The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Repair/ Replacement And Miantenance Of Fire Alarm And Fire Fighting System Including Allied Works At Icgs Malkapuram Under Ge(i)(cg) Vizag in Visakhapatnam, Andhra Pradesh, with an estimated contract value of Rs. 10,00,000. The bid opening date for this tender is 28-10-2026 and the last date for bid submission is 18-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender - AP Tender

Opening Date28 Oct 2026
Closing Soon18 Nov 2026
Tender Amount₹ 10,00,000 
Notes
Download

Costs

Description

Repair/ Replacement And Miantenance Of Fire Alarm And Fire Fighting System Including Allied Works At Icgs Malkapuram Under Ge(i)(cg) Vizag

Contact

Unlock the Tender details

GEM & Bid Advisory Services

Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

Unlock the Tender details
... More
Supply only MS ERW pipe of 150 mm dia, 5.4 mm thickness complete all as specified and directed.

6

108

-

... More
Supply only MS ERW pipe of 100 mm dia, 5.4 mm thickness complete all as specified and directed.

6

108

-

... More
Supply only MS ERW pipe of 80 mm dia, 4.84 mm thickness complete all as specified and directed.

6

108

-

... More
Supply and fixing in repair of damaged/defective/unserviceable fire brigade inlet connection 4 way complete all as specified and directed.

1

108

-

... More
Supply and fixing in repair of damaged/defective/unserviceable fire brigade inlet connection 2 way complete all as specified and directed.

1

108

-

... More
Supply and fixing in repair fire hydrant landing valve GM type A single outlet of 63 mm dia with new hydrant confirming to IS 5290 with PVC blank cap and MS or GI chain complete all as specified and directed.

1

108

-

... More
Supply and fixing in repair fire hydrant landing valve GM type B ( Double head outlet) of 63 mm dia with new hydrant confirming to IS 5290 with PVC blank cap and MS or GI chain complete all as specified and directed.

1

108

-

... More
S&F in repair damaged /defective/unserviceable ABS plastic 3/4" shut off nozzle suitable for 19/20 mm hose complete all as specified and directed.

10

108

-

... More
Supply and fix in repairs 150 mm dia cast iron Sluice Valve, Class PN 1.6, confirming to IS 14846 of 2000 with iron wheel head complete all as specified and directed.

1

100

-

... More
Supply and fix in repairs 100 mm dia cast iron Sluice Valve, Class PN 1.6, confirming to IS 14846 of 2000 with iron wheel head complete all as specified and directed.

1

100

-

... More
S&F in repair 80 mm dia cast iron Sluice Valve, Class PN 1.6, confirming to IS 14846 of 2000 with iron wheel head complete all as specified and directed.

1

100

-

... More
S&F in repair cast iron Non Return valve 150 mm dia, heavy duty, confirming to IS 5312-(Part I) - 1984 complete all as specified & directed

1

100

-

... More
S&F in repair cast iron Non Return valve 100 mm dia, heavy duty, confirming to IS 5312-(Part I) - 1984 complete all as specified & directed

1

100

-

... More
S&F in repair cast iron Non Return valve 80 mm dia, heavy duty, confirming to IS 5312-(Part I) - 1984 complete all as specified & directed

1

100

-

... More
S&F in repair presure gauge glycerine filled with 15 mm inlet connection dial size 100 mm of pressure range 0 to 14Kg/cm2 with 15mm isolation valve with G.I. nipple complete all as specified and directed.

5

108

-

... More
S&F in repair presure gauge glycerine filled with 15mm inlet connection dial size 200 mm of pressure range 0 to 21Kg/cm2 with 15mm isolation valve with G.I. nipple complete all as specified and directed.

5

108

-

... More
Repair/Servicing of fire hydrant landing valve type 'A/B' of 63 mm dia, including spindle thread machine, washers replacementmnt, checkout, packing serving complete to arrest leakage and proper function of valve complete all as specified and directed.

3

108

-

... More
S&F in repair CP hose reel 15 m complete all as specified and directed.

2

108

-

... More
S & F in repairs 15 mm dia Gun Metal, globe or Gate Valve with Iron wheel head Screwed both ends for Iron Pipe and fixed complete all as specified and directed.

2

100

-

... More
S & F in repairs 20 mm dia Gun Metal, globe or Gate Valve with Iron wheel head Screwed both ends for Iron Pipe and fixed complete all as specified and directed.

2

100

-

... More
S&F in repair fire fighting RRL hose pipe of 63mm, ISI marked, IS 63 (type A), 15m long fitted with male and female gun metal coupling ISI marked, IS 903 complete all as specified and directed.

3

108

-

... More
S&F in repair gunmetal branch pipe with long nozzle suitable for 63 mm dia RRL hose pipe, ISI marked, complete all as specied and directed.

3

108

-

... More
Supply and Fix in repair outside hose box cabinet made out of 18 gauge MH sheet of size as per site reqirement but not less than 800mm X 600mm X 250mm with double leafed glazed shutters (glazed with 4mm thick transperent fiber sheet) and door frame made out of 16 guage MS sheet painted fire red outside and brilliant white inside complete all as specied and directed for housing two number RRL hose each 15m long, one number branch pipe with nozzle , first aid hose and single outlet hydrant valve etc and must have the legend " FIRE HOSE" painted prominently in graphic style complete all as specified and directed.

3

108

-

... More
S&F in repair 4 mm thick sheet glass for fire hose boxes of size 0.20 x 0.20 m complete all as specified and directed.

10

108

-

... More
S&F in repair hose reel drum of 20 mm dia and 30 mtr length hose pipe conforming to IS-5132 including gun metal nozzle suitable valve complete all as specified and directed.

2

108

-

... More
Supply, install, testing and commissioning of pressure switch with set point up to 7.5 Bar, suitable for use in fire fighting and water supply systems. The pressure switch shall be compact, robust, and enclosed in a weatherproof IP65-rated housing, equipped with SPDT contacts rated for standard control circuits. The unit shall be suitable for vertical or horizontal mounting and compatible with water and air media. It shall include necessary accessories for secure installation and shall be calibrated and tested for reliable cut-in and cut-out pressure control including taking down old unserviceable switch complete all as specified and directed. Make: Danfoss or equivalent approved by GE.

3

108

-

... More
Repair and maintenance of fire service main pump, multi-stage, horizontal split casing type, with a capacity of up to 100 HP and a head of 90 metres, operating at 1450 RPM, and coupled with a diesel engine of up to 100 HP. The work includes complete servicing of the pump by replacing unserviceable components such as gland packing, bearings, and charging lubricants to ensure smooth operation. It also includes servicing of the diesel engine by replacing filters, lubricant oil, and other defective parts including coupling, oil and air filters, servicing of radiator, replacement of exhaust gasket, and replacement of diesel supply and return pipes from the tank to the engine. Battery leads shall be replaced as required and the charging circuit shall be checked and made fully functional. The complete pump set, including base frame and associated pipelines inside the pump room, shall be cleaned, surface-prepared, and two coats painted with an approved shade of synthetic enamel paint complete all as specified and directed. Note: Pipelines and pump shall be painted in standard red colour as per Fire Fighting Manual and relevant IS codes, using synthetic enamel paint after proper surface preparation.

4

108

-

... More
Repair and maintenance of multi-stage fire service main pump of horizontal split casing type, rated up to 100 HP and delivering a head of 90 metres, operating at 1450 RPM and coupled with an AC induction motor up to 100 HP capacity. The work includes complete servicing of the pump set by replacing worn-out/unserviceable components such as gland packing, bearings, gaskets, nuts, and bolts. Lubricants shall be charged as required to ensure smooth operation. The entire pump set, including base frame and associated pipeline network inside the pump room, shall be thoroughly cleaned, surface-prepared, and painted with two coats of approved shade synthetic enamel paint. Final testing and trial run shall be carried out to confirm smooth and leak-free performance complete all as specified and directed by Engineer-in-Charge. Note: Pipelines and pump shall be painted in standard red colour as per Fire Fighting Manual and relevant IS codes, using synthetic enamel paint after proper surface preparation.

4

108

-

... More
Repair and maintenance of fire service jockey pump, multi-stage, horizontal split casing type, with a discharge capacity of up to 180 LPM at 90 metres head, operating at 2900 RPM and coupled with an AC induction motor of up to 5.5 HP. The work includes complete servicing of the pump by replacing unserviceable components such as gland packing, bearings, gaskets, nuts, and bolts, and charging of lubricants to ensure smooth and efficient operation. The entire pump set, including base frame and associated pipeline network inside the pump room, shall be cleaned, surface-prepared, and painted with two coates of synthetic enamel paint of standard fire-fighting red colour over one coat of primer, as per fire safety norms and relevant IS codes complete all as specified and directed.

4

108

-

... More
Repair and maintenance of fire service terrace/booster/priming pump, multi-stage, horizontal split casing type, with a discharge capacity of 900 LPM at 36 metres head, operating at 2900 RPM and coupled with an AC induction motor. The work includes complete servicing of the pump by replacing unserviceable components such as gland packing, bearings, gaskets, nuts, and bolts, and charging lubricants to ensure smooth and efficient operation. The entire pump set, including base frame and associated pipelines within the pump room, shall be cleaned, surface-prepared, and painted with synthetic enamel paint of standard fire-fighting red colour, as per relevant fire safety norms and IS standards complete all as specified and directed.

2

108

-

... More
S&F in repair ball valve with brass spindle of 25mm dia complete all as specified and directed.

