Military Engineer Services Tender
... More
The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Augmentation And Improvement Of E M Infrastructrue At Afs Hasimara in Alipurduar, West Bengal, with an estimated contract value of Rs. 5,80,00,000. The bid opening date for this tender is 06-06-2025 and the last date for bid submission is 04-07-2025. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.
Military Engineer Services - MES Tender
Eprocure
Opening Date6 Jun 2025
Closing Date4 Jul 2025
Tender Amount₹ 5,80,00,000
AI Insights
Technical
Technical
Financial
Class Of Bidder
... View More
The eligible classes required by a bidder to participate in the tender are 'A Class' and above, 'A' and above, and Class SS to E. Additionally, the "designated class" with any Registering Authority is also mentioned, but the exact class name is not specified.
Technical Capacity
... View More
The required prior work experience for the bidder includes the completion of similar works satisfactorily. For un-enlisted contractors, the completion of works with a value as per the enlistment criteria of Class 'A' and above, and category 'b(ii)' (related to High Tension Electric Works) is required. The bidder should have completed works with Central/State Government/ Central/ State PSUs/ AWHO/ AFNHB/ CGEWHO / DGMAP. For MES enlisted contractors, they should be enlisted with MES in Class 'A' and above and category 'b(ii)', related to High Tension Electric Works, with satisfactory remarks regarding performance in respect of works in hand. No specific amount or percentage of similar works completed is mentioned. However, for consideration of one class below the eligible class bidders, the value of the tendered work should be less than twice the tendering limit of such contractor. Unenlisted contractors are required to upload details of works executed and completed in MES or any other Govt agency in the past five years with a completion certificate.
Costs
EMD
₹ 6,15,000Document Cost
₹ 3,000Tender Fee
Refer Documents
Summary
Augmentation And Improvement Of E M Infrastructrue At Afs Hasimara
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_713075_1Tender No
88475/HAS/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
(Srl Item No. 1.00 Contd...)
iv) Provision for supervision of the two indepandent Trip Circuits for the two Trip Coils to be provided. v)Switchgear classification: PM class
vi) Loss of service continuity class: LSC2A
vii) Duty Cycle : O – 0.3sec – CO – 3min – CO, Vacuum Circuit breaker shall be of M2, E2, C2 duty and capable for minimum 100 short circuit breaking operation at full short circuit level.
viii) STC rating 21 kA for 1 Sec (for Vacuum Interrupter).
ix)Vacuum Interruptor must be hermetically sealed and must comply IEC 60056 ( along with latest amendments). x) Circuit Breaker to be equipped with Suitable tripping arrangement with push button, Mechanical counter to assess the total number of operations of the breaker, Mechanical ON / OFF indicator, Auxiliary switches, Auxiliary Contacts( at least 2 NO + 2 NC of Class 2 category), Emergency trip push button.
xi) The Operating mechanism shall be spring charged motor operated type with Spring Charge Universal motor operable on 24 V DC / 230 V AC.
-
-
-
... More
(Srl Item No. 1.00 Contd...)
xii)Suitable monitoring of Circuit Breaker status ( ON, OFF, Trip, CB Spring Charged) , Trip Circuit Healthy / Unhealthy, DC healthy/unhealthy to be provided using IoT based online monitoring system using microprocessor / digital RTU with historical data saving, capable of updating status and sending alarm signal on IoT monitoring unit, GSM and GPRS platform through which live monotoring status and equipment reading and fault related history can be accessed by user remotely.
xiii) Voltage Presence Indicator shall be provided against each HT circuit ( against each VCB) on line side for knowing the presence of line enerzisation status.
xiv)Number of Mechanical operations at full rated current for breaker: 2000 O/C
HT CT /PT i) One set of 03 nos. ( for 3 phases) dual core Cast Resin CTs for Each incomer VCB complying with IEC:60185 & IS 2705 ( along with latest amendments) , Core -1 - 400-200/1 A , 15 VA, Cl 0.5 for metering ; Core-2 - 400-200/1 A, 15 VA , 5P10 for Protection.
ii) 01 no. of 03 phase Dual Core PT for HT bus ( 11 kV) with protection HRC fuse
Core 1- 11kV-6 kV /√3 / 110V/√3, Cl 0.2s, 100VA Core 2- 11kV- 6 kV /√3 / 110V/3, Cl 3P, 50VA
Multifunction Meter
-
-
-
... More
(Srl Item No. 1.00 Contd...) iii) 2 Nos. 3 phase Digital Multifunction Meter with Voltage, Amps, kWh, kW, P.F., Active, reactive, apparent energy , disturbance direction detection, Individual harmonic up to the 63rd harmonic. at least 256 samples/cycle with ethernet Port with inbuilt webserver and complying to IEC 61557-12, IEC 62053-22 certified by third party laboratory.for each VCB panel ( 96 mm x 96 mm) , Flush mounted, Class 0.2s conforming to IEC 62053-22 ( along with latest amendments) .
