Central Mechanical Engineering Research Institute Tender
Search from over 10,000+ business opportunities that have been announced from the biggest West Bengal tenders, e tender West Bengal, WB government tenders, and the Online Tender Notices posted on West Bengal e tenders to date. Find opportunities that have come in from multiple corporations, West Bengal government departments, State PSUs, and several Private companies from the state.
Central Mechanical Engineering Research Institute - CMERI Tender
Civil And Construction
Building Construction
Electrical and Electronics
Electrical Works
Eprocure
Opening Date16 Jan 2024
Closing Date25 Jan 2024
Tender Amount₹ 83,01,871
Costs
EMD
₹ 1,66,040Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_CSIR_181480_1Bid Award Id
ViewTender No
55/426/23-24/(CE)/P-702/ESDTender Authority
Central Mechanical Engineering Research Institute ViewPurchaser Address
-Website
http://https://www.csir.res.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Tender acceptance letter, Bank Details, Bid Security Declaration and Undertaking (format given)
Make of Electrical and Civil Material, Scope of work Civil and Electrical.
BOQ Items
Dismantling CI or AC rain water/waste pipe 100mm dia. with fittings within a lead of 50m
550
-
-
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.
Using M.S. angels 40x40x6 mm for diagonal braces
12
-
-
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters: 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
10
-
-
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both
faces of shutters: 25 mm thick (for cupboard) including ISI marked nickel plated bright finished M.S. piano hinges with necessary screws
13
-
-
Providing and laying cement concrete 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor block, plain window sills, fillets etc. up to floor five level, excluding the cost of centreing, shuttering and finishing:
1
-
-
Providing, mixing and applying bonding coat of approved adhesive on chipped portion of RCC as per specifications and direction of Engineer-In-charge complete in all respect: Epoxy bonding adhesive having coverage 2.20 sqm/kg of approved make
180
-
-
Providing, mixing and applying SBR polymer (of approved make) modified Cement mortar in proportion of 1:4 (1 cement: 4 graded coarse sand with polymer minimum 2% by wt. of cement used) as per specifications and directions of Engineer-in-charge.
Note: Measurement and payment: The pre-measurement of thickness
shall be done just after the surface preparation is completed and Payment under this item shall be made only after proper wet curing has been done and surface has been satisfactorily evaluated by sounding / tapping with a blunt metal instrument and/or the 75mm size cube crushing strength at the end of 28 days to be not less than
30 N/Sqmm2). 12 mm average thickness.
550
-
-
Shotcreting R.C.C. columns, beams and slabs etc. in layers with approved design mix concrete having the specified minimum characteristic compressive strength [with ordinary portland cement, coarse sand and graded stone aggregate of 10 mm maximum size in proportion as per design criteria] including the cost of centering and shuttering at edges and corners etc. as directed by Engineer in-Charge
Note: Rates shall include the providing necessary ground wires etc.
The levelling gauges, if used, shall be paid for separately. Payment
under this item shall be made only after proper wet curing has beendone and surface has been satisfactorily evaluated by sounding/
tapping with a blunt metal instrument. 25mm thick in Grade M 25 with cement content not less than 330 kg per cum
160
-
-
Shotcreting R.C.C. columns, beams and slabs etc. in layers with approved design mix concrete having the specified minimum characteristic compressive strength [with ordinary portland cement, coarse sand and graded stone aggregate of 10 mm maximum size in proportion as per design criteria] including the cost of centering and shuttering at edges and corners etc. as directed by Engineer in-Charge
Note: Rates shall include the providing necessary ground wires etc. The levelling gauges, if used, shall be paid for separately. Payment under this item shall be made only after proper wet curing has been done and surface has been satisfactorily evaluated by sounding/ tapping with a blunt metal instrument.
