Military Engineer Services Tender
To inquire about any e-tender the Andaman & Nicobar Islands government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder one can find every eprocurement Punjab tender on BidAssist. BidAassist has collated each and every Eproc Andaman & Nicobar Island Tender on its website. Looking for Andaman & Nicobar Island tenders online or going through the cumbersome government websites for it, has been made easier with the help of BidAssist.
Military Engineer Services - MES Tender
Civil And Construction
Civil Works Others
Eprocure
Opening Date7 May 2024
Closing Date1 Jun 2024
Tender Amount₹ 42,50,000
Costs
EMD
₹ 85,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_652683_1Bid Award Id
ViewTender No
8397/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
M&L for fabrication for LT Feeder Pillar Box/ Panel Boards doors made out of 2.00 / 3.15mm thick mild steel sheet by applying two coats of synthetic enamel paint over a coat of red oxide primer with hinges complete all as specified and as directed by Engineer-in-Charge.
75
-
-
Supply only aluminium tower bolts, 200mm long bright bolt including connected accessories for fixing on front/rear side of the doors for locking LT FP Boxes complete all as specified and as directed by Engineer-in-Charge.
4
-
-
Supply only door hinges of LT feeder pillar/Panel box complete with welding complete all as specified and as directed by Engineer-in-Charge.
6
-
-
Supply only aluminium cable lugs of following sizes of any type including reduced terminals/ bottle lugs/ connectors/ ferrules complete all as specified and as directed by Engineer-in-Charge.
Note: Each lug/ reduced terminals/ bottle lugs/ connectors/ ferrules shall be measured as one unit.
-
-
-
10 Sqmm
15
-
-
16 Sqmm
20
-
-
25 Sqmm
25
-
-
35 Sqmm
25
-
-
50 Sqmm
20
-
-
70 Sqmm
18
-
-
95 Sqmm
18
-
-
120 Sqmm
15
-
-
150 Sqmm
12
-
-
185Sqmm
12
-
-
240Sqmm
15
-
-
300Sqmm
15
-
-
400Sqmm
15
-
-
500Sqmm
6
-
-
630 Sqmm
6
-
-
Supply only double compression brass cable glands complete all as specified and as directed by Engineer-in-Charge.
Note: Each gland shall be measured as one unit.
-
-
-
10 - 16 Sqmm
2
-
-
25 - 35 Sqmm
2
-
-
50 - 70 Sqmm
2
-
-
95-120 Sqmm
1
-
-
150-185 Sqmm
2
-
-
Supply only digital MFM meter (V, A, PF, W) class 0.5/1.0 accuracy, CT secondary selectable range 5/1 A with including necessary fabrication requaired and painting the effected area with existing paint complete all as specified and as directed by Engineer-in-Charge.
2
-
-
Supply only CTs moulded type class-1.0, 5VA burden suitable for AC 230V (phase-earth ) 50 Hz supply busbar system of suitable for ratio range 100 to 800/5 Amps capacity complete all as specified and as directed by Engineer-in-Charge.
2
-
-
Supply only LED Indicating lamp (R-Y-B) complete all as specified and as directed by Engineer-in-Charge.
18
-
-
Supply only LT superior quality high grade rubber insulation tape 25 Cm width 2.5m long complete all as specified and as directed by Engineer-in-Charge.
45
-
-
Supply only insulators for supporting Bus bars of voltage grade 550 Volts complete all as specified and as directed by Engineer-in-Charge.
3
-
-
Supply and fix as in repair of MCCB 630 Amps,TPN/ 4 pole, 415 volt, breaking capacity 50 KA, Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
1
-
-
Supply & fix as in repair of sheet metal enclosure of thickness 2.00 mm along with MCCB 630 Amps, TPN/ 4 pole, breaking capacity 50 KA, Thermal magnetic type including spreader links complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
1
-
-
Supply and fix in repair of MCCB 400 Amps,TPN/ 4 pole, 415 volt, breaking capacity 36 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
1
-
-
Supply & fix as in repair of sheet metal enclosure of thickness 2.00 mm along with MCCB 400 Amps, TPN/ 4 pole, breaking capacity 36 KA, Thermal magnetic type including spreader links complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
1
-
-
Supply and fix in repair of MCCB 250Amps,TPN/ 4 pole, 415 volt, breaking capacity 36 KAThermal magnetic type complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
2
-
-
Supply and fix in repair of MCCB 200Amps,TPN/ 4 pole, 415 volt, breaking capacity 25 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
1
-
-
Supply and fix in repair of MCCB 160 Amps, TPN/4 pole, 415 volt, breaking capacity 25 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
2
-
-
Supply and fix as in repair of MCCB 100 Amps, TPN/4 pole, 415 volt, breaking capacity 16 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
3
-
-
Supply and fix as in repair of MCCB 63 Amps, TPN/4 pole, 415 volt, breaking capacity 16 KA Thermal magnetic type complete all as specified and as directed by Engineer-in-Charge.
