Public Works Department Tender
... More
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Public Works Department - PWD Tender
Civil And Construction
Building Construction
Electrical and Electronics
Electrical Works
Eprocure
Opening Date24 Mar 2025
Closing Soon7 Apr 2025
Tender AmountRefer Documents
Costs
EMD
₹ 24,544Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_WBPWD_828573_1Tender No
WBPWD/SE/SWEC/NIQ76/2024-25Tender Authority
Public Works Department ViewPurchaser Address
-Website
http://http://wbpwd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
RPM : 1500
-
-
-
... More
Gross engine Power (HP) : 74.1 HP or Higher
-
-
-
... More
Duty : PRIME
-
-
-
... More
Aspiration/Cooling : TCAC
-
-
-
... More
Cylinder /Arrangement : 3 / inline
-
-
-
... More
Type of Governor : Electronic / Mechanical
-
-
-
... More
Fuel Tank Capacity : Minimum capacity 100 Ltrs. Or higher
-
-
-
... More
Fuel Consumption at 75% rated Load with Radiator or Fan : 10.3 Ltr./ Hr. or Less
-
-
-
... More
Fuel Consumption at 100% rated Load with Radiator or Fan : 13.7 Ltr./ Hr. or Less
-
-
-
... More
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
-
-
-
... More
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
-
-
-
... More
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
-
-
-
... More
Exhaust Silencer : Residential Type
-
-
-
... More
Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
-
-
-
... More
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
-
-
-
... More
Alternator :
-
-
-
... More
Make : Stamford/ Leroy Somer/Mecc alte / CG
-
-
-
... More
Rating : 415 V., 3Ph. 50 Hz., 58.5 KVA, 1500 rpm
-
-
-
... More
Type : Brushless, self excited and self regulated
-
-
-
... More
Insulation : Class H
-
-
-
... More
Protection : Screen-protected drip proof with Min.IP-23 degree of protection
-
-
-
... More
RPM : 1500
-
-
-
... More
Voltage Regulation (max) : ±1%
-
-
-
... More
Winding connection : Star with Neutral
-
-
-
... More
Total Distortion factor : Less than 3%
-
-
-
... More
Total Harmonic distortion in output waveform : 5%
-
-
-
... More
Acoustic Enclosure : The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-IV+ norms.
-
-
-
... More
Base Frame : Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
-
-
-
... More
SITC OF AMF Panel
-
-
-
... More
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 58.5 KVA DG set having following specification/features.
-
-
-
... More
i) 2 No. 100 A AC1 duty, 4pole power contactor and U/V release etc. [make: L&T / ABB / Legrand / Schneider] ii) 2 Nos. 100 A, 3pole, 50 KA MCCB with microprosser based LSIG protection. [make: L&T / ABB / Legrand / Schneider] iii) In Built By-Pass switch for rated capacity iv) On -delay timer for load change over
v) On-delay timer for engine shut off
vi) Engine On-Off switch (Push button type)
vii) Battery charger complete with voltage regulator, booster selector switch, on-off switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine
-
-
-
... More
viii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.
ix) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'. ix) Mode selector for setting the panel on Auto/ Man/ Test Mode
x) Microprocessor based relay with composite meter for digital display of following.
Generator voltage/AC Mains voltage.
Generator Current in all phases
Frequency
Power Factor
Energy
Indication for alternator supply
Running time indications number of hours of operation and service intervals, service due indications
-
-
-
... More
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
-
-
-
... More
Terms & Conditions
-
-
-
... More
(i) Rate should be quoted inclusive of all applicable taxes and Duties etc.
-
-
-
... More
(ii) All materials, equipments & accessories must conform to the relevant IS specifications. The DG Set must be supplied from the authorized OEM of the respective Engine Manufacturer.
-
-
-
... More
(iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to be submited in triplicate during delivery of the equipment.
-
-
-
... More
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from the competent Authority (As per CPCB-IV+).
-
-
-
... More
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM.
-
-
-
... More
(vi) The entire set must be warranted at least 18 months from the date of Delivery/12 months/ 5000 Running Hrs from the date of Commissioning whichever is earlier. Vii) During warrenty period if any discripency occurs regarding performance of the DG set that has to be attended within 24 Hrs. sharp
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%