Public Works Department Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Public Works Department - PWD Tender
Electrical and Electronics
Eprocure
Opening Date10 Jan 2024
Closing Date22 Jan 2024
Tender Amount₹ 6,31,506
Costs
EMD
₹ 12,630Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_WBPWD_639268_1Bid Award Id
ViewTender No
WBPWD/EE/JED/NIT 25e/T of 2023-24.Tender Authority
Public Works Department ViewPurchaser Address
-Website
http://http://wbpwd.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Laying of 4 core 25 sq. mm. cable as below, after cutting floor/ pavement/wall and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish.
35
5670
162
Laying of one No. 4 core 95 sq. mm. cable in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed.
212
46428
219
S & F compression type brass cable gland complete with brass gland, brass ring & rubber ring for dust & moisture proof entry of XLPE/PVC armoured cable.
-
-
-
4 core 25 sq. mm.
4
828
207
4 core 95 sq. mm.
4
1192
298
Finishing the end of the XLPE/PVC armoured cableas by crimping method incl. S&F solderless socket (Dowels make), tapes, anticorrosive paste & joiting materials.
-
-
-
4 core 25 sq. mm.
4
588
147
4 core 95 sq. mm.
4
1580
395
S&F medium gauge 40mm dia GI Pipe (ISI-Medium) Protection with necessary fittings and jointing metarials as required as per GS.
5
1570
314
S&F medium gauge 50mm dia GI Pipe (ISI-Medium) Protection with necessary fittings and jointing metarials as required as per GS.
5
2105
421
Earthing Installation :
-
-
-
Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil)
4
1096
274
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mt. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S&F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level. (By ISI-Medium GI pipe)
2
3492
1746
S&F earth busbar of 40 mm x 6 mm galvanized (Hot Dip) MS flat on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
0.5
123
247
Connecting the equipments body to earth busbar including S&F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc.
30
5280
176
S&F 6-Way double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment incl. double door sheet steel (16SWG), powder coated cable end box for 6-Way TPN DB horizontal enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc. incl. provision for earthing attachment.(M- Legrand: 607716/Havells Metalica /ABB Elegance]
1
5338
5338
S&F of (2+12) Way double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment incl. bothside Wire way box suitable for 2+12-way SPN MCB DB. [M- Legrand: 607712 /Havells Metalica /ABB Elegance]
2
6586
3293
S&F of 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Legrand /Siemense /Havells /ABB)
-
-
-
63A FP MCB
1
2334
2334
32A DP MCB
2
1392
696
6-32A SP MCB
10
2420
242
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (M-Havells/RR Kabel/Polycab/ KEI) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. PVC clips, fittings etc. to light/fan/call bell point with piano key type switch (Anchor make) fixed on sheetsteel fabricated switch board with Perspex/bakelite top cover on wall incl. necy. connections and making earthingattachment and mending good damages to building works. [PVC casing-capping and Switch board both on surface]
-
-
-
On board 5A
9
765
85
Average run 10 mtr.
54
68364
1266
Distribution wiring in 1.1 KV single core stranded 'LS0H or ZHFR' PVC insulated & unsheathed copper wire (M-Havells/RR Kabel/Polycab/KEI) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.
-
-
-
2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) as ECC
80
10400
130
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC
125
19000
152
2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) as ECC
125
30750
246
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
-
-
-
36/0.3 (2.5 sqmm)
110
770
7
56/0.3 (4 sqmm)
12
84
7
84/0.3 (6 sqmm)
24
264
11
Supply & Fixing 250 V two 5 Pin 6A flush type plug socket with two 6A Piano key type (Anchor make) switch on 200x150x65mm sheet metal box [16 SWG] with bakelite top cover and earthing attachment incl. S&F sheet metal box with 3mm thick bakelite top cover.
4
2032
508
Supply & Fixing 240 V, 20A, plug socket with separate 20 APiano key type switch (Brand approved by EIC) on sheetmetal switch board embedded in wall incl. S & F150x100x65mm MS (16SWG) switch board and bakelite/ perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex coverand making necessary connections as required.
6
2196
366
S&F 240V, 12" Sweep Exhaust fan (EPC make) incl. Fixing exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust S&F of louver shutter with nuts & bolts (6 mm dia x 62 mm long).
4
22444
5611
Supply of 48" (1200mm) ceiling fan make: (M- Orient NEWBREEZE or SUMMERCOOL/ Crompton HS Plus/ Havells SS 390) complete with down rod, steel safety rope, canopy fork, blades with all other accessories etc. but without regulator.
16
44592
2787
S&F Electronic Socket type fan regulator [Make: Anchor] on existing switch board with backelight top cover after making housing for regulator knob by cutting backelight top cover including making necessary connections.
16
4832
302
Supply & fixing additional safety arrangement of ceiling fan by stranded GI strain wire of suitable gauge with one end fixed at RC clamp with special type of socket, nut-bolts, thimbles which throughly crimped with the strain wire and the wire passing through down rod (for upto 8 ft) and also other end connected with armature spindle by its existing jam nut hole with special arrangement (sample approved by EIC). The length of the strain wire up to 9ft also considering any type of work required i.e. enlarging the existing hole by file etc. to complete the job including installation as per direction of EIC (Static & Dynamic Load Test (in rotation of 1:20) certificate must be provided with final bill jointly with concerned Junior Engineer & authorised Electrical Supervisor of Agency).
16
800
50
Supply of Twin LED tube light fitting (Philips TMC 501 P 2xT-LED 22W P3242) incl. 2 nos. 1200mm polycarbonate housing LED tube with metal heat sink (M-Philips MAS LED Tube 18W865 T8 l- 2100lm or Equivalent of Havells/ Jaquar/ HPL) complete with all accessories.
18
26784
1488
Supply of Single LED tube light fitting (M- Philips TMC- 501 P 1xT-LED 22W P3241) incl. 1200mm polycarbonate housing LED tube with metal heat sink (M-Philips Philips MAS LED Tube 18W865 T8 l- 2100lm or Equivalent of Havells/Jaquar/ HPL) complete with all accessories.
6
5274
879
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
24
6096
254
S&F of 240V, 9W, B22 LED Lamp. (M-Philips/ Crompton/ Havells )
8
1048
131
Existing LT Panel Repairing
-
-
-
S&f 415V, 63 Amp TPN SFU open execution in existing SS enclosure/ cubical with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make : L&T/ABB/Havells)
2
6126
3063
S&f 415V, 125 Amp TPN SFU open execution in existing SS enclosure/ cubical with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make : L&T/ABB/Havells)
2
13874
6937
S&f 415V, 160 Amp TPN SFU open execution in existing SS enclosure/ cubical with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.(Make : L&T/ABB/Havells)
1
7653
7653
S&F three phase VAF meter CL 1 [L&T: WL411010OOOO] on fabricated MS box incl. interconnection.
1
1880
1880
S&f Current Transformer: 300/5A 15VA Class-1 C.T. 15VA Burden (M- KAPPA/AE)
3
1995
665
Painting the existing LT Panel Board ( L- 4 ft, H-4 ft, B- 1 ft) of One coat of red lead/Zinc hromate priming & 2 no. of coats synthetic enamel paint/ aluminium paint, as given below with ready mixed paint/primer (M-Asian Paints/Berger/Shalimar) incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint as per direction of EIC.
1
1689
1689
Evaluation Notes How It Works ?