Note :(i) MCCB should be Ics = 100 % Icu (ii). MCCB should be adjustable O/L (0.8-1)In and S/C - (5-10)ln
2
-
-
Taking down of unserviciable old UG Cable of any size and any type complete all as specified and as directed by Engineer-in-Charge.
1180
-
-
Suppy and laying in trenches, fixed on walls, passing through pipes, jointing and testing of electric LT cables, XLPE insulated, PVC sheathed, galvanised steel strip or wire armoured electric power cables with stranded aluminium conductors 1100 Volts grade complete all as specified and as directed by Engineer-in-Charge for the following size :-
Note:
(i) The rates shall be inclusive of Cable lugs at both ends of cable and end termination kits will be measured and paid seperately.
(ii) Excavation earthwork, returning and refilling shall be measured and paid seperately.
(iii) Cable Joint kit if required shall be measured and paid seperately.
(iv) Insulation Resistance value of cable shall be recorded before and after laying of cable.
-
-
-
3.5 Core 25 Sqmm
80
-
-
3.5 Core 35 Sqmm
85
-
-
3.5 Core 50 Sqmm
90
-
-
3.5 Core 70 Sqmm
80
-
-
3.5 Core 95 Sqmm
85
-
-
3.5 Core 150 Sqmm
200
-
-
3.5 Core 185 Sqmm
190
-
-
3.5 Core 240 Sqmm
60
-
-
3.5 Core 300 Sqmm
190
-
-
3.5 Core 400 Sqmm
120
-
-
Taking down and relaying of serviciable power cable of size 10 Sqmm to 35 Sq mm 3.5/4 Core XLPE / PVC insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade along with DWC pipe laid in trenches / duct with saddling / on pole / through DWC pipe including all necessary fixing arrangement such as lugs and end termination etc complete all as specified and as directed by Engineer-in-Charge.
120
-
-
Taking down and relaying of serviciable power cable of size 50 Sqmm 3.5 core to 95 Sq mm 3.5 core XLPE / PVC insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade along with DWC pipe laid in trenches / duct with shaddling / on pole including all necessary fixing arrangement such as lugs and end termination etc complete all as specified and as directed by Engineer-in-Charge.
130
-
-
Taking down and relaying of serviciable power cable of size 120 Sqmm 3.5 core to 240 Sq mm 3.5 core XLPE / PVC insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade along with DWC pipe laid in trenches / duct with shaddling / on pole including all necessary fixing arrangement such as lugs and end termination etc complete all as specified and as directed by Engineer-in-Charge.
85
-
-
Taking down and relaying of serviciable power cable of size 300 Sqmm 3.5 core to 630 Sq mm 3.5 core XLPE / PVC insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade along with DWC pipe laid in trenches / duct with shaddling / on pole including all necessary fixing arrangement such as lugs and end termination etc complete all as specified and as directed by Engineer-in-Charge.
60
-
-
Note For Item Nos 25,26,27 & 28:
(i) Excavation earth work, returning and refilling shall be measured and paid seperately under relevant items.
(ii) The cost for replacement of DWC pipe against defective one shall be measured and paid seperately under relevant item.
(iii) Quoted rate inclusive of laying only serviceable portion of DWC pipe.
-
-
-
Supply & Laying DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 50 mm, polythylene confirming to IS 16205 part-24 including coupler & Bend with smoooth internal and corrugated external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge.
402
-
-
Supply & Laying DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 63 mm, polythylene confirming to IS 16205 part-24 including coupler & Bend with smoooth inernal and corrugated external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge.