50mm thick in Grade M 25 with cement content not
less than 330 kg per cum
130
-
-
26.38 Shotcreting R.C.C. columns, beams and slabs etc. in layers with
approved design mix concrete having the specified minimum characteristic compressive strength [with ordinary portland cement, coarse sand and graded stone aggregate of 10 mm maximum size in proportion as per design criteria] including the cost of centering and shuttering at edges and corners etc. as directed by Engineer in-Charge
Note: Rates shall include the providing necessary ground wires etc. The levelling gauges, if used, shall be paid for separately. Payment under this item shall be made only after proper wet curing has been done and surface has been satisfactorily evaluated by sounding/ tapping with a blunt metal instrument.
75mm thick in Grade M 25 with cement content not
less than 330 kg per cum
50
-
-
Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a minimum depth of 100mm upto 200mm in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in position using epoxy resin anchor grout of approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge: Upto and including 12mm dia.
65
-
-
Providing and injecting approved grout in proportion recommended by the manufacturer into cracks/honey-comb area of concrete/masonry by suitable gun/pump at required pressure including cutting of nipples after curing etc. complete as per directions of Engineer-in Charge: Epoxy injection grout in concrete/RCC work of approved make. (The payment shall be made on the basis of actual weight of approved grout injected.)
40
-
-
Providing and inserting 12mm dia galvanised steel injection nipple in honey comb area and along crack line including drilling of holes of required diametre (20mm to 30mm) up to depth from 30mm to 80mm at required spacing and making the hole & crack dust free by blowing compressed air, sealing the distance between injection nipple with adhesive chemical of approved make and allow it to cure complete as per direction of Engineer-In-Charge.
40
-
-
Providing and fixing hard drawn steel wire fabric of size 75 x25 mm mesh or other suitable size wire mesh to be fixed & firmly anchored to the concrete surface by means of "L" shaped mild steel shear key welded with existing reinforcement including the cost of materials, labour, tool & plants as approved by Engineer-in-charge.
40
-
-
15mm cement plaster on rough side of mix 1:4 (1cement: 4coarse sand)
120
-
-
Repair to plaster of thickness 12mm to 20 mm in patches of area 2.5 sqm and under, including cutting the patch in proper shape, raking out joints and preparing plastering the wall surface with white cement based polymer modified self curing mortar, including disposal of rubbish, all complete as per the direction of Engineer-In-Charge.
100
-
-
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade two or more coat.
2300
-
-
Supplying, fitting and fixing Waste fittings of 32 mm for basin/sink complete.
10
-
-
Providing and fixing PVC flexible waste pipe for sink and wash basin : 32 mm dia
64
-
-
Providing and fixing ISI marked M.S. pressed butt hinges bright finished with necessary screws etc. complete : 100x58x1.90 mm
30
-
-
Providing and fixing bright finished brass tower bolts (barrel type) of size 200x10 mm with necessary screws etc. complete.
15
-
-
Providing and fixing bright finished brass tower bolts (barrel type) of size 100x10 mm with necessary screws etc. complete.
20
-
-
Providing and fixing chromium plated brass handles of 125 mm with necessary screws etc. complete
10
-
-
Providing and fixing ISI marked oxidised MS sliding door bolt with nuts & screws etc. complete: 300 x 16mm
10
-
-
Renewing 4mm glass panes with putty and nails necessary
10
-
-
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x0.90 mm M.S. laths with 0.90 mm thick top cover
19
-
-
Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : New work (two or more coats) over and including priming coat with cement primer
4300
-
-
White wash with lime to give an even shade to new work (three or more coats
4200
-
-
Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface :
1500
-
-
Finishing walls with Acrylic Smooth exterior paint of required shade : Old work (Two or more coat applied @ 1.67 ltr/ 10 sqm) on existing cement paint surface
5600
-
-
Providing and fixing brass bib cock of approved quality : 15 mm nominal bore
20
-
-
Providing and fixing brass stop cock of approved quality : 15 mm nominal bore
20
-
-
Removing corroded worn out portion of reinforcement (when the area of bar is damaged by more than 25%) by cutting and replacing the same by a new plain round bar of requisite diameter by binding with required lap / welding with old bar, including cost of reinforcement, including applying of rust off and rust top or equivalent chemical for protection of old corroded rebar complete in all respect including removing unserviceable materials from site as per direction of the Engineer - in - charge. Note : Payment on weight (Kg.) of new reinforcement.