4

108

-

... More
S&F in repair ball valve with brass spindle of 50 mm dia complete all as specified and directed.

4

108

-

... More
Supplying, installing, testing and commissioning of 150mm CI butterfly valve conforming to IS:13095, suitable for waterworks application and hydrostatically tested to a minimum pressure of 20 kg/cm². The body shall be of high-strength cast iron (as per IS:210), circular in shape, designed to withstand a minimum working pressure of 10 kg/cm². The disc shall be heavy-duty cast iron with anti-corrosive epoxy or nickel coating. Valve seat shall be made of high-grade elastomer/nitrile rubber ensuring full 360° sealing in closed position. Shaft shall be of EN-8 grade carbon steel. The valve shall be designed for installation between two pipe flanges with extended rubber edges to ensure leak-proof sealing including taking down old unserviceable valve complete all as specified and directed. (Makes: Audco/Kirloskar/Honeywell)

1

108

-

... More
Supplying, installing, testing and commissioning of 100mm CI butterfly valve conforming to IS:13095, suitable for waterworks application and hydrostatically tested to a minimum pressure of 20 kg/cm². The body shall be of high-strength cast iron (as per IS:210), circular in shape, designed to withstand a minimum working pressure of 10 kg/cm². The disc shall be heavy-duty cast iron with anti-corrosive epoxy or nickel coating. Valve seat shall be made of high-grade elastomer/nitrile rubber ensuring full 360° sealing in closed position. Shaft shall be of EN-8 grade carbon steel. The valve shall be designed for installation between two pipe flanges with extended rubber edges to ensure leak-proof sealing including taking down old unserviceable valve complete all as specified and directed. Approved makes: Audco/Kirloskar/Honeywell.

2

108

-

... More
Supplying, installing, testing and commissioning of 80mm CI butterfly valve conforming to IS:13095, suitable for waterworks application and hydrostatically tested to a minimum pressure of 20 kg/cm². The body shall be of high-strength cast iron (as per IS:210), circular in shape, designed to withstand a minimum working pressure of 10 kg/cm². The disc shall be heavy-duty cast iron with anti-corrosive epoxy or nickel coating. Valve seat shall be made of high-grade elastomer/nitrile rubber ensuring full 360° sealing in closed position. Shaft shall be of EN-8 grade carbon steel. The valve shall be designed for installation between two pipe flanges with extended rubber edges to ensure leak-proof sealing including taking down old unserviceable valve complete all as specified and directed. Approved makes: Audco/Kirloskar/Honeywell.

2

108

-

... More
Supply and fixing in repair approved quartezoid bulb 15 mm dia sprinkler pendent type , IS 15106 chrome plated crossette plate, with temperature rating 68 degree with universal deflector as approved by T.A.C complete with all necessary connections complete all as specified and directed.

4

108

-

... More
Supply Only analogue addressable multisensor detector (Photo + Thermal) with base with galvanised steel, back box and all mounting accessories complete all as specified and directed.

3

108

-

... More
Supply Only analogue smoke detector with all mounting accessories complete all as specified and directed.

3

108

-

... More
Supply only addressable Dual Action Manual Pull staions inside for providing MS box of suitable size for concealing the manual call point in the wall and with mounting accessories complete all as specified and directed.

3

108

-

... More
Supply only addressable Riser Modules with mounting accessories complete all as specified and directed.

2

108

-

... More
Supply only addressable control relay Module with 230 V 2 A where required in a junction box with mounting accessories complete all as specified and directed.

2

108

-

... More
Supply only addressable riser Module for Hooter in a junction box with mounting accessories complete all as specified and directed.

2

108

-

... More
Supply only Electronic Hooter include provide MS box suitable size for concealing the hooter in the wall mounting accessories complete all as specified and directed.

2

108

-

... More
Supply only Conventional Dual Action Manual Pull staions inside for providing MS box of suitable size for concealing the manual call point in the wall and with mounting accessories complete all as specified and directed.

5

108

-

... More
Supply only Electronic Hooter include provide PVC box suitable size for concealing the hooter in the wall mounting accessories complete all as specified and directed.

2

108

-

... More
Supply only EST network card for addressable fire alarm control panel complete all as specified and directed.

1

108

-

... More
Supply only EST make, power supply unit for EST 3 addressable fire alarm control panel complete all as specified and directed.

1

108

-

... More
Supply and fixing of micro processed based upto 16 zone conventional fire alarm control panel with standards NFPA 72 can operate up to 30 detectors per zone, Board should consist of RS 485 ,2 programmable relay, support port for class B style input devices with networkable ability the above price includes two batteries, installations, commissioning, and networking with main integration network including taking down old unserviceable panel complete all as specified and directed.

1

108

-



Evaluation Notes How It Works ?

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.