Protection Relay
i) 2 Nos. of Numerical Type IDMT Relay (50/51, 50N/51N) with two elements for overcurrent and earth fault having settings 50% to 200% for overcurrent and 20% to 80% for earth fault in equal steps with time and current settings and high set instantaneous unit. Additionally, condition monitoring CB wear, condition monitoring CT supervision, disturbance recorder, undervoltage & over voltage protection, trip circuit supervision can be measured through the relay. The device shall support webserver/web HMI through which we can monitor and control the relays over a ethernet Lan network. Licenses for the programming software shall be provided free of cost.The numerical relay shall have large mimic-based LCD screen display . .The relay shall have 8 Digital inputs and 8 Digital Outputs and one additional watchdog ouput.The device has able to controlling of min. six objects (circuit breakers, disconnectors and grounding switches). Controlling has to be done by “select-execute” or “direct control” principle. Controlling has to be possible by: through local HMI, remote communication, via digital input or via function key. Events has to be readable to SCADA systems, front panel or by setting software.The sample rate of the recording has to settable to 32samples/cycle.The devices shall provide storage up to events 2000 based on the resolution.The device shall support following communication protocols: Native IEC 61850 ed1 & ed2, Modbus TCP. The IEC 61850 communication has to support peer to peer communication (GOOSE) if required The IEC 61850 interface must be able to configure through setting software. Also the same setting software has to be able to generate ICD filesThe device shall have KEMA IEC61850 edition 2 certificates.
-
-
-
... More
(Srl Item No. 1.00 Contd...)
ii) Master Trip Relay : High Impedance and High speed relay flush mounted having coil cut-off contact with at least 4NO and 4NC contact and electrical reset facility capable to make, carry and break trip coil current of Circuit Breaker and capable for future integration with SCADA.
iii) Each VCB must have separate Anti Pumping Relay.
Fault Passage indicator (FPI)
The FPI shall facilitate quick detection of faulty section of line. The fault indication may be on the basis of monitoring fault current flow through the device. The FPI should be self-powered and should have internal lithium battery for external indication and setting of FPI in the absence of current.
The FPIs shall include:
Fault detection - Phase to phase and Phase to earth faults.
One potential-free output contacts for hardwiring to RTUs. On this basis, the SCADA/DMS will be able to monitor phase / earth fault condition.
Local fault indications - LCD display on FPI front panel along with LED indication on front panel of RMU enclosure.
-
-
-
... More
(Srl Item No. 1.00 Contd...)
Multiple reset option –
End of time delay (Adjustable from 2 to 16 Hrs)
Remote reset (Via potential free input contact of FPI)
Manual reset (Reset button on front panel of FPI)
Automatic reset on current restoration.
The characteristics of the FPIs shall include:
Phase fault thresholds configurable from at least 100 to 800 A
Earth fault thresholds configurable from at least 20 to 200 A
Multiple number of steps for adjusting phase and earth fault thresholds.
Fault current duration range configurable from at least 40 ms to 100 ms in 20 ms steps and further 100 ms to 300 ms in 50 ms steps. Variations with respect to these characteristics may be acceptable as long as they prove applicable and provide the same or better flexibility.
Earthing The cables shall be earthed by an earthing switch with short-circuit making capacity, in compliance with IEC 62271-102 standard. The earthing switch can only be operated when the switch is open. The switch and earthing switch operating mechanism shall have a mechanical endurance of at least 1000 operations.
Separate line side Earth switches shall be provided in each HT Circuit ( against each VCB)
-
-
-
... More
(Srl Item No. 1.00 Contd...)
RMU Bushing & Cable termination:
It is preferable to have all bushings accessible from the front of the RMU. Bushings along the sides or the rear of the RMU are not acceptable.
For each cable compartment, the bushing shall be at the same height in order to facilitate a possible reversal of the cables
The bushing should be conveniently located for working with cables specified and allow for the termination of these cables: -630 A M16 bolted connectors for switch-disconnectors and vacuum circuit breakers functions.The profiles of the cable connection bushings shall be in compliance with IEC-60137 standard. Cable clamps:A cable clamp arrangement must be provided for all network cables terminated on the RMU. Provision for Cable Entry: There shall be suitable provsion for Cable entry from bottom through 3 mm thick CRCA steel thick detachable gland plate along with provision for termination of 2 runs of 3 c X 300 Sq mm 11 kV (E ) , XLPE insulated Aluminium Cables ( for HT side) and at LT side runs of cables matching with outgoing MCCB current rating.
Note:- Unite quoted works inclue PCC work/ any civil work for foundation and Protection as per OEM for complition of Job.
-
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000V (earthed) grade with stranded aluminium conductor of size 95 Sqmm 3.0 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
5650
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000V (earthed) grade with stranded aluminium conductor of size 120 Sqmm 3.0 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
3100
-
-
... More
Taking up HT UG Cable of size 120 sqmm for checking of HT joints of cable and relaying the same after necessary repair, complete all as specified and directed. Note :- (i) Earthwork shall be measured and paid separately.
1500
-
-
... More
Excavation in trenches not exceeding 1.5 metre wide and not exc 1.5 metre in depth for foundation of pole / stay, cable trenches etc. and getting out in soft/loose soil, complete all as specified and as directed.