200
-
-
Supply of UPVC pipes (B Type) & fittings conforming to IS-13592-1992: Single Socketed 3 Meter Length: 110 mm
400
-
-
Supply of UPVC pipes (B Type) & fittings conforming to IS-13592-1992: Fittings Door Tee 110 mm
96
-
-
Supply of UPVC pipes (B Type) & fittings conforming to IS-13592-1992: Single Socketed 3 Meter Length: 75 mm
160
-
-
Supply of UPVC pipes (B Type) & fittings conforming to IS-13592-1992: Fittings Door Tee 75 mm
72
-
-
Labour for fitting and fixing U.P.V.C. pipes for above ground work
including cost of jointing materials etc. fitting and fixing all necessary specials, cutting pipes, cutting holes in walls or R.C. floor where necessary and mending good all damages excluding the cost of masonry or concrete work, if necessary, but including the cost and fitting and fixing holder bat clamps (any floor) or for underground work including cutting trenches upto 1.5 metre and refilling the same complete as per direction of the Engineer in-charge. (Payment will be made on centre line measurement of the total pipeline including specials. Above ground 110 mm dia.
520
-
-
Labour for fitting and fixing U.P.V.C. pipes for above ground work
including cost of jointing materials etc. fitting and fixing all necessary specials, cutting pipes, cutting holes in walls or R.C. floor where necessary and mending good all damages excluding the cost of masonry or concrete work, if necessary, but including the cost and fitting and fixing holder bat clamps (any floor) or for underground work including cutting trenches upto 1.5 metre and refilling the same complete as per direction of the Engineer in-charge. (Payment will be made on centre line measurement of the total pipeline including specials. Above ground 75 mm dia
320
-
-
Supply of UPVC pipes (B Type) & fittings conforming to IS-13592-1992: 160 mm dia Bend 87.5º
4
-
-
Easing door and windows.
400
-
-
Rewashering stop cock/bib cock/push cock/pillar cock including gland packing if necessary (15mm).
200
-
-
Single Brick Flat Soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with local sand.
35
-
-
Taking out shutter of door and window, dismantling by parts (for repair or replacement of damaged parts) , reassembling and refitting and rehanging same with old fittings but with new screws as necessary.
15
-
-
Styles and rails of wooden shutters fitted and fixed complete. (Payment to be made on area of new work only).At all floor levels: (ii) 35mm Thick shutter: (b) Sishu, Gamar, Champ,Badam,Bhola, Mogra, Hallak.
8
-
-
Panel (made of single plank) of door and window shutters to design as directed:at all floor levels: (Payment to be made on area of exposed new work). (In case of non-supply of single plank penal rate of reduction to a maximum of 30% will be made): (ii) 19mm thick panel of 30cm to 45cm width: (b) Sishu, Gamar, Champ,Badam,Bhola, Mogra, Hallak.
8
-
-
Supplying, fitting and fixing boiling water proof ply conforming to IS: 710-1977 bonded with phenol formaldehyde synthetic resin conforming to IS: 848-1974 of approved make and brand fitted and fixed as per design as per approval and direction of Engineer-in-Charge: 4mm
15
-
-
Supplying, fitting and fixing boiling water proof ply conforming to IS: 710-1977 bonded with phenol formaldehyde synthetic resin conforming to IS: 848-1974 of approved make and brand fitted and fixed as per design as per approval and direction of Engineer-in-Charge: 6mm
15
-
-
Removing chokage of G.I., CPVC, H.C.I. or S.W. pipe of any dia ( Underground ) with split bamboo or any other suitable method as directed.
100
-
-
Cleaning silt of inspection pit.
12
-
-
ELECTRICAL PART
-
-
-
Laying of one number PVC insulated and PVC sheathed/XLPE power cable 1.1 KV grade of following size direct in ground, including excavation, sand cushioning, protective covering and refilling the trench etc. as required.
