The MES has issued a formal invitation for competitive bids for the Military Engineer Services project, for Special Repair /replacement To Ht Cable From Samra Substation To Substation 8a Under Ge N Binnaguri in Jalpaiguri, West Bengal, with an estimated contract value of Rs. 39,50,000. The bid opening date for this tender is 30-10-2026 and the last date for bid submission is 21-11-2026. Interested bidders for Military Engineer Services tender can download the important documents here to check the scope of work, eligibility criteria and technical requirements.

Military Engineer Services - MES Tender - WB Tender

Opening Date30 Oct 2026
Closing Soon21 Nov 2026
Tender Amount₹ 39,50,000 
Notes
Download

Costs

Description

Special Repair /replacement To Ht Cable From Samra Substation To Substation 8a Under Ge N Binnaguri

Contact

Unlock the Tender details

GEM & Bid Advisory Services

Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

Unlock the Tender details
... More
Returning, filling in, including spreading levelling watering and well rammming in layers not exceeding 25 cms in depth complete all as specified and as directed.

384

1

-

... More
Removing surplus soil to a distance not exceeding 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and as directed.

205

1

-

... More
Supply and lay dry river sand filling for under ground cable protection with a layer of 8cm deep before laying and 15cm covering above the top edge of cable after laying complete all as specified and as directed.

118

1

-

... More
Refixing only serviceable PCC cable cover obtained from item No 01 here in before complete all as specified and as directed.

500

1

-

... More
Supplying and Laying Un-inforced precast concrete cable cover , class HVP type 1 with peak size 300mm x 180mm x 40mm all as specified and directed.

7200

1

-

... More
M & L for horizontal boring across the existing road without disturbing the road surface for inserting GI pipe complete all as specified and as directed. Note :- (i) Removal of surplus soil shall be deemed to be include in the unit Rate. (ii) GI pipe will be measured and paid separately under relevant item of Sch 'A'.

12

1

-

... More
M&L 100 mm bore steel tubing light grade ISI marked for protection of cable including necessary joints complete all as specified and as directed.

18

1

-

... More
Material & labour for cable End jointing kit for 11 KV (earthed) grade cable, for indoor termination cold shrinkable type joint complete with jointing material and accessories suitable for XLPE insulated armoured aluminium conductor cable of size 3 Core 95 sqmm complete all as specified and directed.

9

1

-

... More
M&L for precast cable route indicator of size 100x30x10 Cms by using 20 mm graded aggregate type B1 1;2;4 for cable indicator and engraving as "HT CABLE" slightly round from one side incl Red painting with two coat of synthetci enamel paint of a coat of primer complete all as specified & directed

26

1

-

... More
Dismantling of old U/S 11 KV junction box including foundation after disconnecting of all elecrical connection complete all as specified and as directed.

3

1

-

... More
Supply and installation (above ground) including testing HT joint box (CPRI approved)3 way outdoor type of size 1700x1200x1500mm (overall) made out 3.15mm thick CRCA sheet with supprt of angle iron frame of size 40x40x6mm with KIOSK BOX and comprising of 06 Nos HT procelain bushing and copper round bus bar 12mm dia rigidly mounted on bakelite sheet 12mm thick to support insulatiors of suitable size and shape including providing necessary electric connection and applied two coats of synthetic enamel paint over a coat of red oxide primer to steel surfaces (internally & externally) including PCC foundation base of suitable size with PCC 1:3:6 type C1 using 20mm graded aggregate complete including necessary excavation and earth work for foundation and necessary electric connection complete and including dismantling of unserviceable joint box complete all as specified and as directed. NOTE : (i)Cost of digging of HT UG cable loop are included in unit rate. (ii) Valid CPRI approved certificate needs to be produced before execution of work.

3

1

-

... More
Material and labour for PCC 1:2:4 type C2 using 40mm graded stone aggregate for foundation of poles, stay etc complete all as specified and directed.

2

1

-

... More
M&L in replacement for Earthing complete with galvanised steel earth plate electrode 600x600x6.0 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below the ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to galvanised earth strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or of steel all as shown in electrical plate No 3 of SSR part-I 2009 connected to pole/LT Panel all as specified and testing on completion including. Necessary excavation, earthwork, PCC works and CI earth pit cover with watering pipe 20mm dia GI pipe medium grade, funnel with wire mesh and lugs and GI pipe 40 mm dia of light grade, for protection of earth strip complete all as specified and directed. Note: (i) Excavation/PCC/Earth work/Charcoal/ Salt shall be deemed to be include in this unit rate. (ii) Contractor shall produce valid Electrical Licence before execution of work. (iii) The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule 'A'/BOQ.

9

1

-



Evaluation Notes How It Works ?

Related Tenders

Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.