6888
-
-
... More
Returning, filling in soft/loose soil, including spreading, levelling, watering & well ramming in layers n. exc 25 cm complete all as specified and as directed.
1357
-
-
... More
Removing eaxcavated soil material n.exc. 50m and depositing where directed at a level n. exc. 1.5m above the starting point complete all as specified and as directed.
5531
-
-
... More
M&L for sand cushioning to under ground cable provided with a layer of sand 8 cm depth before laying of cable and 15 cm depth after laying and stretching the cable all as specified. Note: Punned thickness of sand shall be measured & paid.
1591
-
-
... More
M&L lifting the existing precast cement concrete cable cover/Serviceble bricks obtained during excavation of existing cable and laying the same covers, in trenches for cable protection, complete all as specified and as directed by the engineer-in -charge.
6375
-
-
... More
S&F Unreinforced Pre-cast Concrete Cable Cover, Class HV type 2 flat of size 450mmx180mmx40mm with minimum average breaking load 350 Kg, as per IS-5820:1970, complete all as specified and as directed.
37612
-
-
... More
S&F Sub-Class ‘B’ Bricks, well burnt, laid breadthwise along the length of Cable laid in trenches over Sand Cushion laid for UG Cable Protection, complete all as specified and as directed.
63328
-
-
... More
S&F galvanised iron pipe light grade of size 40 mm dia as in protection of UG Cable laid in trenches, complete all as specified and as directed. Note : Cost of Mild Steel Clamp, Nuts, Bolts, all fittings and painting is deemed to be included in the Quoted Unit Rate.
70
-
-
... More
S&F galvanised iron pipe light grade of size 50 mm dia as in protection of UG Cable laid in trenches, complete all as specified and as directed. Note : Cost of Mild Steel Clamp, Nuts, Bolts, all fittings and painting is deemed to be included in the Quoted Unit Rate.
60
-
-
... More
S&F galvanised iron pipe light grade of size 80 mm dia as in protection of UG Cable laid in trenches, complete all as specified and as directed. Note : Cost of Mild Steel Clamp, Nuts, Bolts, all fittings and painting is deemed to be included in the Quoted Unit Rate.
80
-
-
... More
S&F galvanised iron pipe light grade of size 100 mm dia as in protection of UG Cable laid in trenches, complete all as specified and as directed. Note : Cost of Mild Steel Clamp, Nuts, Bolts, all fittings and painting is deemed to be included in the Quoted Unit Rate.
110
-
-
... More
Boaring holes horizontally under road without damaging the surface of road (minimum 1.0 Mtr below the road surface with with manual/mechanical means, for inserting GI tubing of any dia. not exceeding 100 mm bore for passing of UG cable, complete all as specified and as directed.
Note :- GI pipe shall be measured and paid separately.
200
-
-
... More
Supply, installation, testing & commissioning of Vacuum Circuit Breaker of 400Amp, HT, 11KV three phase, 250 MVA, AC supply 26.3KA/3 Sec Vacuum interrrupters of the circuit breakers shall not be openly exposed design and shall be completely encapsulated in epoxy housing. The offered circuit braker should have valid type tests to support the afore-mentioned duty class. Tripping and/ or release coils shall be continous rated to ensure longer life. Integral spring charging handle to be provided in the CB with following:-
a) Digital Ammeter type suitable for 11 KV in built with flush type selector switch. b) Resin cast CT with ratio 50-100/5Amps with 2.5VA burden class1 for metering-Set of three. c) Microprocessor controlled numeric relay comprising of three over current, one earth fault protection relay with high set for both phase & earth and with fault memory Minimum relay setting should be at part with the CT ratio, universal auxliary supply- 01 No.
d) Trip circuit supervision realy. e) Master trip relay.
f) Power pack equipment with back up for 15 minutes including batteries suitable for operation of relays and trippling and closing coils complete.
g) Internal bus earthing with Copper strip of size 50x6mm.
h) Manual trip switch.
j) One No. of space heater witth thermostat.
k) Inside moving spot light fiting including lamp and switch (2/3 W LED 230V) - 01 No. l) One No. of plug point with switch (5A, 230V)
m) Insulated copper bus bar common for outgoing feeders. n) Manual charging/ operating arrangement.
o) Fuses for metering and protection system.
5
-
-
... More
(Srl Item No. 17.00 Contd...)
p) Trip circuit unhealthy
q) Breaker ON
r) Breaker OFF
s) Complete control panel wiring with FRLS PVC insulated copper cable of size not less than 1.5 Sqmm.
t) Civil work required for foundation as per manual of manufacturer. Note :- Incomer and outgoing VCB's should be installed in such way that cable entry at bottom side with necessary rating copper bus bar arrangement for outgoing VCB's with rear opning fully isolated. The rate quoted shall deemed to be included the followings:- i). Primary injection test and secondary injection test individually at site after erection and before commissionning at presence of OEM Rep. The contactor shall get the approval of make along with general arrangement drawing, design details from GE before procurement and VCB shall despatch after completion of factory inspection clearance by inspecting officer nominated by Accepting Officer.
ii) Servicing of HT VCB 11 KV in every 3 months after installation and up to defect liability period complete by taking the shut down with prior intimation and cleaning the VCB Bus bar chamber and entire panel by using air blower tightning of connection and earth terminals and inspection of control circuit complete checking of all fuses, power pack with connection at AC & DC side for smooth functioning by employing OEM executive including caliberation/ Checking of relay and testing of HT VCB and replacing the spares during the defect liability period all as directed by Engineer in Charge and submit the report to Engineer-in Charge.
