West Bengal State Cooperative Marketing Federation Limited Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
West Bengal State Cooperative Marketing Federation Limited - BENFED Tender
Electrical Goods and Equipments
Eprocure
Opening Date18 Nov 2021
Closing Date10 Dec 2021
Tender Amount₹ 64,98,911 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 1,29,978Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_SCMFL_351639_1Bid Award Id
ViewTender No
SCMF/MD/ENG/NIT-16/2021-22Tender Authority
West Bengal State Cooperative Marketing Federation Limited ViewPurchaser Address
-Website
http://https://www.benfed.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supply & Installation of 1200A TPN floor mounted, cubicle pattern Main switch Board consisting of1000A TPN Air Circuit Breaker with disconnector fuses, meters etc. as specified in technical specification.
1
-
-
Supply & Installation of 300KVAR 12 stage APFC panel as per direction of EIC as specified in technical specification. Complete with necessary connection arrangements like adequate size cable earthing etc.
1
-
-
Supply & Installation of 500A TPN floor mounted, cubicle pattern, Auxiliary Switch Board with change over switche, SDF 's etc as specified in technical specification.
1
-
-
Supply & Installation of 1000A TPN Air circuit breaker cubicle panel as specified in technical specification. Complete with necessary connection arrangements as directed by EIC.
1
-
-
Supply & Installation of lighting switch board , consisting of 100A 4 pole isolator on incoming side , 16 nos 40A 4P isolator on out going side complete with indicating lamp busbar as specified in technical specification.Complete with necessary connection arrangements.
1
-
-
11KV grade 3 core , XLPE cables & cable termination jointing as specified.
-
-
-
Supply & laying of 11 KV, 3 core 185 mm2 XLPE cable as appropriate or as directed by EIC
36
-
-
11 KV, 3 core 185 mm2 XLPE cable termination jointing as per IER or as directed by EIC.
4
-
-
Supply & laying of 1.1 KV grade , PVC & Aluminium cables along with 2nos Earth wires as specified in technical specification.Following cables may be laid through under ground trench or surface as per site requirements.
-
-
-
Supply & Laying of 3.5 core 300mm2 from substation ACB room to Main Switch Board. Complete with necessary connection arrangements incl. cable trench/protection pipe where required or as directed by EIC.
310
-
-
Supply & Laying of 3.5 core 240mm2 from 400KVA Transformer to ACB On Main Switch Board at substation room. Complete with necessary connection arrangements incl. cable trench/protection pipe where required or as directed by EIC
120
-
-
Supply & laying of 3.5 core 150 mm2 cable as per technical specification.
20
-
-
Supply & laying of 4 core 16 mm2 cable as per technical specification.
110
-
-
Supply & laying of 3.5 core 70 mm2 cable as per technical specification.
130
-
-
Supply & laying of 3.5 core 185 mm2 cable as per technical specification.
30
-
-
Supply & laying of 4 core 6 mm2 cable as per technical specification.
340
-
-
Supply & laying of 4 core 10 mm2 cable through under ground trench or protection pipe by the execavation of soil or as directed by EIC.
40
-
-
Supply & laying of 4 core 10 mm2 cable as per technical specification or as directed by EIC.
80
-
-
Supply & laying of 4 core 4 mm2 cable
60
-
-
Supply & fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture -proof entry of XLPE/PVC armoured cables. Make: Dowlles/commet
-
-
-
3.5 core 300mm2 .
4
-
-
3.5 core 150 mm2
4
-
-
3.5 core 240 mm2
9
-
-
3.5 core 70 mm2
4
-
-
3.5 core 185 mm2
4
-
-
4 core 6 mm2
24
-
-
4 core 16 mm2
2
-
-
4 core 10 mm2
6
-
-
4 core 4 mm2 cable
4
-
-
Finishing of cable ends by crimping method including supply & fixing solder less sockets tape anticorrosive paste and jointing materials.
-
-
-
3.5 core 300mm2 .
4
-
-
3.5 core 150 mm2
4
-
-
3.5 core 240 mm2
9
-
-
3.5 core 70 mm2
4
-
-
3.5 core 185 mm2
4
-
-
4 core 6 mm2
24
-
-
4 core 16 mm2
2
-
-
4 core 10 mm2
6
-
-
4 core 4 mm2 cable
4
-
-
Earthing
-
-
-
Supply & Installation of Earth station with 50mm G.I. pipe as specified.