342
-
-
Supply & Laying DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 77 mm, polythylene confirming to IS 16205 part-24 including coupler & Bend with smoooth inernal and corrugated external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge.
528
-
-
Supply & Laying DWC (Double Wall corrugated) HDPE pipe ISI marked of outer dia of 90 mm, polythylene confirming to IS 16205 part-24 including coupler & Bend with smoooth inernal and corrugated external surface for non pressue under ground cable complete all as specified and as directed by Engineer-in-Charge.
144
-
-
Taking down of old GI Pipe of any size including necessary excavation (if rerquired separately) complete all as specified and as directed by Engineer-in-Charge.
24
-
-
Supply and laying GI pipe of light grade 40 mm dia ISI marked all fitting fixture for fixing with wall / road crossing etc complete all as specified and as directed by Engineer-in-Charge.
Note :Road cutting shall be measured and paid separately.
6
-
-
Supply and laying GI pipe of light grade 50 mm dia ISI marked all fitting fixture for fixing with wall / road crossing etc complete all as specified and as directed by Engineer-in-Charge. Note :
(i) Road cutting shall be measured and paid separately.
6
-
-
Supply and laying GI pipe of light grade 63 mm dia ISI marked all fitting fixture for fixing with wall / road crossing etc complete all as specified and as directed by Engineer-in-Charge.
Note: Road cutting shall be measured and paid separately.
6
-
-
Supply and laying GI pipe of light grade 80 mm dia ISI marked all fitting fixture for fixing with wall / road crossing etc.complete all as specified and as directed by Engineer-in-Charge.
Note : Road cutting shall be measured and paid separately.
6
-
-
Excavation in trenches any soft/loose soil not exc 1.5 mtr wide and not exc 1.5m in depth for foundation, pipe, laying of cable etc not exc 10 Sqm on plan and not exc 1.5 m in depth and getting out complete all as specified and as directed by Engineer-in-Charge.
283.5
-
-
Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil complete all as specified and as directed by Engineer-in-Charge.
252.32
-
-
Removing excavated materials (soil) to a distance not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meters above the starting point complete all as specified and as directed by Engineer-in-Charge.
31.19
-
-
M & L for Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of road repair bitumen instant cold mix matching with the surroundings complete all as specified and as directed by Engineer-in-Charge.
4.86
-
-
S & F for cable jointing kit of size 10 to 16 Sqmm 3.5 core,1100Volt grade cable for indoor / outdoor end termination joint kit, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable complete all as specified and as directed by Engineer-in-Charge.
4
-
-
All as per item No.73.00 above but of capacity size 25 to 50 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
6
-
-
All as per item No.73.00 above but of capacity size 70 to 120 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
4
-
-
All as per item No.73.00 above but of capacity size 150 to 185 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
4
-
-
All as per item No.73.00 above but of capacity size 240 to 300 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
2
-
-
All as per item No.73.00 above but of capacity size 400 to 500 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
2
-
-
M/L for attending LT breakdown complaints/defects from transformer LT terminal box upto Bldg feeder pillar box/DBs with connected switchgears, cables etc complete for making the continuity of supply after rectifying the defects of the electrical network by carrying out with the following scope of work:- (i) cable faults : disconnecting the both ends of cable and check the insulation resistance value.Physical inspection / tracing the cable in cable duct/ trenches. Cutting/disconnecting damaged portion and re-checking for insulation value, and make the cable connection after rectification at both end terminations to restore the power supply.
(ii) unserviceable control switch gears / MCCBs / MCB: remove the MCCB/MCB from the panel board and clean the carbonized / burnt surfaces with varnish / CRC solution to make good and fix the new MCCB of suitable rating and connect the cable to MCCB terminals with proper lugging and by applying proper torque to avoid loose connections. spreader links shall be provided if necessary as per site requirement.
(iii) Terminals/lugs failure: check for any cable terminal damage / melting by over heating, loose contacts. the damaged portion of cable shall be removed and fixing the lugs and terminate the cable by applying proper torque to avoid loose connections and proper re-distribution of over loading of cable complete all as specifed and as directed.
Note :- (i) cable joint kit, MCCB/MCB, lugs and cable fault detection by fault finding machine, any excavation earth work shall be measured and paid seperately under relevant items. spreader links /insulation tape shall be deemed to be included in the rate quoted.