-
-
-
... More
(Srl Item No. 17.00 Contd...)
iii) Contractor is liable to attend the break down caused by any error/ fault in VCB relay, Control circuit without any delay in time to restore the power supply irrespective of cost/ number of spares to be replaced during the defect liability period.
iv) Contractor shall install one Nos UPS for back up for each VCB panels/ Substation having single phase AC input 160 to 260 V and out put 230 + 1% sine wave out put wave form of capacity 5/ 5.5 KVA capacity with necessary battery bank as per following specifications:- a) Full load output current 15 + 0.5 A
b)Boost mode charging wih battery 12 V /up to min 150/152 Ah battery -08 Nos mounted on separate stand/ including connection from battery bank to UPS/Charging circuit complete as per manufacture Thechnical specifications. b) Over load, Short circuit, Battery deeo discharge, Battery over charge Main low a, Mains high, and thermal protection.
-
-
-
... More
M&L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron 32X6 mm as earthing lead by mean of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earth work GI pipe 20mm dia light grade for watering PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to panel board / Gen Set as indicated including testing, complete all as specified and as directed.
98
-
-
... More
Supply and fixing HT Bus Bar box outdoor type, factory made, CPRI approved, powder coated inner and outer shell made out of 3.15mm thick MS sheet, IP 66 protection on angle iron framing 50x50x6 mm MS with cannopy on top spread out 15 cm from top, HT resincust moulded bushing fitted on 12 mm glass fiber inside top plate suitable for 11KV with 3 Nos copper bus bar 400 amp current capacity, separeted with fire retardent separator mounted on HT Insulator 06, duly powder coated painted externaly and internaly and danger marking of 11000 volt complete of size 1.0X1.5X1.0 metre including all cable jointing nuts bolts made of brass/ HS steel of suitable size and PCC for grouting of joint Box to be fixed 02 feet height from ground level including dismantling the existing junction box complete all as specified and directed . Note: Necessary earth work, PCC foundation, taking out the HT UG Cable loop for connection, dismantling of existing junction box shall be deemed to be included in quoted rate.
10
-
-
... More
Supply, installation, testing and commissioning step down transformer, outdoor type, plinth mounted HT 11 KV, 3 phase 433 volts, 4 wire, 50 Hz, delta/star connected, vector group DYN -11 double copper wound, ONAN, manual type off load tap changing facility on HT side to vary secondary voltage from minus 7.5% to plus 7.5% in steps of 2.5 %, continuous rating, conforming to IS-1180 (Part-I) : 2014, Level-III as per latest 4th amendment in March 2021 of capacity 400 KVA incl bushing on HT end cable box on LT side. The transformer shall be complete with all standard fittings and accessories, gauges, first fill of transformer oil, etc, and conforming to IS 1180 Part-1:2014 duly mounted on plinth and all as specified and as directed.
(a) Oil conservator with filling hole, cap and drain plug
(b) Silica gel breather with oil seal and first fills of dehydrating agent (c) Adequate Nos of thermometer pockets incl one No for accomodating bulb type thermometer
(d) Drain cum bottom filter valve
(e) Top filter valve
(f) Prisomatic oil level gauge
(g) Inspection cover
(h) Cover fitting lugs
(j) Jacking and fitting lugs
(k) Separate neutral bushing brought out for earthing on LV side
(l) Earthing terminal
Note: PCC platform / plinth for placing transformer is not included in the quoted rate and will be measured and paid under seperate item.
2
-
-
... More
M&L for cable end jointing kit Indoor termination Cold Shrinkable type complete with jointing materials with all accessories suitable for XLPE 11 KV (Earthed), 3 Core, armoured aluminium conductor cable of size 95 Sqmm, complete all as specified and as directed.
52
-
-
... More
M&L for cable end jointing kit outdoor termination Cold Shrinkable type complete with jointing materials with all accessories suitable for XLPE 11 KV (Earthed), 3 Core, armoured aluminium conductor cable of size 50 Sqmm to 95 Sqmm, complete all as specified and as directed.
4
-
-
... More
M&L for cable end jointing kit Indoor termination Cold Shrinkable type complete with jointing materials with all accessories suitable for XLPE 11 KV (Earthed), 3 Core, armoured aluminium conductor cable of size 120 Sqmm, complete all as specified and as directed.
1
-
-
... More
M&L for cable end jointing kit straight through termination Heat Shrinkable type complete with jointing materials with all accessories suitable for XLPE 11 KV (Earthed), 3 Core, armoured aluminium conductor cable of size 120 Sqmm, complete all as specified and as directed.
