Military Engineer Services Tender
To inquire about any e-tender the Andaman & Nicobar Islands government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder one can find every eprocurement Punjab tender on BidAssist. BidAassist has collated each and every Eproc Andaman & Nicobar Island Tender on its website. Looking for Andaman & Nicobar Island tenders online or going through the cumbersome government websites for it, has been made easier with the help of BidAssist.
Military Engineer Services - MES Tender
Electrical Generators And Transformers
Electrical and Electronics
Aerospace and Defence
Eprocure
Opening Date1 Jun 2024
Closing Date8 Jul 2024
Tender Amount₹ 44,50,000
Costs
EMD
₹ 89,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_657263_1Bid Award Id
ViewTender No
8385/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
NOTE :
(i) The OEM of the transformers should have in house LAB Certificate for Accreditation from National Accreditation Board for Testing and Calibration laboratories. (iii) Manufacturer /OEM must have type test / short circuit reports for each & every rating from CPRI / ERDA ( matching all the major parameters including the Loss Figure) shall not be older than 5 years. (iv) Core shall be procured from one of these manufacturers – Posco/Nippon/NLMK/AK Steels or NOVEX Trader CRGO and CRGO core grade used should be M-OH / ZDKH / TCH only. Procurement, Mill's Test Certificate / Invoice from supplier /Bill of landing Bill of entry certificate by CUSTOMS shall be provided. The OEM Should have in house core cutting / slitting Machine. Burr level should be less than 10 Microns. (v) CPRI Short circuit test report for exactly similar transformer (matching all major electrical parameters including Loss Figure) shall not be older than 5 years to be furnished). (vi) OEM should be BIS and BEE certified for all the ratings of the transformer that are to be submitted. (vii) Rate quoted includes the cost of making and Testing of control wiring connection at the Transformer. (viii) Expenses / cost for FAT and necessary Travel / freight / conveyance / stay expenses for inspecting/ testing officers as nominated by the accepting Officer for FAT shall be included in the rate quoted. (ix) Tender/ contractor shall submit all the necessary certificates/ material Invoice of core as mentioned in above note (a) to (e) along with Guaranteed Technical Particulars (GTP) from the OEM of transformer for make Approval by the Accepting Officer before placing the Order.
(x) All technical drawing of the transformer/technical parameter as required shall be got approved by the Accepting officer duly recommended by Engineer-in-Charge before placing of order.
-
-
-
Supply and install AC 33 KV CT/PT Metering Pole mounted unit with digital electronic meter, Meter connection cabling passing through in flexible PVC conduit pipe complete with necessary suitable MS channel (MC-100) structure with necessary foundation including welding, nuts bolts, clamps etc including painting to MS channel structure surfaces with two coat of synthetic enamel paint over a coat of redoxide primer with following specifications:- (a) Outdoor type oil immersed, pole mounted 33 KV CT/PT combined unit with CT ratio 60/1-1, class-0.5, burden 15VA, 33KV 50 Hz with insulation level 75KV/170KVp as per IS: 2705/1992 and PT 33KV/110 volt, class-0.5, burden per phase-50 VA, 3 phase 50 Hz, insulation level 75KV/170 KVp, voltage factor 1.2 CNT conforming to IS : 3156/1992. Make- L&T/CG/Schneider/ABB
Note:- (1) Electric meter to be installed in weather proof meter box made of UV stabilized transparent polycarbonate/flame retarded high engineer plastic to be fixed along outdoor steel structure poles including fixing arrangement. This all will include the rate quoted above and nothing extra on this account will be admissible.
(2) Electric meter installed will be direct digital reading and also meter reading through meter reading instrument digital with printing facility to measure on line 33 KV consumed unit, power factor, voltage and other important parameters
1
-
-
Supplying and laying XLPE cable for 33000 volts grade system, heavy duty, XLPE insulated screened PVC bedded galvanised steel strip wire around electric cable of aluminium conductor layed in trenches, induct, on pole, as required at site including of testing of cable 3 core 95 sqmm (Earthed) complete all as specified and directed by Engineer-in-Charge.
15
-
-
Supply and fixing cable jointing kit for 33 KV (earthed) grade cable for outdoor termination cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XPLE armoured aluminium cable of size 3 core 95 sqmm complete all as specified and directed by Engineer-in-Charge.
2
-
-
Material and labour for switch air break gang operated triple pole mechanically operated mounted on HT insulators (09 insulator type) with DO fuse unit insulator barrel type fuse of suitable rating and MS galvanised steel frame with operating mechanism worked from ground level incl operating rod and operating handle with 33 KV insulation for current rating up to 200 Amp 33000 volts complete all as specified and directed by Engineer-in-Charge.