(iii) Each Breakdown complaint/defect attended shall be measured as one job through job card.
(iv) The contractor shall depute necessary man power on daily basis for rectifying the jobs including sundays and holidays.
6
-
-
M&L for detecting LT UG cable faults located in any stretch/ depth with sophisticated cable fault locator consisting of microprocessor based pre-locator system, surge generator of capacity upto 1.1 KV, fault pin point surge wave reciever, cable indentification instrument , cable tracer for exact location of under ground cable routes complete all as specified and as directed by Engineer-in-Charge. Note: The rate quoted deemed to be inclusive of transportation of equipment from any location and charges for service engineer for identifying the fault including their boarding & lodging complete.
2
-
-
Taking down of old unserviceable Joit Kit complete all as specified and as directed by Engineer-in-Charge.
15
-
-
S & F for cable jointing kit for 1100Volt grade cable for Straight through, heat shrinkable type joint complete with jointing materials and accessories suitable for LT, XLPE armoured aluminium conductor cable of size 10 to 16 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
4
-
-
All as per item No 82.00 above but of size 25 to 50 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
3
-
-
All as per item No 82.00 above but of size 70 to 120 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
3
-
-
All as per item No 82.00 above but of size 150 to 185 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
2
-
-
All as per item No 82.00 above but of size 240 to 300 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-Charge.
3
-
-
Taking down and rerouting / Discipline the serviciable Power Cable on wall /cable duct of size 16 to 50 Sqmm 3.5/4 core with saddling, aluminium trunks/tray with required size of screw inside cable duct / on wall complete all as specified and as directed by Engineer-in-Charge.
60
-
-
Taking down and rerouting / Discipline the serviciable Power Cable on wall /cable duct of size 70 to 185 Sqmm 3.5 core with saddling, aluminium patti with requard size of screw inside cable duct / on wall complete all as specified and as directed by Engineer-in-Charge.
55
-
-
Taking Down of old unserviceable Junction box/ Busbar chamber of any type and any size complete all as specified and as directed by Engineer-in-Charge.
2
-
-
Supply & fix as in repair sheet metal enclosed TPN Aluminium bus bar chamber with IP 54 protection having bus bar of rating 200 Amps with provision for minimum 04 outgoing ways and the bus bar design shall be step type complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply & fix as in repair sheet metal enclosed TPN Aluminium bus bar chamber with IP 54 protection having bus bar of rating 100 Amps with provision for minimum 04 outgoing ways and the bus bar design shall be step type complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Material and labour earthing with copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead, buried directly in ground to a depth not less than 2.25m deep below normal ground level with top edge of the earth plate not less than 1.5m deep below normal ground level connected to 20×3mm copper strip as earthing lead by means of nuts, bolts and washers of steel after welding of copper strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with aluminium XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site as specified in plate No 3 of SSR Part-I including testing on completion complete all as specified and as directed by Engineer-in-Charge. NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe,Copper earth strip upto 7.5 m long for connecting to test point etc as required at site for complete earthing and dismantling of old defective earthpit.
2
-
-
Material and labour for earthing with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertically to a depth of not less than 2.25m below ground level connected to galvanised iron strip 25 mm x 3 mm by means of GI Welding made out of galvanised iron mild steel and 40 mm dia GI pipe "light grade" for protection of earth lead, 20 mm dia GI pipe for watering and earth plate surrounded by packed layer of coal and common salt, 15cm thick all around bottom and top, watering pipe of 20 mm bore of light grade with funnel all as shown in electrical plate No 3 of SSR Part-I (2009) and connecting to earthing test point, main switch board, transformer neutral and testing on completion as directed including earthing pit in PCC (1:3:6) type C-1, pre-cast reinforced cover with MS XPM Jalli, RCC 1:1.5:3 cover slab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar, wire mesh and testing complete all as specified and as directed including dismantling old defective earth pit.
Note: (i) Cost of GI earth Strip and GI protection pipe upto 7.5m length shall be deemed to be included in the rate quoted for this item.
(ii) The unit rate shall also includes for Wire mesh, funnel, excavation.returninng & filling. PCC chamber pit,RCC cover & test point.
(iii) If the desired earth resistance is not achived during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissible.
