Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Repair Maintenance Of Lt Electrical Panel Boards And All Accessories Including Replacement Of Unsv Items Gallery Earthings Earthing Strips And Allied Works At New Dockyard Jetty Substations At Naval Dockyard Visakhapatnam Under Ge (i) (dm) Visakhap in Visakhapatnam, Andhra Pradesh, with an estimated contract value of Rs. 47,23,000. The bid opening date for this tender is 29-10-2026 and the last date for bid submission is 19-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender - AP Tender
Opening Date29 Oct 2026
Closing Soon19 Nov 2026
Tender Amount₹ 47,23,000
Costs
EMD
₹ 94,460Document Cost
₹ 500Tender Fee
Refer Documents
Description
Repair Maintenance Of Lt Electrical Panel Boards And All Accessories Including Replacement Of Unsv Items Gallery Earthings Earthing Strips And Allied Works At New Dockyard Jetty Substations At Naval Dockyard Visakhapatnam Under Ge (i) (dm) Visakhap
Contact
Tender Id
2026_MES_796310_1Tender No
8712/C/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
Repair, maintinance of Air Circuit Breaker 630 Amps to 3200 Amps capacity by drawing out movable unit, forced air cleaning of movable and fixed unit, decarbonize breaker contracts and checking for any defects due to any flush/loose contact, cleaning of all fixed and moving contact point, terminal connection points with CTC, replacement of defective parts and re-fixing ACB, cables completes all as specified and directed. Note: (a) Required male/female ACB contacts, trip coils, closing coils, electronic protection unit will be measured as supply only. (b) All cleaning agents are included in the quoted rate. (c) Cable connection and disconnection are included in the quoted rate.
30
-
-
... More
Supply only fixed contract of ACB 630A to 3200A all as specified and directed.
6
-
-
... More
Supply only Moving contract of ACB 630A to 3200A all as specified and directed.
6
-
-
... More
Supply only Electronic protection unit of ACB 630A to 3200A all as specified and directed.
6
-
-
... More
Supply only shunt trip coil of ACB 630A to 3200A all as specified and directed.
2
-
-
... More
Supply only closing coil ACB 630A to 3200A all as specified and directed.
2
-
-
... More
Supply only digital electronic Ammeter (0-3200 amps range) with built in selector switch suitable for LT 415 V panel flush pattern square type 96 mm x 96 mm with adopter complete all as specified and directed. Make :- Cat Part No:-30002385 (DM3110) of Schneider or Conserve/L&T/HPL
10
-
-
... More
Supply only digital electronic Volt meter (0-500 volts range) with built in selector switch suitable for LT 415 V panel flush pattern square type 96 mm x 96 mm with adopter complete all as specified and directed. Make :- Cat Part No:- 30002386 (DM3210) of Schneider or Conserve/L&T/HPL
12
-
-
... More
Supply only indication lamps (LED type) red, yellow and blue in colours of 22.5 mm dia to monitor on LT panel board suitable for 240 V AC supply and taking down unserviceable indication lamps all as specified and directed. Cat Part No:-1SFA619402R5201of Siemens or C&S/schneider/ABB
60
-
-
... More
Supply only metering current transformer of 2500/5 Amps class-1, 15 VA, all as specified and directed.
3
-
-
... More
Supply only metering current transformer of 2000/5 Amps class-1, 15 VA, all all as specified and directed.
3
-
-
... More
Supply only metering current transformer of 1600/5 Amps class-1, 12.5 VA, all all as specified and directed.
6
-
-
... More
Supply only three (3) Phase, multifunction power and energy meter with Class 0.5S /1.0 as per IEC 62053-22 / 21 with IO module integration for onboard data logging for real time montioring of following parameters Amps, PF, THD, Hz, W, Wh, VA, VAh, VAR, VARh, min/max demand monitoring with communication port RS485 all as specified and directed.