1
-
-
Material and labour expulsion type surge arrester (lightning arrestors) confirming to IS-3070 (Part-1) having voltage rating 36 KV, rated frequency 50 Hz, nominal discharge current 65 KA (heavy duty) expulsion type transmission class for outdoor use, non linear resistor type, horn gap and choking coil complete with all fittings suitable for 36 KV, 3 phase earthed distribution system complete all as specified and directed by Engineer-in-Charge.
1
-
-
Material and labour for mild steel cross arms, bracings supports, clamps and back plates fabricated from structural steel sections, channel including nuts, bolts, washers welding, bending cold or not, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engineer-in-Charge.
2
-
-
Material and labour for disc type insulator, porcelain, vitreous 145mm high and 255 mm dia ball and socket type, white, brown or green, single disc assembly for tension with tension clamps of GI including provision of nuts and bolts for conductors, working pressure 36000 volts grade, complete all as specified and directed by Engineer-in-Charge.
3
-
-
M&L for supply and fix pin type insulator porcelain vitreous white / brown / green insulators including one galvanised mild steel spindle two galvanised iron washer & one galvanised iron washer & one galvanised iron nut 100 mm height 65 mm dia for 1100 volts grade complete all as specified and directed by Engineer-in-Charge.
3
-
-
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT , 25 cm x20cm size complete all as specified and directed by Engineer-in-Charge.
4
-
-
Material and labour for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for LT , 20 cm x15 cm size complete all as specified and directed by Engineer-in-Charge.
4
-
-
Supply and laying galvanized steel tubing , light grade 80 mm bore laid in trenches / fixed pole /wall or laid in any position complete with all fitting light grade complete all as specified and directed by Engineer-in-Charge.
15
-
-
Supply and Fixing LT feeder pillar box with CRCA sheet and CPRI approved,outdoor cubical type, IP-56, confirming to IS 61439 part-I & II, 415 Volts, 50 Hz, free floor mounted front and back double door openable, made out of 3.15 mm thick cold rolled MS sheet of suitable size to accommodate the following items, vermin proof, dust proof, supported on and including ISMC 75 X 40mm powder coated steel frame and totally powder coated with epoxy siemen grey colour from inside and outside with locking arrangement and fixing arrangement i.e nuts, bolts, washers, clamps etc, with naturally air cooled copper bus bar 4 strip suitable for 600 Amps with detachable gland plate for incoming and outgoing cable including termination of cable ends both incoming and outgoing with sufficient working space inside including installing, testing and commissioning complete all as specified and as directed consisting of following :- (a) Incoming
(i) MCCB 320 Amps 36 KA 4 Pole -01 No, 415volt, 50Hz
(b) Outgoing
(i) MCCB 160 Amp 36 KA 4 Pole -01 Nos ,415 Volts,50 Hz (ii) MCCB 100 Amp 25 KA 4 Pole -01 No ,415 Volts,50 Hz (iii) MCCB 63 Amp 16 KA 4 Pole -01 No ,415 Volts 50 Hz (c) RYB indication LED type ,240 V, 50 Hz, AC supply -01 No, Set of 03 (d) Ammeter digital, 96x96mm, with suitable ratio CTs with built in selector switch -1 No
(e) Volt meter digital type of range 0-500 Volts, 96x96mm with built in selector switch -1 No (f) Changeover switch 250 Amp ,4 Pole ,50 Hz front operated 415 Volts on load type Note : (i) All wiring used in panel board should be with FRLS grade copper conductor of suitable size.(ii) All MCCBs must be thermal magnetic release with over load (O/L), short circuit protection (S/C)ICS= 100% ICU
1
-
-
Supply and Fixing LT feeder pillar box with CRCA sheet and CPRI approved,outdoor cubical type, IP-56, confirming to IS 61439 part-I & II, 415 Volts, 50 Hz, free floor mounted front and back double door openable, made out of 3.15 mm thick cold rolled MS sheet of suitable size to accommodate the following items, vermin proof, dust proof, supported on and including ISMC 75 X 40mm powder coated steel frame and totally powder coated with epoxy siemen grey colour from inside and outside with locking arrangement and fixing arrangement i.e nuts, bolts, washers, clamps etc, with naturally air cooled copper bus bar 4 strip suitable for 600 Amps with detachable gland plate for incoming and outgoing cable including termination of cable ends both incoming and outgoing with sufficient working space inside including installing, testing and commissioning complete all as specified and as directed consisting of following :- (a) Incoming
(i) MCCB 250 Amps 36 KA 4 Pole -01 No, 415volt, 50Hz
(b) Outgoing
(i) MCCB 160 Amp 36 KA 4 Pole -02 Nos ,415 Volts,50 Hz (ii) MCCB 63 Amp 25 KA 4 Pole -01 No ,415 Volts,50 Hz (iv) MCB 32 Amp SPN 10 KA -01 No,415 Volts,50 Hz (c) RYB indication LED type ,240 V, 50 Hz, AC supply -01 No, Set of 03 (d) Ammeter digital, 96x96mm, with suitable ratio CTs with built in selector switch -1 No
(e) Volt meter digital type of range 0-500 Volts, 96x96mm with built in selector switch -1 No (f) Changeover switch 250 Amp ,4 Pole ,50 Hz front operated 415 Volts on load type Note : (i) All wiring used in panel board should be with FRLS grade copper conductor of suitable size.
