Public Health Engineering Department Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Public Health Engineering Department - PHED Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date1 Jul 2024
Closing Date31 Jul 2024
Tender Amount₹ 12,57,741
Costs
EMD
₹ 25,902Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Wbphed/ee/nmd/niet- 04 Of 2024-2025,sl No 03
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PHED_702990_3Bid Award Id
ViewTender No
WBPHED/EE/NMD/NIeT- 04 OF 2024-2025Tender Authority
Public Health Engineering Department ViewPurchaser Address
-Website
http://https://wbphed.gov.in/en/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
12core x 1.5 sqmm ar. copper cable for control valve at the delivery line as per requirement.
10
-
-
1.1 kv GRADE 25 sq.mm 3.5 core XLPE insulated Al. Ar. armoured cable conforming to IS 7098 (Part-I) 1988, with upto date amendments
20
-
-
Supply, delivery and storage at site of Wall mounted 2 mm. thick epoxy painted sheet steel enclosed front open fully automatic cum manual control motor control centre for operation of the pump motor in STAR-DELTA mode ranging from 15 - 25 HP, actuator with DOL starter, Chlorinator with DOL starter and timer operated outdoor and indoor lighting as per approved drawing and NIT specification as laid in SCOPE OF WORK.
1
-
-
Supply and delivery of the following valves, pipes and gauges etc at site:
-
-
-
80mm dia M.S. seamless column pipe(black) 6.8mm to 7.1 mm thick with 150 mm long heavy type socket at one end.
-
-
-
3.00 m long excluding socket having 8T.P.I. thread.
9
-
-
1.50 m long excluding socket, one end having a thread of 11 T.P.I & the other end having a thread of 8 T.P.I.
2
-
-
Heavy type suitable dia MS suspension clamp along with nuts bolts and washer.
2
-
-
Cast Iron wafer type 80 mm dia Butterfly Valve generally as per BS-5155, having body of cast iron as per 1S:210 gr. FG-260, disc of SS Gr CF-8, Shaft of St.steel AISI-410,‘O’ ring for shaft seal of Nitrile rubber, valves are suitable for PN 1.0 rating.Valves are operated by suitable RotorkK.range (three phase 415 V) multi turn electrical actuator without starter.
1
-
-
80 mm dia CIDF sluice valve-1 no., Non Return Valve-1 no., CIDF 90° bend-2 no., Cl flanged tee-1no. blank flange-1 no., Cl/ MS flanged short piece 0.50 mtr.-2no, Cl/ MS flanged pipe 1 mtr. 2 no. etc as per IS specification and certification for Construction of delivery pipe line and wash out line.
1
-
-
Heavy type 250 mm dia split type tube well cover with 12 mm thick clamping arrangement including holes of column pipe, air pipe and cable entry with 2 sets heavy type suspension clump, nuts, bolts and washer as per departmental design.
1
-
-
Depth gauge 100 mm dia with steel air pipe of required length with all accessories for the above work including supply of good quality hand pump [This cost includes 15 mm. dia G.I. pipes and specials)
1
-
-
Pressure gauge [H.Gur u/ Febi g] 150 mm dia [0-7Kg/Sq.cm] brass cock and fitting complete[This cost includes 15 mm. dia G.I. pipes and specials]
1
-
-
5O mm. dia. non metalic pipes (IS:14930) and specials for protection of
submersible cable
3
-
-
Anti snapping safety device for pump set by supplying suitable size MS clamps two sets and nylon rope of required length including supplying of nuts, bolts and all other materials.
1
-
-
100 Amps porcelin based rewirable type male female kit Kat fuse unit.
3
-
-
100 Amp, 415 V TPN Rewireable type TPN Main switch.
1
-
-
Laying of 25 sq. mm. 3.5 core AL. ar. Cable in wall/ floor by supplying of all
necessary materials as per IE Rules and as per direction
20
-
-
Installation of the materials (to be supplied under above sl no 1 to 3) such as Pump motor set with column pipes, valves, panel fiting fixing pressure gauge, depth gauge, Non-return valve & drawing delivery out-let & washout line with the supplied specials / accessories including supply of cable gland,sockets etc including brick, sand, cement rod stc as required to complete the job as per direction and up to the entire satisfaction of the EIC.
1
-
-
Making brick pillar 0.25 mtr x 0.25 mtr. for supporting of valves and pipes with 12 mm thick plaster and net cement finish complete
1
-
-
Making suitable size pump foundation with supplying of necessary cement, sand and stone chips including plastering and net cement finish complete
1
-
-
Making double earthing arrangement in compliance with IE rules by G.I. pipe electrode of 5O mm. dia 3 mtr. Long 2 Nos for panel and pumping machinery 25 mm. x 6 mm. G.I. earth strips from earth pit to panel and all other accessories required to complete the work.
1
-
-
Making internal electrification of pump house consisting of two bracket point, one tube light point, two bulk head point, one fan point and 1NO. 74 watt LED fixture with arm bracket at outside and one three pin plug point including supply of all necessary materials to complete the work as per IE rules and as per direction [All the fittings and lamp should be LED type as per choice of EIC)
1
-
-
Supply & delivery of the PVC moulded Chair .
1
-
-
Supply & delivery of thePVC moulded Table .
1
-
-
Supply, delivery & installation of the following Fan as directed by EIC. a) Ceiling Fan 1200mm sweep OR
b) Wall mounting Fan 400 mm sweep including Fan clamp as and when required.
