Public Works Department Tender

Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.

Public Works Department - PWD Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date27 Jul 2023
Closing Date14 Aug 2023
Tender Amount₹ 19,09,180 
This is an estimated amount, exact amount may vary.
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Rated power 250KVA

-

-

-

... More
Cooling-Mineral Oil

-

-

-

... More
Rated frequency 50 Hz

-

-

-

... More
Rated primary voltage 11 KV

-

-

-

... More
Basic Impulse Level (BIL) 75kVp & 28KVrms.

-

-

-

... More
Off-circuit tapping @ 2.5%,+5% to -10%

-

-

-

... More
Secondary voltage at no load between phases 415V

-

-

-

... More
Vector group Dyn11

-

-

-

... More
Losses shall be as per ECBC guideline Maximum Losses at 50% Load 0.98 KW Maximum Losses at 100% Load 2.93KW Maximum with load Loss at 75Deg C

-

-

-

... More
% Impedance 4.5% (IS tol)

-

-

-

... More
Temp Rise (Oil/Wdg):40/45deg

-

-

-

... More
Enclosure of Ingress of protection: IP65

-

-

-

... More
Painting should be epoxy as per latest standard with paint shade 631 of IS 5

-

-

-

... More
Terminal arrangement HV cable box suitable for HT cable 3C x 180 sqmm XLPE insulated cable, LV/HV suitable cable boxes orientation 180deg

-

-

-

... More
Fittings –

-

-

-

... More
(i) OTI,WTI, Conservator, Lifting Lugs, PRV, earthing terminals, Buchholtz relay, breather, Bi directional rollers

1

-

-

... More
Installation of 11 KV / 415 volt, 250KVA oil type outdoor transformer incl. carriage to the location within a lead of 30mtr. by placing in position and fixing after levelling, fitting all components incl. S & F base channels etc.

1

-

-

... More
Supply & laying of 11 KV grade 3 core 185 sq.mm. XLPE (E) HT cable with Al. conductor from WBSEDCL H pole feeder to transformer to be laid partly through clamping with pole and partly masonery trench as per G.S. as per direction of EIC.

20

-

-

... More
(Make - Polycab/ KEI/Havells/RR)

-

-

-

... More
S & Laying of 1.1KV grade 4 core 300 sq.mm. PVC/A AL. cable to be laid through masonary / U.G trench as per G.S. (from Transformer to ACB of sub-station L.T. main pannel board and to proposed Building) -

80

-

-

... More
(Make - Polycab/ KEI/Havells/RR)

-

-

-

... More
S & F compression type gland complete with brass gland, rubber ring for dust & moisture proof entry of 3.5 core 300 sq.mm. PVC/A Al. cable incl. finishing the ends by crimping method as per G.S.

2

-

-

... More
Making termination of the 3 core 185 sq.mm. HT cable incl.supply of necy. jointing materials & compound (Heat shrink cable jointing kit of approved make) at switch gear & transformer terminations on H.T. sides incl. testing as per G.S.

2

-

-

... More
Earthing with 80 mm dia GI pipe (TATA-Medium)x 6.0 Mts. long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 6.65 Mts. [For Transformer neutral − (1x2) nos, transformer body − (1x2) nos.]

4

-

-

... More
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.

4

-

-

... More
Extra treatment of soil by using salt & charcoal for pipe electrode as to G.S.

4

-

-

... More
Connecting the equipment body & Neutral to earth busbar incl. S & F 40 mm x 6 mm galvanized (Hotdip) M.S. flat on Wall/floor woth G.I. saddle as required and making connection to equipments with incl. drilling holes, nuts, bolts & washers as per G.S.

30

-

-

... More
Making testing arrangement and submitting the test report for high voltage testing of specified voltage incl. checking & testing of all HT / LT equipments by authorized firm of Directorate of Electricity & commissioning the installation after obtaining the Approval of Directorate of Electricity.

1

-

-

... More
S & F 11 KV grade rubber hand gloves.

1

-

-

... More
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required A) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.