(ii) All MCCBs must be thermal magnetic release with over load (O/L), short circuit protection (S/C)ICS= 100% ICU
1
-
-
S&F pre-stressed cement concrete pole, 11 metre long, class 09, complying withrequirements of IS-1678-1998 erecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in white and blue colour up to 1.5 metre height from top of PCC pedestal/coping of poles including numbering of poles with synthetic enamel paint black in 80mm high letters over 150mm x 230mm yellow base made from synthetic enamel paint complete all as specified and directed by Engineer-in-Charge.
Note : PCC for foundation and earth work shall be measured and paid for separately.
2
-
-
S&F Mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment complete (Fe-410W Gde-E 250 quality-A) complete all as specified and directed by Engineer-in-Charge.
350
-
-
Supply testing, installation and commissioning of 160 KVA isolation transformer, 3 Phase, outdoor type, copper wound, oil cooled, class of insulation H, metallic body duly powder coated as per IS 9815 and 2026, designed for input voltage range 415 ± 5% and output voltage range 415 ± 5%, Ratio 1:1, vector group: Dyn 11, delta-star with first filling of transformer oil of requiste dielectric strength upto level, efficiency more than 95%, separate neutral bushing shall be brought out for earthing.Potential difference between neutral to earth less than 1 Volts with all standard fittings like digital temperature meter,adequate number of cooling radiators, lifting hooks one set, earthing terminals 2 nos complete with over load/ short circuit protection. ,complete all as specified and directed by Engineer-in-Charge.
Note:- PCC platform /plinth for the transfomer shall be as per OEM recommendation/ design and as per SBC. The same shall also be approved from Accepting officer before placement of order. Cost of the plinth shall be deemed to be included in qouted rate. (i) The OEM of the transformers should have in house LAB Certificate for Accreditation from National Accreditation Board for Testing and Calibration laboratories. (ii) All technical drawing of the transformer/technical parameter as required by Engr-in-Charge shall be provided for approval by the Accepting officer beffore placing of order.
(iii) all the documents as required for item No 1.00 (1.16) against NOTE shall also be applied for this item also.
1
-
-
Material and Labour for cutting existing bituminous road/PCC of size 45cm x 60cm for taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface Premix road repair in appropriate proportions and removing debris to a distance not less than 50m complete all as specified and directed by Engineer-in-Charge.
20
-
-
Material and labour for cable route indicator showing "MES LT UG 1.1KV" or "MES HT UG 33KV" and route of cable with arrow (should be embossed or engraved) made of RCC in suitable shape and fixed in PCC block 1:3:6 type C-2 using 40mm graded aggregate including bricks works and excavation, size of route indicator 60cm x 30cmx 10cm, 30cm below ground level and 30cm above ground level to show clear indication of cable including painting the complete slab with red paint and making the engraved/embossed letters/arrow with white paint complete all as specified and directed by Engineer-in-Charge.
10
-
-
Material and labouir for broken stone boulder hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified and directed by Engineer-in-Charge.
10
-
-
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering, and removing surplus soil to a distance n exc 50 m and making good surface complete all as specified and directed by Engineer-in-Charge.
30
-
-
Material and labour for Plain Cement Concrete 1:3:6 type C2 (using 40mm graded crushed stone aggregate) as in post holes including formwork complete all as specified and directed by Engineer-in-Charge.
4.25
-
-
Supply and fixing of mild steel posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe 290 Gde E-165. complete all as specified and directed by Engineer-in-Charge.
540
-
-
Supply and fixing of mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, but lenth of bolt exc 5cm and n exc 10 cm long and diameter of neck 10mm and over complete all as specified and directed by Engineer-in-Charge.
3
-
-
M&L PVC coated GI chain link fencing 3.5mm dia with 50mm x 50mm mesh including fixing of MS line wire / rod, flat iron & machine made hexagonal or square head bolts to fencing posts including dismantling of fencing and fencing post complete all as specified and as directed by Engineer-in-Charge.