6
-
-
... More
M&L for cable end jointing kit straight through termination Heat Shrinkable type complete with jointing materials with all accessories suitable for XLPE 11 KV (Earthed), 3 Core, armoured aluminium conductor cable of size 95 Sqmm, complete all as specified and as directed.
8
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 33000V (earthed) grade with stranded aluminium conductor of size 120 Sqmm 3.0 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
100
-
-
... More
M&L cable end jointing kit indoor termination Heat Shrinkable type complete with jointing materials with all accessories suitable for XLPE 33 KV (Earthed), 3 Core, armoured aluminium conductor cable of size 120 Sqmm, complete all as specified and as directed
2
-
-
... More
M&L for dismantling existing 4 pole structure complete in rplacement of 4 way RMU, complete all as specified and as directed
8
-
-
... More
M&L for shifting of transformer 200 KVA with LT panel from KV no -02 Sub station to MES MD Accn area including dismatling the HT/LT Connections and installed at new location including RCC foundation, complete all as specified and as directed
1
-
-
... More
Dismantling old LT panel of bus bar capacity upto 400 Amp including MCCBs, complete all as specified and as directed
18
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 400 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
1540
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 300 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
80
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 240 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
250
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 185 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
180
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 150 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
260
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 120 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
240
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 70 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
1020
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 50 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
600
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 35 Sqmm 3.5 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
1020
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 25 Sqmm 4.0 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
4050
-
-
... More
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100V (earthed) grade with stranded aluminium conductor of size 16 Sqmm 4.0 core all as per IS:7098(Pt-II) complete all as specified and directed. NOTE: Earth work, cable cover, sand cushioning shall be measured and paid seperately under respective items.
225
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1400(H)x1350(W)x600(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 630A, 4 Pole, 50KA TM- 01 No.
b) Spreader link 630A 4P- 01 No
c) Extended Rotary Handle 630A- 01 No
d) C T Coil 600/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 250A 4P 36KA TM - 03 Nos
b) Spreader link 250A 4P- 03 Nos
c) Extended Rotary Handle 250A- 03 Nos
d) MCCB 200A 4P 36KA TM- 01 No.
e) Spreader link 200A 4P- 01 No. f) Extended Rotary Handle 200A - 01 No
Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1950(H)x1350(W)x600(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 630A, 4 Pole, 50KA TM- 01 No.
b) Spreader link 630A 4P- 01 No
c) Extended Rotary Handle 630A- 01 No
d) C T Coil 600/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 250A 4P 36KA TM - 02 Nos
b) Spreader link 250A 4P- 02 Nos
c) Extended Rotary Handle 250A- 02 Nos
d) MCCB 200A 4P 36KA TM- 02 Nos.
e) Spreader link 200A 4P- 02 Nos. f) Extended Rotary Handle 200A - 02 Nos
Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1000(H)x9000(W)x400(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 250A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 250A 4P- 01 No
c) Extended Rotary Handle 250A- 01 No
d) C T Coil 250/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 125A 4P 36KA TM - 03 Nos
b) Extended Rotary Handle 125A- 03 Nos
c) MCCB 40A 4P 25KA TM- 03 Nos.
d) Extended Rotary Handle 40A - 03 Nos
e) Terminal 63A 4P- 03 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1150(H)x1050(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 100A, 4 Pole, 25KA TM- 01 No.
b) Spreader link 100A 4P- 01 No
c) Extended Rotary Handle 100A- 01 No
d) C T Coil 100/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 40A 4P 25KA TM - 06 Nos
b) Extended Rotary Handle 40A- 06 Nos
c) Terminal 63A 4P- 06 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1300(H)x1050(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 125A, 4 Pole, 25KA TM- 01 No.
b) Spreader link 125A 4P- 01 No
c) Extended Rotary Handle 125A- 01 No
d) C T Coil 150/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 40A 4P 25KA TM - 07 Nos
b) Extended Rotary Handle 40A- 07 Nos
c) Terminal 63A 4P- 07 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
3
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1250(H)x1200(W)x400(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 250A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 250A 4P- 01 No
c) Extended Rotary Handle 250A- 01 No
d) C T Coil 250/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 125A 4P 36KA TM - 03 Nos
b) Spreader link 125A 4P- 03 Nos
c) Extended Rotary Handle 125A- 03 Nos
d) MCCB 40A 4P 25KA TM- 01 Nos.
e) Extended Rotary Handle 40A - 01 No. f) Terminal 63A 4P- 01 No.
Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1350(H)x1050(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 100A, 4 Pole, 25KA TM- 01 No.
b) Spreader link 100A 4P- 01 No
c) Extended Rotary Handle 100A- 01 No
d) C T Coil 100/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 40A 4P 25KA TM - 07 Nos
b) Extended Rotary Handle 40A- 07 Nos
c) Terminal 63A 4P- 07 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1350(H)x1050(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 200A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 200A 4P- 01 No
c) Extended Rotary Handle 200A- 01 No
d) C T Coil 200/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 63A 4P 25KA TM - 03 Nos
b) Extended Rotary Handle 63A- 03 Nos
c) MCCB 40A 4P 25KA TM- 05 Nos.
d) Extended Rotary Handle 40A - 05 Nos. e) Terminal 63A 4P- 08 Nos.
Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1250(H)x1200(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 63A, 4 Pole, 25KA TM- 01 No.
b) Spreader link 63A 4P- 01 No
c) Extended Rotary Handle 63A- 01 No
d) C T Coil 60/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 40A 4P 25KA TM - 05 Nos
b) Extended Rotary Handle 40A- 05 Nos
c) Terminal 63A 4P- 05 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
2
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1800(H)x1300(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 320A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 320A 4P- 01 No
c) Extended Rotary Handle 320A- 01 No
d) C T Coil 400/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 320A 4P 36KA TM - 02 Nos
b) Spreader link 320A 4P- 02 Nos
c) Extended Rotary Handle 320A- 02 Nos
d) MCCB 40A 4P 25KA TM- 03 Nos.
e) Extended Rotary Handle 40A - 03 Nos f) Terminal 63A 4P- 03 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1650(H)x1100(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 320A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 320A 4P- 01 No
c) Extended Rotary Handle 320A- 01 No
d) C T Coil 400/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 125A 4P 36KA TM - 02 Nos
b) Spreader link 125A 4P- 02 Nos
c) Extended Rotary Handle 125A- 02 Nos
d) MCCB 40A 4P 25KA TM- 08 Nos.
e) Extended Rotary Handle 40A - 08 Nos f) Terminal 63A 4P- 08 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1650(H)x1100(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 250A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 250A 4P- 01 No
c) Extended Rotary Handle 250A- 01 No
d) C T Coil 250/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 200A 4P 36KA TM - 02 Nos
b) Spreader link 200A 4P- 02 Nos
c) Extended Rotary Handle 200A- 02 Nos
d) MCCB 40A 4P 25KA TM- 04 Nos.
e) Extended Rotary Handle 40A - 04 Nos f) Terminal 63A 4P- 04 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1650(H)x1100(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 200A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 200A 4P- 01 No
c) Extended Rotary Handle 200A- 01 No
d) C T Coil 200/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 40A 4P 25KA TM - 10 Nos
b) Extended Rotary Handle 40A - 10 Nos c) Terminal 63A 4P- 10 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1200(H)x1100(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 200A, 4 Pole, 36KA TM- 01 No.
b) Spreader link 200A 4P- 01 No
c) Extended Rotary Handle 200A- 01 No
d) C T Coil 200/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 100A 4P 36KA TM - 02 Nos
b) Spreader link 100A 4P- 02 Nos
c) Extended Rotary Handle 100A- 02 Nos
d) MCCB 40A 4P 25KA TM- 06 Nos.
e) Extended Rotary Handle 40A - 06 Nos f) Terminal 63A 4P- 06 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1200(H)x1100(W)x500(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 100A, 4 Pole, 25KA TM- 01 No.
b) Spreader link 100A 4P- 01 No
c) Extended Rotary Handle 100A- 01 No
d) C T Coil 100/5- 03 Nos
e) R Y indicator lamps LED- 02 Set
f) Blue Indicator Lamp LED- 01set
g) Digital Multifunction Meter - 01 No
h) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 40A 4P 25KA TM - 05 Nos
b) Extended Rotary Handle 40A - 05 Nos c) Terminal 63A 4P- 05 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
1
-
-
... More
Dismantling of LT UG cables of any size, complete all as specified and as directed.
6600
-
-
... More
M&L for relaying of LT UG Cable of size 50sqmm 3.5 core, complete all as specified and as directed. Note :- Earthwork, PCC cover and Sand cushioning shall be measured and paid separately.
50
-
-
... More
M&L for relaying of LT UG Cable of size 35sqmm 3.5 core, complete all as specified and as directed. Note :- Earthwork, PCC cover and Sand cushioning shall be measured and paid separately.
60
-
-
... More
M&L for relaying of LT UG Cable of size 25sqmm 4core, complete all as specified and as directed. Note :- Earthwork, PCC cover and Sand cushioning shall be measured and paid separately.
280
-
-
... More
M&L for relaying of LT UG Cable of size 16sqmm 4core, complete all as specified and as directed. Note :- Earthwork, PCC cover and Sand cushioning shall be measured and paid separately.
40
-
-
... More
Supply, Installation and Commissioning 12.5 Mtrs Motorised High Mast having provision for 120 Watt 04 Nos LED FLOOD LIGHT LUMINAIRES Thickness : Top -3 mm , bottom -4 mm , Diameter : 150 mm , bottom 300 mm , with resisting wind speed 180 Km/Hr , Intergral motor , 6 mm Hoisting SS ropes Drouble Drum Winch, Movable Landern Carriage , 5 core 4 sq mm Trailing Cable , Lightning Final , Anchor plate and Template . Hot dip Galvanised system Internally and Externally Including necessary foundation ,foundation Bolts and Nuts with including following with two luminaire mounting arm, pulley assembly, including LED aviation obstruction light, lightening arrestor spike, monkey menance spike with including suitable Timer panel RCC Foundation as per manufacturer instruction complete, suitable for 04 Nos 120 Watt LED Flood lights all as specified and directed by Engineer-in-Charge .
