
-
-
... More
Supply only rubber gum boot all as specified and directed.
23
-
-
... More
Supply only protective mask with special filter for protection from chlorine all as specified and directed.
72
-
-
... More
Supply only TDS analyser Kit all as specified and directed
2
-
-
... More
Supply only Chlorine test kit complete all as specified and directed and as required in site with reagant 1 and reagant 02 of 1 litre capacity all as specified and directed.
2
-
-
... More
Supply only hydraulic lifting trolley double scissor type capacity not less than 0.3-0.5 ton all as specified and directed.
2
-
-
... More
Supply and laying cable with copper conductor PVC round sheathed (flexible) industrial cable 1100volts grade including copper lugs with new nuts/botls etc, cross-sectional area 16sqmm single core incl dismantling taking down unsv aluminium cable into schedule of credit from wall, cable tray, trench complete all as specified and as directed
180
-
-
... More
Supply and laying High density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 fixed complete to walls, ceilings or in floors etc., all as specified and directed.
90
-
-
... More
Material & labour for PCC (1:2:4), type B1 (using 20 mm graded stone aggregate) as form work and finishing the exposed surfaces of concrete fair complete all as specified and directed and dispose the waste at dumpyard inside ND (V).
1
-
-
... More
M&L Mild Steel framed work with ends of bars souldered, welded or reveted or forced into spikes, framed guard bars, ladders,chequred plates framed balusters, walk ways, railings, gates, frame work of tank, valvepit and similar work incl painting with one coat of red oxide primer and one coats of anticorrosive black bituminous paint incl dismantling mild steel work of any description not otherwise specially provided for all as specified and directed.
4600
-
-
... More
Earthing complete with copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to 20×3mm copper strip by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and directed.
15
-
-
... More
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20x3mm copper strip complete all as specified and directed.
60
-
-
... More
Labour only for attending electrical breakdowns checking the serviceability, testing, replacement of minor spare parts in starters, panels, pumps, making the unit completely functional complete all as specified and directed. Note 1:- The quoted rate is deemed to be include (i) necessary T&P to attend the breakdown. (ii) Necessary labour/trade men for attending emmergency break down . (iii) labour element and spares required for making the unit completely functional such as control wiring,terminal bolts copper cables,lugs etc. (iv) PCC work wherever required
146
-
-