Uttarakhand Jal Vidyut Nigam Limited Tender
View complete overview of Uttarakhand UJVN Tender
Uttarakhand Jal Vidyut Nigam Limited - UJVN Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date30 Sep 2024
Closing Date21 Oct 2024
Tender Amount₹ 3,58,91,700
Costs
EMD
₹ 7,18,000Document Cost
₹ 17,700Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_UJVN_76435_1Bid Award Id
ViewTender No
08/UJVNL/EE (MG)/KPS/2024-25Tender Authority
Uttarakhand Jal Vidyut Nigam Limited ViewPurchaser Address
-Website
http://uktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Post –Dismantling Inspection, Testing , Measurement and Analysis
1
-
-
... More
Repair of Runner Blades
1
-
-
... More
Repair of Guide Vane
1
-
-
... More
Repair, re-babitting, DP test and Ultrasonic test of GGB, TGB and Thrust Bearing Pads
1
-
-
... More
Repair of Guide Vane Bearing body assemblies
1
-
-
... More
Repair of Runner Hub
1
-
-
... More
Repairing of Runner cone
1
-
-
... More
Repair of Runner Chamber
1
-
-
... More
Repair of Top Cover
1
-
-
... More
Repair of Guide Vanes Servo Motor
1
-
-
... More
Repair of Regulating Ring
1
-
-
... More
Repair of Governing System & OPU system
1
-
-
... More
Compatible OPU pump motor starter control panel as specified above suitable for following HP of motor 40 HP motor panel.(as per technical specification)
1
-
-
... More
Repairing and overhauling electronic solonide valve(ESV)
1
-
-
... More
Repairing of Upper bracket and turbine pit cover
1
-
-
... More
Repairing and overhauling of oil header
1
-
-
... More
Repairing of clean water system(stainers)
1
-
-
... More
Repairing of Penstock drain valve and Draft tube drain valve
1
-
-
... More
Automation of pre-installed weda pump
1
-
-
... More
Repair of Turbine Shaft assembly
1
-
-
... More
Repair of Pivot Ring
1
-
-
... More
Pressure grouting of draft tube
1
-
-
... More
Overhauling of Generator Stator, Pilot stator, Main Excitor Assembly
1
-
-
... More
Providing and replacement Complete wedges in for Slot 100 No
1
-
-
... More
Fixing of New Carbon Brushes Grade EGOR
84
-
-
... More
ELCID testing, Wedge Deflection Tests after replacement of new wedges
1
-
-
... More
a) Over Voltage Test
1
-
-
... More
b) DC High Voltage Test
1
-
-
... More
c) AC High Voltage Test
1
-
-
... More
d) Partial Discharge Test
1
-
-
... More
e) Tan Delta and Tan Delta Tip Up
1
-
-
... More
f) Capacitance and Capacitance increment
1
-
-
... More
g) Partial Discharge Test inception voltage
1
-
-
... More
Rewinding of PMG rotor pole -32 No.
1
-
-
... More
ITC (Installation Testing and comissioning) of braking& jacking system panel with all accessories
1
-
-
... More
ITC (Installation Testing and comissioning) NGT transformer rating: 6.6kV/110 V ,20 kVA, register- 0.289 ohm & rated current continuous 220 Amp
1
-
-
... More
Dismantling, cleaning, repairing & reassembly of Generator Stator Water Coolers (08 NO)
1
-
-
... More
Retubing of Generator Water Cooler all 84 copper tubes.
2
-
-
... More
Lagging over cooling pipe line by Class O, Nitride Insulation Closed Cell Sheet, thickness min. 15 mm.
1
-
-
... More
Making of Rotor Pole joint and also replace the copper strip connection in all thrre machine A,B &C
5
-
-
... More
Fixing of multistrand DC copper cable 150 sq mm
1
-
-
... More
Fixing of 100 mm LCD frequency display unit.
1
-
-
... More
Fxing of 100 mm LCD RPM display unit
1
-
-
... More
Fixing of 6.6 kV Post Insulator
1
-
-
... More
Fixing of 11 kV post insulator for bus bar support in Generator & GT side cubical.
24
-
-
... More
Laying of Single core 500 sq mm,6.6 kV power cable from Gen Duct to T/F duct (07 Nos ,200 m each) and fixing the end joint kit and associated work.
1
-
-
... More
Shiting the old power cable after rolling on drum from Cable Gallery to Center Store (07 Nos ,200 m each)
1
-
-
... More
Fixing of diffused LED panel light & strip LED light for lower bracket area.