2
-
-
Material and labour for earthing with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground vertically to a depth of not less than 2.25m below ground level connected to galvanised iron strip 32 mm x 6 mm by means of GI Welding made out of galvanised iron mild steel and 40 mm dia GI pipe "light grade" for protection of earth lead, 20 mm dia GI pipe for watering and earth plate surrounded by packed layer of coal and common salt, 15cm thick all around bottom and top, watering pipe of 20 mm bore of light grade with funnel all as shown in electrical plate No 3 of SSR Part-I (2009) and connecting to earthing test point, main switch board, transformer neutral and testing on completion as directed including earthing pit in PCC (1:3:6) type C-1, pre-cast reinforced cover with MS XPM Jalli, RCC 1:1.5:3 cover slab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar, wire mesh and testing complete all as specified and as directed including dismantling old defective earth pit complete all as specified and as directed by Engineer-in-Charge. Note: (i) Cost of GI earth Strip and GI protection pipe upto 7.5m length shall be deemed to be included in the rate quoted for this item.
(ii) The unit rate shall also includes for Wire mesh, funnel, excavation.returninng & filling. PCC chamber pit,RCC cover & test point.
(iii) If the desired earth resistance is not achived during testing as per IS the complete earthing shall be carried out by the contractor at his own cost and no extra claim shall be admissible.
2
-
-
Dismantling defective old PCC Earth pit including broken cover of earthing pit chamber of any size and supply and fixing new PCC earthing pit in PCC (1:3:6) type C-1 of outer size 300X300 X200mm and inner Size 200X200X200mm and pre-cast reinforced cover with RCC 1:1.5:3 cover slab of size 300 x 300 x 100 mm with one handle made out of 8 mm dia round bar in center including necessary earth work complete all as specified and as directed by Engineer-in-Charge.
15
-
-
Dismantling the cable connections of four pole/ three pole Air circuit breaker of capacity 800 to 1250 Amps ,415 V 50 HZ of L&T Make/C&S/GE/ABB make, strip opening the Air circuit breaker, inspecting the parts for serviceability/overhauling complete and carrying out the following repairs/maintenance :- a) Cleaning the insulation parts including bushings with CRC solution.
b) Checking the alignment and condition of movable and stationary contacts and adjust them all as per manufacturer's instructional manual.
c) Check the bolts, nuts, washers, cotter pins and all terminal connections are in place and tights. Replace the worn-out parts. d) Check arc chutes for damage .
e) Clean and lubricate the operating mechanism with a light machine oil for pins and bearings and with a non-hardening grease for the wearing surfaces . Adjust breaker operating mechanism all as per manufacturer's instructional manual . f) Checking / inspecting shunt trip coil for serviceability and replacing the same if required. g) Checking control device free for operation.
j) Check after servicing the circuit breaker to verify the contacts move to the fully opened and fully closed positions, that there is an absence of friction and that the electrical operation is functional.
Note : The rate quoted deemed to be inclusive of T&P and minor spares like lubricants, nuts/bolts/washers/ pins etc. Major spares like Shunt release & trip coil etc will be measured & paid separately under relevant schedule items.
5
-
-
Supply only CTs suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing make complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply only auxiliary contact block suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing make complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply only arcing contacts (fixed/ moving) suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing make complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply only arc chutes (for 415 V) suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing make complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply only shunt release / under voltage release (110 /220 V DC or 240 V/415 V AC) suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing make complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply only cluster contact suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing make complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply only trip coil suitable for air circuit breakers of rating 800 Amps to 1250 Amps as all per existing make complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply only microprocessor based relay suitable for legrand/ C&S/ L&T/ Schneider make air circuit breakers of rating 800 Amps to 1250 Amps as per existing make complete all as specified and as directed by Engineer-in-Charge.
3
-
-
Supply and fixing as in repair service wire aluminium conductor Weather Proof 06 Sqmm two core complete all as specified and as directed by Engineer-in-Charge.
90
-
-
Supply and fixing as in repair service wire aluminium conductor Weather Proof 10 Sqmm two core complete all as specified and as directed by Engineer-in-Charge.
180
-
-
Supply and laying broken stone or Boulders filling of Gauge not exc. 63 mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface complete all as specified and as directed by Engineer-in-Charge.