Note :Mild Steel rod,flat iron and bolts will be measured and paid seperately.
120
-
-
Supply only mild steel rounded bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips, Fe-410-W( GdeE-250) quality A or Fe290 (Grade-E-165) including mild steel screw bolts 10mm dia machine made with hexagonal or square head at one end and screwed the other or screwed both ends for fixing of chain link fencing complete all as specified and as directed by Engineer-in-Charge.
170
-
-
Material and labour for preparation of new steel surfaces, of any description not otherwise described, n.exc 10 cm width or girth and applying two coats of approved colour synthetic enamel paint, over a coat of red oxide zinc crome primer complete all as specified and directed by Engineer-in-Charge.
15
-
-
Material and labour for preparation of new steel surfaces, of any description not otherwise described, over 10 cm width or girth and applying two coats of approved colour synthetic enamel paint, over a coat of red oxide zinc crome primer complete all as specified and directed by Engineer-in-Charge.
30
-
-
Material and labour for preparation and applying three coats of white wash on new plastered surface of wall complete all as specified and directed by Engineer-in-Charge.
65
-
-
Material and labour for hardcore broken stone boulder hand packing (any thickness) at back of walls over arches etc. and raising (or lowering) to the required level complete all as specified and directed by Engineer-in-Charge.
2
-
-
M&L for anti climbing devices; comprising 2.24mm dia galvanised steel 2-strand barbed wire with 2.00mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered (clamps measured separately) inclusive two coat of Aluminium paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-Charge.
0.05
-
-
M& L for Aluminum conductor, steel reinforced ( ACSR ) drawn / fixed on poles including aluminum binding wire for jumpering complete all as specified and directed by Engineer-in-Charge.
0.15
-
-
Material and labour for machine pressed, vibratory compacted, precast concrete coloured (using red colour pgment), rubber moulded, interlocking designer paver blocks, confirming to IS-15658-2006, 60mm thickness, of M-35 grade, as in path, hard standing, etc. laid over and including 25 mm thick bedding layer of sand well rammed complete all as specified and directed by Engineer-in-Charge.
20
-
-
Material and labour for framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing confirming to Fe-290 (Gde E- 165) complete all as specified and directed by Engineer-in-Charge.
90
-
-
Materials and labour for earthing complete with galvanised iron earth plate electrode of size 600 mm x 600 mm x 6 mm thick, burried directly and vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with and including galvanised earth strip of size 32 x 6mm (Upto length of 7.5m strip including) by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia complete all as specified and directed by Engineer-in-Charge.
16
-
-
Excavation in trenches not exc. 1.5m wide and not exe 1.5m in depth for laying GI pipes,cable etc. and getting out in soft/loose soil complete all as specified and directed by Engineer-in-Charge.
50
-
-
Returning filling in soil from excavation including spreading, leveling, watering and well ramming in layers n.exe. 25 cm thick complete all as specified and directed by Engineer-in-Charge.
45
-
-
Removing excavated (surplus soil) to a distance not exc. 50 m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified and directed by Engineer-in-Charge.
5
-
-
Supply & lay in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 90 mm and inner dia 76 mm polethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed by Engineer-in-Charge.
100
-
-
Supply & lay in replacement Telerex DWC (Double Wall Corrugated) HDPE pipe ISI marked of outer dia of 110 mm and inner dia 95 mm polethylene including couplers, bends, cap etc., with smooth internal and profiled external surface for non pressure under ground cable complete all as specified and directed by Engineer-in-Charge.
100
-
-
Supply and fixing cable jointing kit for 1100 V grade cable for outdoor termination cold shrinkable type joint complete with jointing material and accessories suitable for 3.5 core XPLE armoured aluminium cable of size 3.5 core 240 sqmm complete all as specified and directed by Engineer-in-Charge.
2
-
-
Supply and fixing and connecting up Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe as directed/specified for loop earthing etc as required of galvanised iron strip of size 32 x6 mm complete all as specified and directed by Engineer-in-Charge.
Note:- This item shall be measured for the quantity used at site after the length of strip 7.5m.
50
-
-
Supply , laying, jointing and testing in replacement of underground LT cable XLPE insulated ,screened PVC bedded , galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 Core laid in trenches/ducts/along poles/ through pipe under road etc all as specified and directed by Engr-in-Charge
115
-
-
Supply , laying, jointing and testing in replacement of underground LT cable XLPE insulated ,screened PVC bedded , galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sqmm 3.5 Core laid in trenches/ducts/along poles/ through pipe under road etc all as specified and directed by Engr-in-Charge
110
-
-