30
-
-
Earthing of Transformer neutral with 40mm x 6mm copper flat bar as specified.
30
-
-
Earth busbar & earthing of substation equipments with 50mm x 6mm GI flat bars to earth stations as specified.
220
-
-
Earth busbar & Earthing of equipments with 25x6mm GI strip as specified.
90
-
-
Earthing of equipments with 8 SWG GI wire.
60
-
-
Lighting Arrestor for cold storage building as specified.
-
-
-
Supply & fixing of Air Terminals as specified.
10
-
-
Interconnecting Air Terminals & Earth stations with 40x6mm G.I. flatbars as specified.
330
-
-
Supply & Installation of following at appropriate places, as specified or as directed by EIC.
-
-
-
Enamelled DANGER Boards 11000 Volt/440volt
4
-
-
Electric shock Treatment chart, framed in glass
1
-
-
Rubber mat, 10mm thick, 1mx3m
3
-
-
Electrician Rubber Gloves
2
-
-
First Aid Box
2
-
-
Dry type fire extinguisher as per IS specification minimum 5Kg cylinder
20
-
-
sand bucket
8
-
-
Supply & fixing of 1400mm sweep ceiling fans with double ball bearings as specified in technical specification.
-
-
-
For main chamber 450mm downrod , with out regulator
96
-
-
For drying shed & Plant room : 750mm down rod , with out regulator
44
-
-
For office block & labour shed: 450mm down rod with regulators.
7
-
-
Supply & fixing of 450mm sweep , 1440/1420 RPM exhaust fan as specified in technical specification.
4
-
-
Supply & Fixing of following Lighting fittings complete with connection & mending good damages to original finish.
-
-
-
Supply & fixing of LED T8 light fitting, complete with suitable down rod if required as specified.
56
-
-
Supply & Installation of 12/18 watt LED light fittings with B22 holder as specified
12
-
-
Supply & Fixing of 45watt LED street light as specified.
12
-
-
Industrial utility shaded light fitting with lamp as specified.
256
-
-
Sodium vapour light fitting with 250w lamp as specified.
1
-
-
Bulkhead light fitting with specified watt lamp etc. as specified.
6
-
-
Supply & installation of out door fittings with 36/37 LED Bulb & holder complete with reflector angle bracket etc.or as directed by EIC
15
-
-
LED flood light as specified.
2
-
-
Supply & fixing 9/12watt LED lamp on angular batten holder on wall.
6
-
-
Alarm Bell
-
-
-
Alarm Bell wiring with 1.5 sq.mm single core flexible copper wire & 1 sq.mm flexible copper wire as earth wire , complete with push switches with indicating lamps mounted on acrylic boxes fixed on the nearest column inside the chamber door. 5 sets of push switches & indicating light in a loop of 60m up to alerm bell in plant room as specified.
1
-
-
Alarm call bell as specified.
1
-
-
Point wiring with 2 nos 2.5 sq.mm single core , flexible copper wires in rigid PVC conduits , along with 1 no. 1.5 sq.mm earth wire in loop for 8 nos ceiling fans /loop of 50 mtr avg. run as specified.
12
-
-
Point wiring with 2 nos 1.5 sq.mm single core flexible copper wire in rigid PVC coduits along with 1 x 1.5 sq.mm as earth wire for lights in cold chambers as specified.(7 points per loop of 50 mt avg. run)
36
-
-
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sq. mm ) single core stranded FR PVC insulated and unsheathed copper wire (app. Make) in suitable size of PVC casing capping with 1x22/0.3(1.5 sq.mm) single core stranded FR PVC insulated copper wire for ECC including necessary PVC clips fittings etc. to light/ fan/outdoor light point with piano key (6A/16A as directed by EIC) type switch fixed on the sheet metal fabricated switch board with perspex/bakelite top cover on wall/inside the panel box including necessary connection and making earthing attachment and making earthing attachment & making good damages to building works.[PVC casing caping & switch board both on surface.]
-
-
-
Stair Block light points, 2 points /loop as specified avg.run 12mtr
5
-
-
Drying shed light & fan points as specified in avg. run -9 mtr.