Note: Rate quoted shall be inclusive for necessary earth work for installation at any type of soil and following and Luminaire installed in High Mast will be measured and paid seperately. Note :- 1. A Vandal and weather proof door with provision to padlock is to be provided to have clear access to the base compartment equipments like winch, motor, cable, termination etc;. The base flange welded to high mast shaft develops full strength of the section. 2. Winches are completely self sustaining with out the need of any break/spring/clutch, self lubricating by means of oil bath, worm gear driven of ratio 53:1, grooved drums for tidy and smooth rope lay. The winch is designed to install or remove through the mast door. Name plate is provided giving the details of type of winch, SWL, operating speed and year of manufacturing and instruction plate for the type of the lubricant.
1
-
-
... More
(Srl Item No. 62.00 Contd...)
3. Stainless steel wire ropes in grade 304 or 316 in flexible 7/19 construction (central core is also of same material) of various diameters to have factor of safety more than 5 specified in the TR No-7. Ropes for 2 wire rope, DD type winches have both ends with factory fitted talurit and thimble and copper crimping. 4. The standard luminary's carriage in two halves is of welded construction fabricated from durable round steel tube for aerodynamic effect and to act as conduit with holes in bottom side to take the wiring flexible cable. Arms with circular profile for mounting luminaries are welded to the ring. HDG clamps with S.S hardware are provided to mount the CG boxes and balance the weight oncarriage to avoid eccentric load. Legs are welded to anchor the wire rope for 2 or 3 ropes.
5. Provision of lightening arrestor spike along with earthing connection and canopy to fix the hot dip galvanized lightening finial fabricated out of ERW tube.
-
-
-
... More
Supply, Installation and Commissioning 16 Mtrs Motorised High Mast having provision for 210 Watt 08 Nos LED FLOOD LIGHT LUMINAIRES Thickness : Top -3 mm , bottom -4 mm , Diameter : 150 mm , bottom 410 mm , with resisting wide speed 180 Km/Hr , Intergral motor , 6 mm Hoisting SS ropes Drouble Drum Winch, Movable Landern Carriage , 5 core 4 sq mm Trailing Cable , Lightning Final , Anchor plate and Template . Hot dip Galvanised system Internally and Externally Including necessary foundation ,foundation Bolts and Nuts with including following with two luninaire mounting arm, pulley assembly, including LED aviation obstruction light, lightening arrestor spike, monkey menance spike with including suitable Tmer panel RCC Foundation as per manufacturer instruction complete, suitable for 08 Nos 210 Watt LED Flood lights all as specified and directed by Engineer-in-Charge .
Note: Rate quoted shall be inclusive for necessary earth work for installation at any type of Soil and following and Luminaires installed in High Mast will be measured and paid seperately. Note :- 1. A Vandal and weather proof door with provision to padlock is to be provided to have clear access to the base compartment equipments like winch, motor, cable, termination etc;. The base flange welded to high mast shaft develops full strength of the section. 2. Winches are completely self sustaining with out the need of any break/spring/clutch, self lubricating by means of oil bath, worm gear driven of ratio 53:1, grooved drums for tidy and smooth rope lay. The winch is designed to install or remove through the mast door. Name plate is provided giving the details of type of winch, SWL, operating speed and year of manufacturing and instruction plate for the type of the lubricant.
2
-
-
... More
(Srl Item No. 63.00 Contd...)
3. Stainless steel wire ropes in grade 304 or 316 in flexible 7/19 construction (central core is also of same material) of various diameters to have factor of safety more than 5 specified in the TR No-7. Ropes for 2 wire rope, DD type winches have both ends with factory fitted talurit and thimble and copper crimping. 4. The standard luminary's carriage in two halves is of welded construction fabricated from durable round steel tube for aerodynamic effect and to act as conduit with holes in bottom side to take the wiring flexible cable. Arms with circular profile for mounting luminaries are welded to the ring. HDG clamps with S.S hardware are provided to mount the CG boxes and balance the weight oncarriage to avoid eccentric load. Legs are welded to anchor the wire rope for 2 or 3 ropes.
5. Provision of lightening arrestor spike along with earthing connection and canopy to fix the hot dip galvanized lightening finial fabricated out of ERW tube.
-
-
-
... More
Supply, installation of LED flood light of capacity 120 watt including all connected wiring of luminaries with all wiring material like PVC insulated with PVC sheathed flexible cable of suitable size with suitable lugs etc. the flood light luminaries shall be gray epoxy powder coated pressure die cast aluminium housing (LM 24) with IP-66 protection and elegently designed heat sink for efficient thermal management, sturdiness and excellent corrosion resistant and cable gland to be provided at cable entry for maintaining ingress protection with heat resistant clear toughened glass fixed to the frame with silicon gasket and SS screw with high efficiency long life LED chips in moudle with Ra more than 70 and lumen efficiency of 120 lumen per watt in built electronic driver with APFC, complete all as specified and directed.
