West Bengal State Electricity Distribution Company Limited Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
West Bengal State Electricity Distribution Company Limited - WBSEDCL Tender
Eprocure
Opening Date27 Jun 2024
Closing Date19 Jul 2024
Tender Amount₹ 3,27,589
Costs
EMD
₹ 6,600Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Illumination Of Inside And Outside Of The Newly Constructed Second Store Meter Godown Under Kolkata Zonal
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_WBSED_697747_1Bid Award Id
ViewTender No
ZMK/Electrical/e-TENDER /2024-25/ 20Tender Authority
West Bengal State Electricity Distribution Company Limited ViewPurchaser Address
-Website
http://https://wbtenders.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.
3
-
-
Supply and fixing wiring in 1.1 KV grade single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 25mm PVC casing-capping (Precision make) incl. necy. PVC clips, fittings etc.(C) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm)
257
-
-
Supply and fixing wiring in 1.1 KV grade single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 25mm PVC casing-capping (Precision make) incl. necy. PVC clips, fittings etc.(C) 2 x 56/0.3 (4 sqmm) + 1 x 22/0.3 (1.5 sqmm)
32
-
-
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.Havells 8 way Enclosure (DHDPTHODRW08)
2
-
-
Supply & Fixing 240V, Modular Socket (1 Module) type fan regulator (Step type) (Brand approved by EIC) on existing Modular GI switch board with top cover plate incl. making necy. connections etc.
4
-
-
Supplying & Fixing bulk head light fitting (Havells make) with die cast aluminium housing & frosted glass on wall/ceiling incl. S&F 8watt LED/20 watts GLS lamp complete set.
52
-
-
Supply & Fixing CEILING FAN on CEILING with necy. (CROMPTON)48''
4
-
-
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection for Havells 6-32 A 4p
2
-
-
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection for Havells 6-32 A SP
9
-
-
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection for Havells 6-32 A DP
2
-
-
SUPPLY of Pedestal fan
2
-
-
Supply & Fixing 25 WATT LED LAMP on CEILING /WALL . (CROMPTON)
8
-
-
Supply & Fixing 240 V, 16 A, 3 pin Modular type TOP (Brand approved by EIC) S&F and making necy. connections with PVC Cu wire and earth continuity wire etc.
2
-
-
(supply / Laying / OLD cable dismeting), dressing, clamping, testing & commissioning of following sizes 1.1 KV Grade Aluminium/ Copper conductor, XLPE insulated, PVC inner sheathed, PVC type ST-2 outer sheathed and Galvanized wire/flat strip armoured LT Power Cables conform to IS 7098 Part-I (latest edition). The cables shall be laid along cable trench/ trays including anchoring, fixing/ clamping in trench/ trays with supplying and fixing of cable clamps & cable identification tags. The scope excludes cost of fabrication and erection of cable tray but include dressing clamping etc. as required and to the satisfaction of engineer.For cable size : 3.5C x 25 Sq. mm. Al. Arm.
17
-
-
End termination & connection including dressing and clamping of following sizes 1.1 KV Grade XLPE insulated, aluminium conductor armoured LT Power cables of following sizes using heavy duty single compression brass cable gland, crimpping type socket & other consumables as required. The scope includes of all consumable and accessories for cable size : 3.5C x 25 Sq. mm. Al. Arm.
2
-
-
Supply & fixing on wall industrial Plug & socket DB in metal enclosure with one 40 Amps industrial socket (P+N+E) but with 40 Amps DP MCB (Legrand) duly inter connected.
2
-
-
Earthing as per IE Rules including making of 1 No. earth station with 50 mm dia 2.5 mts. length GI pipe buried at an average depth of 3 mts. below ground level with including providing masonary inspection pit and restoration of urface duly rammed.complete as per IS 3043 : 1987.
2
-
-
Main switch : Supply & fixing steel main switchs on angel iron frame on wall, 100 Amp (Standard/Havells) installation & testing and commissioning of wall mounted flushed type, vertical double door mainswitch (100 Amp) distribution board complete with bus bar, connection, locking arrangement and fitted with etc.
1
-
-
Providing and fixing of following GI strip on surface or in recess for earth connection etc. along cable tray as required and absolute as required to comply with IS 3043 :1987-2.5 Sq mm 2 Core Copper aur. Cable.
70
-
-
SUPPLY DELIVERY AND INSTALLATION OF 1.5 TON AIR CONDITION WITHOUT INVERTER MAKE (VOLTAS , BLUE STAR ,L.G , HITACHI )
2
-
-
AC Outlet water pipe ( in Sqft )
20
-
-