-
-
-
Up to 35 sqmm
1240
-
-
Above 35 sqmm and up to 95 sqmm
173
-
-
Laying of one number PVC insulated and PVC sheathed/XLPE power cable 1.1 KV grade of of following size in the existing massionary open duct. etc as required.
-
-
-
Above 185 sq.mm and up to 400 sq.mm
30
-
-
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
-
-
-
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
10
-
-
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
6
-
-
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
-
-
-
Up to 35 sqmm
110
-
-
Above 35 sqmm and up to 95 sqmm
51
-
-
Above 95 sqmm and up to 185 sqmm
14
-
-
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.
-
-
-
Above 35 sq. mm and upto 95 sq. mm
286
-
-
Above 95 sqmm and up to 185 sqmm
390
-
-
Supply & making end termination with brass compressor gland and aluminium lugs for following sizes of PVC insulated and PVC sheathed/XLPE aluminium conductor armoured cables 1.1KV grade as required.
-
-
-
3.5 X 300 sq mm (70mm).
4
-
-
3.5 X 185 sq mm (57mm).
13
-
-
3.5 X 150 sq mm (50mm).
3
-
-
3.5 X 70 sq mm (38mm).
6
-
-
3.5 X 50 sq mm (35mm).
11
-
-
4 X 16 sq mm (28mm).
44
-
-
3 X 10 sq mm (22mm).
54
-
-
Supplying and making indoor cable end ermination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:
-
-
-
120 sq. mm
1
-
-
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-
3.5 X 50 sq. mm
4
-
-
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
5
-
-
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
30
-
-
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe
of 2.7 metre long etc. with charcoal/ coke and salt as required.
1
-
-
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
7
-
-
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
5
-
-
Providing and making steel pole collar with cement concrete (1 cement : 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required,
curing etc as required. (volume of pole/ pipe not to be deducted)
3
-
-
Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required.
16
-
-
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling
etc. as required.
-
-
-
Above 4.5 metre and upto 6.5 metre
5
-
-
Dismantling of pole/ street light standard/ strut embedded in brick ballast foundation etc. as required.
5
-
-
Dismantling of over head lines comprising of copper/ aluminium over head conductor, G.I. wire, cross arms, insulators etc. as required.The dismentled old materials etc to be shifted and deposited to CMERI office store division by the firm.
420
-
-
Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required.
10
-
-
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet,suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group: C
30
-
-
Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connections, painting etc. as required
8
-
-
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
-
-
-
2 x 1.5 sq. mm.+ 1x 1.5 sq. mm earth wire
200
-
-
2 x 2.5 sq. mm.+ 1x 2.5 sq. mm earth wire
110
-
-
Supplying and fixing brass batten/ angle holder including connection etc. as required.
25
-
-
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
25
-
-
Painting with aluminium paint of approved brand and manufacture to give an even shade Two or more coats on new work .
126
-
-
Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
126
-
-
With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works
126
-
-
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer all complete.
50
-
-
Installation of exhaust fan with making suitable size opening, including making good the damage, connection, testing, commissioning etc. as required. Upto 450 mm sweep
6
-
-
Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes.
6
-
-
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required (LT Switch room).
1
-
-
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
2
-
-
Supply of 1.1 KV grade XLPE insulated, cores laid up, Thermoplastic tape inner sheathed, armoured and extruded PVC type ST2 outer sheathed Aluminium Conductor armoured power cables conforming to IS 7098 ( Part - 1) 2011 and ISI marked of following sizes
-
-
-
3.5 X 300 sq mm A2XWY/A2XFY cable.
30
-
-
3.5 X 185 sq mm A2XWY/A2XFY cable.
210
-
-
3.5 X 150 sq mm A2XWY/A2XFY cable.
200
-
-
3.5 X 70 sq mm A2XWY/A2XFY cable.
250
-
-
3.5 X 50 sq mm A2XWY/A2XFY cable.
270
-
-
4 X 16 sq mm A2XWY/A2XFY cable.
750
-
-
3 X 10 sq mm A2XWY/A2XFY cable.
600
-
-
Supply and drawing of 1.5 sq.mm 1.1 KV grade FR PVC insulated and PVC round sheathed three core (colour of cores are red, black & green) bright annealed bare copper conductor flexible cable conforming to IS 694:2010 and ISI marked.
300
-
-
Supply and Fixing of 47 watts,High performance street light luminaire having single die ceramic base high power LED light source, IP66 protection, PDC housing with finless design and polycarbonate cover (IK08). The luminaire family comes with dedicated street optics fixing dia 48-60 mm for fixing/mounting in existing pole/roof perapit wall, connection, testing, commissioning as required. (BRP056 LED47 CW SLF PSU S1 of Philips or equivalent.)
50
-
-
Supply and Fixing of Extruded aluminium batten available in 4ft run length with multiple lumen packages and suitable for surface, wall & conduit mounting, Clamp, nut bolts and all accessories for fixing wall mounting, connection, testing, commissioning etc as required BN021C LED22S PSU CW GR of Philips or equivalent.)
70
-
-
Supply and Fixing of Extruded aluminium batten available in 2ft run length with multiple lumen packages and suitable for surface, wall & conduit mounting, Clamp, nut bolts and all accessories for fixing wall mounting, connection, testing, commissioning etc as required BN 021 LED12S 6500 PSU GR of Philips or equivalent.)
94
-
-
Supplying and fixing of LED Bulk head with IP 65 protection & IK08 impact resistance suitable for surface and wall mounting applications light fittings complete with connections, testing and commissioning etc. as required. (WT140W LED7S CW PSU s1 PC of Philips or equivalent.)
6
-
-
Supply of 1phase, 300mm Sweep, Heavy Duty Exhaust Fan with nut-bolt as required. (Orient or equivalent.)
6
-
-
Supply and fixing of 1200 mm sweep, 230 Volt, Metallic Ivory colour, full copper motor and aluminium blades Ceiling mounted fan with suitable suspension rod, nut-bolt, with connection alongwith 3x1.5 sq.mm FRLS PVC insulated copper conductor single core wire, testing, commissioning etc as required. job inclusive of dismentling of unserviceable ceiling fan. (GRATIA of Orient or equivalent.)
14
-
-
Supplying and fixing of FP sheet steel enclosure with 63A, four pole, 415 V, MCB (10 kA, "C" curve) complete with connections, testing and commissioning etc. as required.
5
-
-
Supply and fabrication of Light Pole made with 80 mm dia 6 Mtr. Long G.I Pipe (M) ISI make and necessary provision of accessories complete with top cover and 200x200mm MS base plate, earthing system, necessary hole for connection and painting etc. as required.
5
-
-
Supply and fixing of henged cover MS looping box,1.5 meter above the ground level of the existing street light pole, box made by 16 SWG MS Sheet of size 200mm X 250mm X 100mm deep, including painting with 1No. 6 Amp. rating, 240 V, 10 kA, "C" curve, SP MCB and 63 Amp. 4 pole insulated looping Terminal connector and one earthing point etc. as required.
54
-
-
Supply and fixing of DPX3 - 250, MCCB 25 kA, 250A Thermal magnetic releases four pole MCCB with rotary type handle, speeder link for termination both side alongwith supply & fixing DPX3 MCCB enclosures to be in the existing panel. including connections from busbar with suitable size cu cable, testing and commissioning etc. as required. The Job inclusive of dismentling of unserviceable SFU. (Legrand Model - 4202 19 (MCCB) and 507802 (enclosure)/eqv. )
4
-
-
Supply and fixing of Four pole 100 Amps, 415V AC, 50 Hz in sheet steel enclosure, Onload Changeover Switch I-0-II. With both side cable end box, in the existing MS frame/wall. including connections, testing and commissioning etc. as required. Model IHCNFE0100 of Havells
.
1
-
-
Servicing and repairing of Old TPGO Isolator in the existing over head H pole.11 KV , 400 Amp. Outdoor type Switching Unit with Vertically mounted manually gang operated Air Break Isolator, alongwith Supply and fixing of suitable size GI Operating pipe with handle, in the existing H pole, including replacement of damage required parts, electrical connection , testing and commissioning etc. as required. The job inclusive of replacement of transformer oil (Transformer oil suppled by CMERI) in the HT oil fuse unit (VLE type). .
1
-
-
Supply and fixing of energy-efficiency and long-lifetime, and high power factor. TForce Core 27W/3000lm E27 LED Lamps for replacing existing old HPI/SON/HPL Lamps as required.
12
-
-
Making metalic Road boaring by jack push method including supply of following dia G.I. pipe (medium class) with underground cables (75 cm deep) etc as required
-
-
-
100 mm dia
4
-
-
80 mm dia
26
-
-
Supply Installation Testing and commissioning of compartmentalised cubicle Panel as per CPWD Electrical spefication front operated outdoor cubical type MV Feeder panel of suitable size, Minium depth 300 mm(D) suitable for operation on 440V, three phase, 4 wire, 50 HZ, AC supply system. The panel shall be fabricated by 14 SWG CRCA sheet steel with necessary anti-corrosive tretment and shall be dust and vermin proof construction along with body earthing, suitable for installation on Brick/concrete foundation (Minimum Height - 300 mm from ground level) with the following facilities for - MF1.(Near SA C&D block). a) Fire and corrosion resistant coating similar to VIPER FR-1101 applied in two coats with necessary primer.b) Fire retardant DMC/SMC fillings for openings around bus bar near the sectional barriers. c) Facilities for terminals must be insulated Bus connected or suitable Ampere rated control power cabler with speeder link termination system for MCCBs. d) Shall have high mechanical and dielectric e) Double Door with locking facility including rotary type handle . strength. f) Shall have fire barriers.g) Switch body shall be made of fire retardant materials/heat insulating materials. h) Shall be painted with heavy coat of anti corrosive paint. I) FP MCCBs shall not be fixed in more than 3 Nos. in each compartment. j) Panel name as well as Feeder name along with Denger Plate to be setup.k) Provition of Top and Bottom cable entry hole. The panel shall consisting of the followings. Incoming: DPX3 - 250, MCCB 25 kA, 250A Thermal magnetic releases four pole MCCB with rotary type handle and speeder link for termination both side. -1Set. (DPX3 250 of Legrand Model - 4202 19 / eqv. ) Bus Bar: 300A TPN Aluminium Bus bar (insulated).-1Set. Outgoing: A) DPX3 - 160, MCCB 16 kA, 125A Thermal magnetic releases four pole MCCB with rotary type handle and speeder Link for termination both side.- 4 Set. (DPX3 - 160, 4200 16 of Legrand / eqv.), Metering: 3 ph 4 wire (0-500V) Digital Voltmeter with Phase selector switch- 1set. (0-250A) Digital Ammeter with CTs and Phase selector switch- 1set. Phase indication LED lamps with fuse and control -3 Nos,as required. All are to be fitted inside the pannel.Make- AE/L&T/Legrand/ eqv. Bus Bar: 300A TPN Aluminium Bus bar (insulated).-1Set.
