Military Engineer Services Tender
To inquire about any e-tender the Andaman & Nicobar Islands government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder one can find every eprocurement Punjab tender on BidAssist. BidAassist has collated each and every Eproc Andaman & Nicobar Island Tender on its website. Looking for Andaman & Nicobar Island tenders online or going through the cumbersome government websites for it, has been made easier with the help of BidAssist.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date11 Jun 2024
Closing DateCancelled
Tender Amount₹ 70,00,000
Costs
EMD
₹ 1,30,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_658949_1Tender No
801250/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
ENGINE PROTECTION: Battery voltage monitoring, protection, overspeed shutdown, low oil pressure warning and shut down, low coolant temperature warning, fail to start, cranking lockout, sensor failure indication, low fuel warning or shut down.
-
-
-
ALTERNATOR: Synchronous alternator rated at 400KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 400C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class - F/H insulation and voltage regulation + 1%, voltage variation + 5%,overload duration 10% for one hour in every 12 hours of continuous operation, provision of suitable space heaters to maintain the winding temperature automatically.
-
-
-
Base frame and foundation: Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacurer.
-
-
-
Fuel Tank: Daily service fuel tank of capacity 12 hrs continous running and fabricated out of 3 mm thick MS sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia complete with valves, level indications & accessories as required as per specifications.
-
-
-
Starting System: 12V/24V DC starting system comprising of starter motors, voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries (25 plates, 180 Amp Hour capacity lead acid type) as required as per specifications.
-
-
-
Accoustic Enclosure: Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphaere as per specifications.
-
-
-
Exhaust System: Supplying and fixing exhaust gas piping of required length and suitable dia. Welded black MS 'B' Class pipe conforming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool /Rockwool, 50 mm thick wiremesh & aluminum cladding etc., as required as per specifications.
-
-
-
Operator panel features: Display the utility data/ AC bus data having 320 x 240 pixels graphic LED back light LCD with bar graph for displaying electrical parameters, auto manual start stop, fault reset and lamp test/ panel lamp switches, alpha numeric display with push buttons, LED Lamps including genset running remote start, not in auto, common shutdown, common warning, manual run mode, auto mode and stop.
-
-
-
Control functions: Paralleling control functions Digital frequency synchronization and voltage matching, Isochronous KW and KVAR, load sharing controls, drop KW and KVAR, Sync check, extended paralleling, Digital power transfer control (AMF) provide load transfer, operation in open or closed transition or soft (ramping) transfer mode:-
(a) Alternator data - Line to neutral and line to line AC volts , three phase AC current, Frequency, KW, KVAR, power factor KVA (3 phase and total)
(b) Engine data DC voltage, Engine speed, lub oil pressure, coolant temperature/ low level, (c) Other data Genset model, Start attempts, starts, running hours, KW hours, Load profile, Fault history, data logging and fault simulation (d) Digital governing - Integrated digital electronic isochronous governor, temperature dynamic governing (e) Digital voltage regulation - Integrated digital electronic voltage regulator, three phase four wire line to line sensing, configurable torque matching
(m) AC protection - Over current and short circuit shutdown, Over current warning, single/three phase fault regulation, Over and under voltage shutdown, Over and under frequency Shutdown, Overload warning with alarm, Reverse power shutdown, Field over load
-
-
-
Notes: Unit rate quoted by the tenderer shall deemed to be inclusive for the following:-
(i) Providing the artificial heat/water load, fuel, oil etc for testing the DG set at site. (ii) All civil works for making good the disturbed surface during installation. (iii) The DG Set should comply with all the latest CPCB Norms.
(iv) 04 numbers of GI strip earthing complete with 32x6 mm GI strip. (v) Contractor shall ensure that this 400 KVA DG set is synchronized with other existing DG sets in the CAPTIVE POWER HOUSE and ensure that it works perfectly without any extra cost.
(vi) Taking down old DG set of any capacity from captive power house and unload & handover the same to MES store yard as directed by Engineer In Charge.
-
-
-