4
-
-
... More
Supply, installation of LED flood light of capacity 210 watt including all connected wiring of luminaries with all wiring material like PVC insulated with PVC sheathed flexible cable of suitable size with suitable lugs etc. the flood light luminaries shall be gray epoxy powder coated pressure die cast aluminium housing (LM 24) with IP-66 protection and elegently designed heat sink for efficient thermal management, sturdiness and excellent corrosion resistant and cable gland to be provided at cable entry for maintaining ingress protection with heat resistant clear toughened glass fixed to the frame with silicon gasket and SS screw with high efficiency long life LED chips in moudle with Ra more than 70 and lumen efficiency of 130 lumen per watt in built electronic driver with APFC, complete all as specified and directed.
16
-
-
... More
Supply & installation of Hexagonal steel poles of 8 meter height, 1 meter double armed normal bracket, 3 mm section thickness, top dia. 70 mm, bottom dia. 135 mm, base plate 225x225x16 mm and its accessories including 02 Nos of 70 W LED Lights Note:- Earthwork and PCC foundation shall deemed to be included in quoted rate and PCC foundation shall be constructed as per manufacturer's instruction.
47
-
-
... More
Supply, installation, testing and commissioning of CPRI approved outdoor type feeder piller of size 1000(H)x900(W)x400(D)mm, double layer door, inner parts made of 2mm thick CRCA sheet and outer shell of 3.15mm thick CRCA sheet, having rain canopy type four side slope top, supported on 50x50x6mm angle iron base frame and legs of 600mm height , painted with textured aluminium powder coated paint of thickness not less than 100 microns after preparation of surface in 8 tank sheet process system, aluminium busbar & strips current capacity. All outgoing switchgears shall have extended strips (for ampere rating more than 63A) or extended wires with terminals (for ampere rating below 80A) for easy and comfortable outgoing connection. The wiring will be complete with sockets and ferrule markings. The control wiring shall be done by 1.5 Sqmm copper wire. Internal connection with suitable size Al strip/Cu wire, complete with the following. Incoming:-
a) MCCB 25A, 4 Pole, 25KA TM- 01 No.
b) Extended Rotary Handle 25A- 01 No
c) C T Coil 30/5- 03 Nos
d) R Y indicator lamps LED- 02 Set
e) Blue Indicator Lamp LED- 01set
f) Digital Multifunction Meter - 01 No
g) MCB 6A SP for meter protection- 03 Nos.
Outgoing:-
a) MCCB 25A 4P 36KA TM - 01 Nos
b) Extended Rotary Handle 25A- 02 Nos
c) Astro time switch - 02 Nos
d)3 Pole Power Contractors - Type MNX - 02 Nos e) Auto manual selector switch - 02 Nos f) Terminal 63A 4P- 02 Nos. Note :- Foundation and PCC work for LT panel shall deemed to be included in quoted rate.
5
-
-
... More
M&L for Cement Concrete 1:4:8 type D2 (using 40mm graded stone aggregate) as in Foundation of Poles, Stay Assembly, etc., including necessary formwork, complete all as specified and as directed.
1
-
-
... More
M&L for Cement Concrete 1:3:6 type C2 (using 40mm graded aggregate) as in foundation of Poles, Stays, etc. including necessary formwork, complete all as specified and as directed.
1
-
-
... More
M&L for Cement Concrete 1:2:4 type B1 (using 20mm graded aggregate) as in Coping of Poles, etc. and finishing the Concrete surfaces fair and even including necessary formwork, complete all as specified and as directed.
1
-
-
... More
M&L for power cable route marker pre-cast RCC of size 1500mm x 300mm x 50mm with top curved protion, 8mm dia round bar reinforcement, emboshing of letter (MES-POWER CABLE) both faces of pre-cast during casting of RCC pre-cast, applying two coats of external emulsion paint witth primer of approved colour and painting of emboshed surface with black colour, complete all as specified and as directed.
70
-
-
... More
M&L Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as required of 32x6mm galvanised iron strip, complete all as specified and as directed.
60
-
-
... More
Horizontal directional drilling (HDD) boring of holes under road, pavement, hard standing, runway/PTT by trenchless technology using ultra sound technique and necesary machine including provision of HDPE pipe of size not less than 150 mm dia. suitable for 0.4 Mpa working pressure, complete all as specified and directed.
40
-
-
... More
S&F Junction box made from SMC/FRP sheet ready made of size 350x225x140 mm with aluminium bus bar of 100 Amp capacity for RYB and half for netural made in suitable size fixed inside the junction box with necessary supporting insulators fixed on hylem sheet, MS sheet fixed inside the bottom portion of box to connect the cable gland complete, entire assembly fixed to pole/Wall with MS clamp 25 x 5 mm and nuts & bolts or inside the copping of pole/ post top including MCB SP 6 Amp 10 KA 240 V -02 Nos, with necessary size copper lugs for connecting cables from junction box to fittings, complete all as specified and directed.
25
-
-
... More
Supply, laying and fixing copper cable 1.5 sqmm 3.0 core, PVC insulated FR round sheathed copper conductor PVC cable, complete all as specified and directed.
940
-
-
... More
Note:- Schedule of cedit (Sch 'A' Part- II) amount of Rs 4,71,630.00 shall be deducted from the total quoted amount of BOQ.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%