6
-
-
Material and labour for cross arms, bracing, supports, clamps and back plate fabricated from structural MS section for gate including nuts, bolts, washers, welding, bending, cold or hot, drilling holes for bolts in any shape or size as indicated or directed complete all as specified and as directed by Engineer-in-Charge.
1
-
-
Supply and fixing as in repair for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 20 mm x 3 mm thick, copper strip using porcelain clit/post insulators, complete all as specified and as directed by Engineer-in-Charge.
15
-
-
Supply and fixing as in repair for GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 32 mm x 6mm thick, Galvanised using porcelain clit/post insulators, complete all as specified and as directed by Engineer-in-Charge.
18
-
-
Supply and fixing as in repair for GI earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required for 25 mm x 3 mm thick, Galvanised using porcelain clit/post insulators, complete all as specified and as directed by Engineer-in-Charge.
12
-
-
Supply and fix as in repair MCB 40 - 100 Amp TPN/4 pole, 415 volt, breaking capacity 16 KA complete all as specified and as directed by Engineer-in-Charge.
3
-
-
M & L for Cutting vegetation around the LT panel upto 1.5m distance and surface dressing not exceeding 15 cm deep including removing the materials to a distance not-exc 60m complete all as specified and as directed by Engineer-in-Charge.
10
-
-
Supply, installing, testing and commissioning of LT panel board factory made indoor type, fabricated out of 2.00 mm thick CRCA sheet, floor mounting, dust and vermin proof, suitable for voltage 415volts 3 Phase 4 wire weather proof, with IP-43 protection, with back door openable (Screwed), including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with aluminium busbar (TPN), suitable double compression copper cable glands complete in all respect and including PCC work and provn of the following and including dismantling old LT panels:
a) Aluminium Bus bar of rating 1200-A mounted on porcelain insulator - 01 Set ( Set of 4 Nos) with PVC sleeve insulation.
b) Incoming:
(i) ACB 800 Amps, 4P, MDO, 50 Hz, 415 V with minimum rupturing capacity 50 KA, Ics=100%Icu with advanced self powered micro processor based protection units having adjustable overload setting 40% to100%, Adjustable short circuit and earth fault protection- 01 No.
c) Outgoing:
Through Bus bar
d) Digital multi function meter for measuring voltage, current & frequency - 01 No.
f) RYB LED indicator- 01 set
Note:
(i) Drawing shall be approved by Accepting Officer before placement of order duly recommended by Engineer-in-charge. (ii)LT panel shall be puchaged from the one of the makes specified in PS attached alongwith tender documents.
1
-
-
Supply, installing, testing and commissioning of LT panel board factory made outdoor type, double door, fabricated out of 3.15 mm thick CRCA sheet, floor mounting, dust and vermin proof, suitable for voltage 415 V 3 Phase 4 wire weather proof, with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing switchgears/ACB/MCCB etc with locking arrangement, with back door openable (Screwed), including painting with two coats of epoxy powder paint over a coat of primer after under going a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate and with aluminium busbar (TPN), suitable double compression copper cable glands complete in all respect and including PCC work and provn of the following and including dismantling old LT panels:
a) Aluminium Bus bar of rating1000-A mounted on porcelain insulator - 01 Set ( Set of 4 Nos) with PVC sleeve insulation.
b) Incoming:
(i) ACB 630 Amps, 4P, MDO, 50 Hz, 415 V with minimum rupturing capacity 50 KA, Ics=100%Icu with advanced self powered micro processor based protection units having adjustable overload setting 40% to100%, Adjustable short circuit and earth fault protection- 01 No. (provision for compartment only with busbar orientation suitable for fixing of approved make of ACB )
c) Outgoing:
Through Bus bar
d) Digital Voltmeter of rating 0-500 volts with selector switch - 01 No.
e) Digital Amp meter of rating 0-1000 Amp, selectable CT seconday as 5/1 A with suitable rating of CT's - 01 Nos (set of three)
f) RYB LED indicator- 01 set
Note: (i) The ACBs for incomer shall be measured and paid seperately under relevant item as supply and fixing.
(ii) Drawing shall be approved by Accepting Officer before placement of order duly recommended by Engineer-in-charge. (iii)LT panel shall be purchased from the one of the makes specified in PS attached alongwith tender documents.
2
-
-