1
-
-
Supply, delivery & storage at site of automatically controlled diaphragm type Chlorinator dosing Pump with flow rate 100 LPH and maximum pressure of 10 kg/cm2 with all accessories for pump and motor , foundation bolt , suction and discharge flange and with storage tank of dosing solution of 100 liter capacity and the prime mover to be coupled with pump of 0.5 HP, 3 phase , 1450 RPM ,squirrel cage TEFC induction motor , Motor will be IE3. [ Test & Warranty Certificates are to be submitted at the time of delivery ]
1
-
-
installation & Commissionig of above supplied chlorinator with all accessories, PVC tank & drawing of power line as per IE Rules by supplying of necessary wire & continuous earthing. This include the cost of all necessary CC foundation (atleast 200 mm. height) with concrete mixture (Sand, Cement, Stone,chips) and neat cement finish by supplying of all required materials and testing the entire set as per direction of the EIC. [Power will be feed from PLC Panel of pumping machinery.]
1
-
-
Supply delivery at site of calcium hypochlorite Ca(OCL)2 Chlorine tablet with minimum 60-65% chlorine contentin air tight plastic jar (25 Kg Each) as per direction of E.I.C. Test certificate, containing toxic element to be submitted at the time of delivery with showing chlorine percentage of the above materials.
100
-
-
Supply and delivery at site following voltage corrector with electrical accessories.
-
-
-
Supply and delivery at site of 30KVA, 3 phase oil cooled type Servo Motor operated copper wound line voltage corrector conforming to IS-9815 (Pt.-1)-1994 suitable for un-balanced input voltage with following specification including first filling oil as per IS-335 where applicable.(Make: Approve make of P.H.E. Dte.) a) Input Voltage:- 3 phase, Main supply may or may not be balanced with respect to Phase to Phase 250V.-500V.Phase to Neutral-145V.-290V.
b) Out put voltage:- 3 phase balanced out put voltage. Phase to Phase 400V.or 415V.± 1% ,Phase to Neutral- 230V.-240V.±1% ( Provision should be made to adjust the Variation of out put voltage per phase by a variable pot oil within ± 5% of out put).
c) Line regulation:- Out put voltage should remain well with ±1% of set voltage ( From Minimum to Maximum i.e. either 400V. or 415V. supply variation).
d) Load regulation : Out put voltage should remain neutral well within ±1% of set voltage be (From no load to full load ) i.e. either 400V. or 415V. e) Correction speed:- Better than 35 Volt / Second.
f) Efficiency:- Better than 95% on full load.
g) Cut off limit for ( minimum & maximum ) by limit switch with Audio & Visual.
h) Metering Indication:- By Selector switch provision should be made available to measure input mains supply and out put voltage other stabilizer for load current measurement an Ammeter with selector switch should be available.
i) Lamp Indication :- For Input & Output should be provided. ( 3 lamps per side ).
j) MCB Protection: For Input side.
k) Load protection : HRC Fuse on each out put phase should be available. l) Output over shoot:- Beyond 210V to . 255V /phase in case of “ MANUAL MODE” & voltage protection :AUTO MODE” operation.(Manufacturing test certificate should be provided at the time of delivery)
m) VISUAL Indication for under voltage & over voltage of output.
n) Manual Mode:- Up & Down correction with O / P voltage over shoot protection. Beyond 210 V-255 V. per phase.
o) Nature of cooling:- Oil/ air cooled system .
p) Electric current over load protection .
q) Circuit for delay out put .
r) Input high voltage cut - off above 500 V. s) Mode of Operation:- AUTO/MANUAL with a provision to restore the normal working of the unit “STANDBY OPERATION” should be available increase of any Electronic failure in auto mode.
t) Auto Mode:- Normal * Standby.( Manufacturing test certificate should be Provided at the time of delivery)
1
-
-
100 Amp, 415 V, 4 pole on load changeover switch
1
-
-
100 amp, 415 V TPN Rewireable type Mainswitch
1
-
-
100 Amp 4 way copper busbar chamber box by 16 SWG sheet steel enclosure including porcelain chair etc . With painting complete as per direction of EIC.
1
-
-
1.1 kv GRADE 25 sq.mm 3.5 core XLPE insulated Al. Ar. armoured cable conforming to IS 7098 (Part-I) 1988, with upto date amendments
20
-
-
Making brick built foundation with supplying of all required materials suitable for the above voltage stabilizer by (4:1) cement mortar including holding down foundation bolts and plaster with neat cement finish, sloping all complete as per direction of EIC.
1
-
-
Fitting , fixing of change over switch, Busbar chamber and main switch as mentioned in item no. 15.02 to 15.04 on the iron angle frame of suitable size fixed at suitable position on wall by supplying all necessary fixing materials all complete as per direction of EIC.
1
-
-
Installation of the above voltage stabilizer as in item no. 15.01 on the foundation including making all connection complete as per direction of EIC.
1
-
-
Drawing & connection of cable on wall as in item no. 15.05 & all connection complete with all equipment as per requirement & as per direction of EIC.
20
-
-
Making joints of the cable by Supplying compression type gland thimple socket etc as per requirement & as per direction of E.I.C.
10
-
-
Making double earthing arrangement in compliance with IE rules by G.I. pipe electrode of 5O mm. dia 3 mtr. Long 2 Nos for panel and pumping machinery 25 mm. x 6 mm. G.I. earth strips from earth pit to panel and all other accessories required to complete the work..
1
-
-
Commissioning of the installation with full satisfaction of EiC and trial run as per departmental operation & guarding by engaging skilled staff for 90 days
1
-
-
N.B.:MAKE: AS PER PHE APPROVED VENDOR LIST AND ADDENDUM/CORRIGENDUM (IF ANY)
-
-
-
Add GST @18%
1
-
-
Add Labour Welfare Cess @ 1%
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements