Public Works Department Tender

Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.

Public Works Department - PWD Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date22 Dec 2023
Closing DateCancelled
Tender AmountRefer Documents 
Notes
Download

Costs

Summary

Wbpwd/se/swec/niq50/2023-24/ Retender

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Engine Type : 4 Stroke Diesel Engine

-

-

-

... More
RPM : 1500

-

-

-

... More
MoEF certified power : 240 BHP or Higher

-

-

-

... More
Duty : PRIME

-

-

-

... More
Cooling : Water cooled with radiator

-

-

-

... More
Cylinder : 6 inline

-

-

-

... More
Aspiration : Turbo Charged

-

-

-

... More
Type of Governor : Electronic

-

-

-

... More
Fuel Tank Capacity : Minimum capacity 360 Ltrs.

-

-

-

... More
Fuel Consumption at 75% rated Load with Radiator or Fan : 33 Ltr./ Hr. or Less

-

-

-

... More
Fuel Consumption at 100% rated Load with Radiator or Fan : 44.8 Ltr./ Hr. or Less

-

-

-

... More
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better

-

-

-

... More
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.

-

-

-

... More
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator

-

-

-

... More
Exhaust Silencer : Residential Type

-

-

-

... More
Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.

-

-

-

... More
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning

-

-

-

... More
Alternator

-

-

-

... More
Make : Stamford/ Leroy Somer/ Crompton Greaves

-

-

-

... More
Rating : 415 V., 3Ph. 50 Hz., 200 KVA, 1500 rpm

-

-

-

... More
Type : Brushless, self excited and self regulated

-

-

-

... More
Insulation : Class H

-

-

-

... More
Protection : Screen-protected drip proof with Min.IP-23 degree of protection

-

-

-

... More
RPM : 1500

-

-

-

... More
Voltage Regulation (max) : ±1%

-

-

-

... More
Winding connection : Star with Neutral

-

-

-

... More
Total Distortion factor : Less than 3%

-

-

-

... More
Total Harmonic distortion in output waveform : 5%

-

-

-

... More
AMF Panel

-

-

-

... More
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 200 KVA DG set having following specification/features.

-

-

-

... More
i)2 No. 315/320 A AC1 duty, 4pole power contactor and U/V release etc. [make: ABB, Legrand, Schneider]

-

-

-

... More
ii) 2 Nos. 315/320 A, 3pole, 50 KA MCCB with microprosser based LSIG protection. [make: Legrand]

-

-

-

... More
iii) In Built By-Pass switch for rated capacity

-

-

-

... More
iv) On -delay timer for load change over

-

-

-

... More
v) On-delay timer for engine shut off

-

-

-

... More
vi) Engine On-Off switch (Push button type)

-

-

-

... More
vii) Battery charger complete with voltage regulator, booster selector switch, on-off switch, voltmeter and ammeter for charging the battery from mains. This will be in addition to the battery charging alternator fitted on the engine

-

-

-

... More
viii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.

-

-

-

... More
ix) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'.

-

-

-

... More
ix) Mode selector for setting the panel on Auto/ Man/ Test Mode

-

-

-

... More
x) Microprocessor based relay with composite meter for digital display of following.

-

-

-

... More
Generator voltage/AC Mains voltage.

-

-

-

... More
Generator Current in all phases

-

-

-

... More
Frequency

-

-

-

... More
Power Factor

-

-

-

... More
Energy

-

-

-

... More
Indication for alternator supply

-

-

-

... More
Running time indications number of hours of operation and service intervals, service due indications

-

-

-

... More
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.

-

-

-

... More
Acoustic Enclosure

-

-

-

... More
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms.

-

-

-

... More
Base Frame

-

-

-

... More
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.

-

-

-

... More
Supply & delivery and pouring including transportation of HSD oil

150

-

-

... More
Supply & laying 2.5 sq. mm. 10 core multi core multistrand PVC insulated flexible Cu cable in uPVC / GI pipe from DG to separate AMF panel. [Gloster/ Polycab/KEI / Havells/RR Kabel] [Bidder should visit the site]

10

-

-

... More
Supply & laying of 1.1KV grade 95 sq. mm. single core multistrand PVC insulated flexible Cu cable from earth electrode to neutral earth busbar and from earth busbar to neutral point as required incl. finishing the ends as required (for neutral earthing) [Gloster/ Polycab/KEI/ Havells/RR Kabel] [Bidder should visit the site]

15

-

-

... More
Extending the exhaust system with Supply & installation of MS 200 mm dia 5 mm thick MS pipe with covering of glass wool insulation and wrapping of 24 swg Al sheet of suitable size dia with necessary holding & hanging structure arrangement from ceiling/ wall with 5 mm thick ms conical shape canopy arrangement for rain water protection on top. internal pipes should be welded with each other & necessary providing of MS bend of same dia with wrapped and fabricated as per internal pipe lying with necessary asbestor rope of 18 mm dia thoroughly wrapped on MS pipe over that glass wool covering as per direction of EIC [Bidder should visit the site]

20

-

-

... More
Supply & Installation of suitable industrial shed (4mm thickness) having dimension of 5.5mtr(L) x 4.5mtr(W) with 06 no 65mm dia ISI-M pipe structure (vertical) and 32mm x 32 mm MS iron frame (shed structure) with 760 x 600 x 600 mm RCC muffing for each pipe (above 3 ft from the highest point of DG Set) as per direction of EIC. [Bidder should visit the site]

1

-

-

... More
Covering the foundation for AMF panel area with suitable fibre shed (4mm thickness) with suitable hinged door for access incl locking arrangements. Supprts should be made by S&F 32 mm MS angle frame (as per direction of EIC) [Bidder should visit the site]

1

-

-

... More
Construction of foundation suitable for erection of the 200 kVA DG set approx 4.6 M (L) x 2.20 M(W) x 0.46M (H) above GL and .9 M under GL or as per manufacturer standard specification with Ordinary cement concrete mix. 1 : 5 : 3 : with graded stone chips of 20 mm down pakur variety laying concrete base ( 1 : 3 : 6 ) using 40 mm down stone metal & single brick flat solling of picked jhama brick incl. at shuttering work by 25 mm to 30 mm thick wooden plank also , reinforcement with 12 mm dia steel TMT bars atleast 300 KG total , this rate are incl. all materials , labour charges & carrying etc. (suitable for 200 KVA DG set). Including Bricks stair of (3 steps atleast). (step height 6inch, wedth 4.5 feet)- 2 Sides as per direction of E-in-Charge and manufacturer recommendation.[Bidder should visit the site]

1

-

-

... More
Terms & Conditions

-

-

-

... More
(i) Rate should be quoted inclusive of all applicable taxes and Duties etc.

-

-

-

... More
(ii) All materials, equipments & accessories must conform to the relevant IS specifications. The DG Set must be supplied from the authorized OEM of the respective Engine Manufacturer.

-

-

-

... More
(iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to be submited in triplicate during delivery of the equipment.

-

-

-

... More
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from the competent Authority (As per CPCB-II).

-

-

-

... More
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM.

-

-

-

... More
(vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier. Vii) During warrenty period if any discripency occurs regarding performance of the DG set that has to be attended within 24 Hrs. sharp

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.