11
-
-
... More
M & L for ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 3200 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 2500 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 2000 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 4 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 1600 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 3200 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 2500 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 2000 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 1600 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 1250 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for ACB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 1000 Amps and taking down unserviceable all as specified and directed.
1
-
-
... More
M & L for MCCB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 630 Amps with breaking capacity 50 KA and taking down unserviceable all as specified and directed.
3
-
-
... More
M & L for MCCB 3 Pole, 415 V, with Thermal Magnetic Release (Manual Drawout type) of capacity 400 Amps with breaking capacity 36 KA and taking down unserviceable all as specified and directed.
4
-
-
... More
Supply and fix heat shrikable cable end termination of sizes 300/ 400 sqmm, 3.5 core complete all as specified and directed.
20
-
-
... More
Supply and fix heat shrikable cable end termination of sizes 185/240 sqmm, 3.5 core complete all as specified and directed.
10
-
-
... More
Supply only Heat Shrink sleeve outer protection insulating tube (Coated) single core, for application range 9-29mm all as specified and directed.
150
-
-
... More
Supply only coloured Heat Shrink sleve busbar insulation tube single core, for application range upto 150 mm all as specified and directed.
100
-
-
... More
Supply only Busbar anodised aluminium of as per site requirement sizes including required drilling holes for fixing with other bus / cable connections all as specified and directed.
150
-
-
... More
Supply only Busbar anodised copper of as per site requirement sizes including drilling holes for fixing with other bus / cable connections all as specified and directed.
150
-
-
... More
Supply and fix MS cable support structure made with ISA 75x75x8mm grouted to gallery wall with angle fastner bolt of dia not less than 16 mm at interval of 300 mm fixing of cross support with cadmium coating bolts not less than 12 mm dia,painting the MS structure with one coat of red oxide primer and two coat of synthetic enamel paint complete including taking out old UNSV cable support structure from the jetty gallery complete all as specified and as directed.
850
-
-
... More
M&L for MS Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachmens complete all as specified and as directed including taking out of old unserviceable MS cable cover/support structure.Grade of steel Fe 410 -W (Gde E- 250) quality -A structure all as specified and directed.
348
-
-
... More
M&L for painting of outer surface of multiple section of complete LT Panel board size up to 5.5 m x 3.2 in substation Panel board comprising ACBs/MCCBs/SDFs ,busbar chamber, swich gear chamber, metering chamber cable termination/tray using one coat of synthetic enamel paint after preparation of surface, providing protection cover to all metering equipment, panel meters, switchgears, cleaning of all meters and switch gears complete all as specified and as directed
25
-
-
... More
Cleaning of cable duct of size 1.2 x 1.0 by removing out all mud, soil, waste materials and disposal of waste materials outside Dockyard area complete all as specified and directed
15
-
-
... More
Supply and fix line diagram of substation panel to Jetty panel and cope point with blue background and white letter made with retro reflective sheet and pasted on 2 mm thick aluminium sheet of total size 0.45 m high X 5.5 mtr long fixed to MS fabricated structure with welding, nuts, bolts complete including dismantling taking old unserviceable glow sign board of any type complete all as specified and directed.
6
-
-
... More
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to using galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion, including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including testing to achieve earth resistance value as per IS specification on completion.
10
-
-
... More
M&L for Earth continuity conductor or main earth lead fixed to wall of batten or recess or chases or buried in ground or drawn in conduct/pipe or any other indicated situation for loop earthy etc of 32x6 mm including taking down old one complete all as specified and directed.
200
-
-
... More
Supply and laying of electrical insulating rubber mat in front of and around 11KV HT Panels, suitable for high-voltage electrical installations. Mat shall be IS 15652 compliant, electrically insulating, flame-retardent, oil/moisture resistant and provided with a non-slip surface. The mat shall be of suitable thickness and voltages class as required for 11 kV HT switchgear, complete with cutting, jointing and proper installation all as per specified and as directed.
24
-
-