86
-
-
Plant Room, Substation room, office room & labour shed light & fan points including exhaust point as specified. Avg. run 5mtr
60
-
-
point wiring with 2 nos 2.5 sq.mm single core flexible copper wires in rigid PVC conduits , along with 1 x1.5 sq.mm earth wire for sodium vapour/LED flood light as specified. Avg. run 18m
4
-
-
Point wiring with 3 nos 1.5 sq.mm , single core flexible copper wires in rigid PVC conduits along with 1.00 sq.mm earth wire for solenoid & float , with a 1A SP MCB DB at stair case controlling switch as specified. Avg. Run 36mt.
6
-
-
Point wiring with 2 nos 1.5 sq.mm ,single core flexible copper wires in rigid PVC conduits, along with 1.5 sq.mm as earth wire , for out door lights with a 6A switch on acrylic covered metal box as controlling switch as specified. Avg run 12 mt
30
-
-
Supply & fixing including wiring of 250V 5 pin 16A flush type plug socket with 16A piano key type (approved make) switch on sheet metal box with bakelite top cover and earthing arrangements incl. supply and fixing of 16SWG metal box and bakelite cover as directed by EIC..
26
-
-
5A/6A plug switch combination units on acrylic boxes with point wiring by 2x1.5sqmm +1x1.5sq.mm single core flexible copper wire in rigid PVC conduits from MCB DB or nearest Joint Box. Avg run 30 mtr.
15
-
-
5A/6A On board socet including internal connection as directed by EIC.
15
-
-
Supply & fixing 50mm dia G. I. protection pipe (medium ISI make) for protection the cable under the road & and also used as a riser of the cable incoming including mending good damages to the original finish.
50
-
-
Supply drawing 1.1KV grade 2x2.5sq.mm + 1x1.5sq.mm FR PVC strandard copper wire for main line wiring in rigid PVC pipe or casing from MCB DB to the nearest JB/switch board for main line wiring.
2200
-
-
Supply & Installation of Double door MCB DB consisting of an incoming 4-pole isolator , SP/SPN/TPN MCB's on out going sides in S.S. enclosures as specified as directed by EIC.
-
-
-
40A 4 pole isolator on incoming side & 12nos 10/16A SP MCBs on outgoing sides for chamber lights as directed by EIC
6
-
-
63A 4 pole isolator on incoming side & 19 nos 16A SP MCB & 6 nos 1 Amp SP MCB on out going side for main chamber ceiling fans & float & solenoid valves as directed by EIC.
1
-
-
40A 4 pole isolator on incoming side & 10nos 10/16A SP MCBs on outgoing sides for drying shed , plant room, labour shed substation etc as directed by EIC.
6
-
-
Supply & fixing of CRC sheet metal (16SWG)JB box 150mm x10mm x 65mm complete with three no. suitable size copper bar with holes fixed on bakelite /hard rubber insulator over MS welded chairs including bakelite /perspex cover.
34
-
-
Supply & fixing of 4"x4" PVC box with cover used as a pull box for long run of PVC copper wire.
18
-
-
Repairing & renovation of existing main panel & auxiliary panel of existing 4000MT cold storage by replacing of damage main switches(feeder), busbar ,connector , cables(if required), indicator lamps & change over switch etc. with a adequate size suitable range accessories which can be fitted in the existing panel complete with required connection arrangements, painting etc. thus, the panels can be performed with their desired utility to run the cold storage from a common plant room or as directed by EIC.
1
-
-
Dismantling the existing transformer, gear & other non-useful accessories including their cables & reconnect to newly installed or repaired accessories as directed by EIC. Dismantling material kept in convienient place for subsequent disposal.
1
-
-
Repairing the existing change over switches (4000 MT)including replacement of damage switch , connector as per requirement of the common run of (4000+6000)MT cold storage. So that required panels can be run with both the existing DG sets & complete with necessary connection arrangements as directed by the EIC.
1
-
-
Supply and installation of 250A change over switch for existing pump panel by replacing of existing main switch . Complete with necessary connection arrangements as directed by EIC.
1
-
-
Drawings approval of drawings by Chief Electrical inspector , Govt. of West Bengal ,Testing including H.V. pressure test , Registration of D.G. sets & Domestic consumption meter etc. from appropriate authority.
1
-
-
Hiring of DG set for testing overall electrical installation and also for use during the erection work , if required.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements