Overhauling And Repairing, Painting Of Power T/f
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_UPCL9_51844_1Bid Award Id
ViewTender No
EDC(H)/47/2022-23Tender Authority
Uttarakhand Power Corporation Limited ViewPurchaser Address
-Website
http://https://www.upcl.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
oil temperature indicator (OTI) with 3 meter capilary and atleast +-5% Accuracy of Meter.
8
-
-
... More
winding temperature indicator (WTI) with 3 meter capilary and atleast +-5% Accuracy of Meter.
32
-
-
... More
11 KV Bushing & Bushing rod.
32
-
-
... More
LV Site 'L' Contactor
200
-
-
... More
33 KV Bushing & Bushing rod.
20
-
-
... More
ACE CHEMROD (GI) size outer dia 48mm legth 2000 mm or higher with 25 Kg (Minimum) Highly Conductive Substances for Soil Treatment
384
-
-
... More
G.I. Strip 40x5 Sq. mm
100
-
-
... More
Flexible XLPE GI/Al wire 16 Sqmm.
50
-
-
... More
GI Crimping lug 16 Sqmm.
5
-
-
... More
Labour Charge
-
-
-
... More
(a) Dismentling of all accessories of T/F from top plate including disconnection of HT/LT side cable, bushing connections etc. Taking out of top plate and disconnection of bushings, bushing rod & taking out of the same from T/F. (b) Re-assemble of all dismantiling part, bushing rod its connection after tightening of all nuts and bolts, top plate will be related with all accessories and property fitting on its location. (c) Replacement of Neoprene rubber gaskets of top plates, coilling fins. Buchholz relay, conservator tanks etc. for prevention of oil leakage.
8
-
-
... More
Centrifuging of T/F oil including draining out of old T/F oil & Top up after recleaning & centrifuging of oil with proper BD value of 8 MVA T/F (Approx oil capacity 3600 litre in each in each T/F) & for 5 MVA T/F (Approx oil capacity 2805 litre)
40040
-
-
... More
Fixing & Commisioning of 11 KV Bushing & Bushing rod.
28
-
-
... More
Fixing & Commisioning of 33 KV Bushing & Bushing rod.
23
-
-
... More
Painting of T/F after clearing and removel of grease/oil, oil paint from surface of T/F with 1 coat of primer & 2 coats of first grade gray enamel paint.
8
-
-
... More
Installation and commissioning of oil temperature indicator (OTI) with 3 meter capilary and atleast +-5% Accuracy of Meter including complete wiring & Connections to the control panel.
8
-
-
... More
Installation and commissioning of winding temperature indicator (WTI) with 3 meter capilary and atleast +-5% Accuracy of Meter including complete wiring & Connections to the control panel.
8
-
-
... More
Cleaning of Carbonized contact and minor repairing of Buchholz Relay
8
-
-
... More
Painting of Structure in yard after cleaning and removal of old paint from in with 1 coat of primer and 2 coats of silver paint. With Yard + Fancing
8
-
-
... More
Fixing of LV Site 'L' Contactor
6
-
-
... More
Laying of Control cable in trench from CT,PT,WTI,OTI,Bhuchholz,Breakers etc.to control panel and making all connections.
1200
-
-
... More
Repairing and overhauling of 33 KV Isolator in Switchyard at 33 /11 KV
20
-
-
... More
Complete Vagitation Clearence On Switchyard Including Wire mesh fencing.
4
-
-
... More
Fixing of WTI,OTI and Buccholz Indicator Board.
8
-
-
... More
Digging the pit of size approx 2100 mm depth & 150 mm dia. or higher by drilling, place ACE Chemrod Earthing Electrode . Connecting the Earthing Electrode with VCB Panels with G.I. Strip/ Wire. While making the joint, The surface should be cleaned thoroughly by wire brush, regmal etc. If digging of pit is not practically possible than the above process may be done by horizontally but electrode will be placed a depth not less than 1.25 Mtr from the surface of ground.
256
-
-
... More
Installation of G.I.Strip size 40x5 mm / flexible GI/Al wire 16 Sq mm
6000
-
-
... More
Painting of Wire Mesh Fencing i/c Cost of Paint.
6
-
-