1
-
-
Supply Installation Testing and commissioning of compartmentalised cubicle Panel as per CPWD Electrical spefication front operated outdoor cubical type MV Feeder panel of suitable size, Minium depth 300 mm(D), suitable for operation on 440V, three phase, 4wire, 50 HZ, AC supply system. The panel shall be fabricated by 14 SWG CRCA sheet steel with necessary anti-corrosive tretment and shall be dust and vermin proof construction along with body earthing, suitable for installation on Brick/concrete foundation (Minimum Height - 300 mm from ground level) with the following facilities for - MF2.(Near AII&BII block). and MF-3 near SA A block. a) Fire and corrosion resistant coating similar to VIPER FR-1101 applied in two coats with necessary primer. b) Fire retardant DMC/SMC fillings for openings around bus bar near the sectional barriers. c) Facilities for terminals must be insulated Bus connected or suitable Ampere rated control power cabler with speeder link termination system for MCCBs. d) Shall have high mechanical and dielectric strength. e) Double Door with locking facility including rotary type handle . f) Shall have fire barriers. g) Switch body shall be made of fire retardant materials/heat insulating materials. h) Shall be painted with heavy coat of anti corrosive paint.I) FP MCCBs shall not be fixed in more than 1Nos. in each compartment. j) Panel name as well as Feeder name along with Denger Plate to be setup. k) Provition of Top and Bottom cable entry hole. The panel shall consisting of the followings. Incoming: DPX3 - 250, MCCB 25 kA, 250A Thermal magnetic releases four pole MCCB with rotary type handle and speeder link for termination both side. -1Set. (DPX3 250 of Legrand Model - 4202 19 / eqv. ) Outgoing: A) DPX3 - 160, MCCB 16 kA, 125A Thermal magnetic releases four pole MCCB with rotary type handle with speeder Link for termination both side - 5 set. (DPX3, 160- 4200 16 of Legrand / eqv.), Metering: 3 ph 4 wire (0-500V) Digital Voltmeter with Phase selector switch- 1set. (0-250A) Digital Ammeter with CTs and Phase selector switch- 1set. Phase indication LED lamps with fuse and control -3 Nos,as required. All are to be fitted inside the pannel.Make- AE/L&T/Legrand/ eqv.
2
-
-
Repair, installation, testing and commissioning of existing 500 KVA,11000/415 Volts, 3 phase, 50Hz, Delta/Star, Vector group- DYN-11, indoor mounting, oil cooled, ONAN, Transformer, Make A.P.E.E.C, Sl no- V 666/87. With supply and fixing of new 1) Copper wire for winding material HV (S.E./D.P.C) & LV copper strips (T.P.C/D.P.C). 2) OFF Load Tap Changer (Ratio switch with handle) suitable for incomming voltage variation of +5% to -5% in equal step of 2.5% to give a constant Secondary voltage. 3) Oil seal for HV & LV bushing. 4) Silica gel breather with container, 5) MS Channel for fixing of core as required, 6) insulating material , 7) ampere tape sleeve rings, 8) Gasket sheet (8mm). 9) Transformer oil EHV Grade as required.10) Nut bolts washer fittings and all accessories as required for full functioning. Transformer will be supplied with filling of transformer oil as per IS 335/1983. All routine test as per IS 2026 shall be conducted free of cost. All TC & GC for transformer must be submitted.( Job inclusive of dismentling, loading, un loading and transportation etc as required).
1
-
-
Providing and fixing of ABC Stored pressureType Fire Extinguisher of 4 kg capacity consist of wielded cylinder, squeeze lever discharge valve fitted with pressure indicating gauge withinternal discharge tube, discharge nozzle, suspension bracket,confirming to IS 13849 duly charged with ISI Marked Mono Ammonium phospate base powder confirming to IS 14609 and pressurised with Nitrogen Gas and with Wall Mount Hook. Make CEASE FIRE. For Sub station transformer room & LT Panel room at CSIR-CMERI new colony, durgapur.
3
-
-
Providing insulated Electrical Matting Class 2-PV Tested Upto 20 KV, 2.6mm thickness, 1mtr X1 mtr Color Black/Grey with Fabric print as per IEC 61111
2
-
-
Supply and Fixing of 200 watts, LED integral flood light with driver inside a PDC houing energy efficient light fittings complete to ensure uniform distribution area lighting including all accessories for fixing/mounting on pole/roof perapit wall, connection, testing, commissioning as required. (BVP184 LED215 CW FG SYWB 200W PSU/ BVP184 LED196 CW FG WB 200W PSU of Philips or equivalent.)
8
-
-
Supply and fixing of DPX3 - 160, MCCB 16 kA, 100A Thermal magnetic releases four pole MCCB with rotary type handle, speeder link for termination both side alongwith supply & fixing of DPX3 MCCB enclosures to be fix in the wall. including connections from busbar with suitable size cu cable, testing and commissioning etc. as required. The Job inclusive of dismentling of unserviceable SFU. (Legrand Model - 4200 15 (MCCB) and 507801 (enclosure)/eqv. )
1
-
-
Evaluation Notes How It Works ?
Potential Partner