1
-
-
... More
Copper Plate Earting 600x600x6 mm with 50x5 mm copper strip termination for Gen Transformer
1
-
-
... More
Dismantling of old LA assembly and fixing of new Lightening Arrestor assembly with surge monitor 120 kVA class 3 zinc oxide -03 nos
1
-
-
... More
Overhauling of Stator Air Cooler Cast Steel glove valve: 150 mm
2
-
-
... More
Overhauling of Stator Air Cooler Cast Steel glove valve 100 mm
4
-
-
... More
Overhauling of Stator Air Cooler Cast Steel glove valve 50 mm
16
-
-
... More
Overhauling of AVR (Automatic Voltage Regulator) System along with reheostat
1
-
-
... More
Replacement of Instruments: RTD- Pt-100 with calibration
30
-
-
... More
TSD-150 mm dial , 15 mtr length with calibration
14
-
-
... More
Fixing of Lightning Arrestor 6.6 kV for Generator
1
-
-
... More
Filtration of UAT, Station Ist & IInd and Generator Transformer Oil
1
-
-
... More
Dissolved Gas Analysis (DGA) & Furan test, BDV and Water content of Gen Transformer Oil and UAT, Station Ist & IInd
1
-
-
... More
Painting of UAT, Station Ist & IInd and Generator Transformer
1
-
-
... More
Repairing & Overhauling of Circuit breaker Control Panel
1
-
-
... More
Painting of all metallic parts
1
-
-
... More
Reassembly, Alignment, Leveling & Re-commissioning of the Unit
1
-
-
... More
Testing, Commissioning, Dry Out and Synchronization
1
-
-
... More
Dynamic balancing and vibration testing of machine Vibration testing of machine
1
-
-
... More
Supply of self lubricated bushes upper side for TGB (Make- Throdon)
24
-
-
... More
Supply of self lubricated bushes middle side(Make- Throdon)
24
-
-
... More
Supply of self lubricated bushes bottom side(Make- Throdon)
24
-
-
... More
Supply of self lubricated bushes guide vane linkage(Make- Throdon)
48
-
-
... More
Supply of runner hub MS locking plate and SS cover plate
16
-
-
... More
Supply of SS HT stud with nut of size is M-27 X 90mm ( as per sample)
192
-
-
... More
Supply of Servo motor limit switch (as per sample)
2
-
-
... More
Supply of Brass side-08 nos and bottom pad -08 nos
16
-
-
... More
Supply of Piano wire with attachment
2
-
-
... More
Supply of feed- back mechanism steel wire rope dia -8 mm
1
-
-
... More
Supply of electronic solonide valve(ESV) for 115% over speed tripping( as per sample)
1
-
-
... More
Supply of OPU pump( as per sample)
1
-
-
... More
Supply of NRV for OPU pump (as per sample)
2
-
-
... More
Supply of Governor Limit switch(as per sample)
4
-
-
... More
Supply of OPU NRV limit switch
2
-
-
... More
Supply of CI glow- valve-50mm, (high pressure, 40 kg testing) (as per sample)
2
-
-
... More
Supply of CI glow- valve-25mm, (high pressure, 40 kg testing)
1
-
-
... More
Supply of NRV cup seal/gland seal, make – Neoprene(as per sample)
1
-
-
... More
Supply of ‘O’ Ring and gas kits (as per sample)
1
-
-
... More
Supply of Heavy duty Filter (as per sample)
2
-
-
... More
Supply and fixing Glass/ Acrylic Tubes for oil level indicator/gauge technical scale with limit switch of OPU(as per sample)
1
-
-
... More
Supply of digital techo meter/speed meter 10 mm x 100 mm size, range 0-200 %
2
-
-
... More
Supply of CI globe valve dia 100 mm rising spindle
1
-
-
... More
Supply of GM bushes for oil header
3
-
-
... More
Supply of MS Bucket with wire mesh complete
24
-
-
... More
Supply of CI Gate valve rising spindle 80 mm
1
-
-
... More
Supply of GM vertical NRV dia- 50 mm
4
-
-
... More
Supply of Neoprene air seal for TGB
1
-
-
... More
Supply of Neoprene gland seal for TGB
4
-
-
... More
Supply of New Carbon Brushes Grade EGOR
84
-
-
... More
Supply of braking& jacking double acting system panel with all accessories
1
-
-
... More
Supply NGT transformer rating : 6.6kV/110 V ,20 kVA, register- 0.289 ohm & rated current continuous 220 Amp
1
-
-
... More
Supply of FCB contact coil as per sample
1
-
-
... More
Supply of multistrand DC copper cable 150 sq mm
100
-
-
... More
Supply of 100 mm LCD frequency display unit.
1
-
-
... More
Supply of 100 mm LCD RPM display unit
1
-
-
... More
Supply of 6.6 kv Post Insulator as per sample
24
-
-
... More
Supply of 11 kV post insulator for bus bar support in Generator & GT side cubical.
24
-
-
... More
Supply of Cable clamp complete suitable for 500 sq mm single core cable as per sample
50
-
-
... More
Supply of Heat shrinkable Indoor termination kit for Single core cable ,500 sq mm, 11kV(E)
14
-
-
... More
Supply of diffused LED panel light & strip LED light for lower bracket area.
1
-
-
... More
Providing of Lightning Arrestor 6.6 kV for Generator
6
-
-
... More
Supply of Lightening Arrestor assembly with surge monitor 120 kVA class 3 zinc oxide
3
-
-
... More
Supply of Cup seal (LV bushing) as per sample
20
-
-
... More
Supply of HV Bushing 132 kV
2
-
-
... More
Supply of LV bushing 6.6 kV
2
-
-
... More
Supply of OTI and WTI
2
-
-
... More
Supply of Generator Transformer Inlet Outlet valve as per sample
2
-
-
... More
Field Testing & Maintenance of unit protection Relay Panel (Numerical Relays generator & transformer protection.)(as per scope of work)
1
-
-
... More
Generator Testing (as per scope of work)
1
-
-
... More
Intake gate control panel field testing.(as per scope of work)
1
-
-
... More
Generator Transformer testing (as per scope of work)
1
-
-
... More
UAT Testing (as per scope of work)
1
-
-
... More
Earth resistance testing(as per scope of work)
1
-
-
... More
Unit circuit Breaker testing (as per scope of work)
1
-
-
... More
LBB testing(as per scope of work)
1
-
-
... More
Governor testing speed 115%,165% and gate testing
1
-
-
... More
DC earth fault testing (as per scope of work)
1
-
-