Pey Jal Nigam Uttarakhand Tender
View complete overview of Uttarakhand Pey Jal Nigam Uttarakhand Tender
Pey Jal Nigam Uttarakhand Tender
Civil And Construction
Civil Works Others
Eprocure
Opening Date23 Feb 2024
Closing DateCancelled
Tender Amount₹ 7,52,46,000
Costs
EMD
₹ 15,04,000Document Cost
₹ 11,800Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MDPEY_70188_1Tender No
832/Nivida(Garh) (Elect) D.Dun/04 Dt. 20/02/2024Tender Authority
Pey Jal Nigam Uttarakhand ViewPurchaser Address
-Website
http://http://peyjal.uk.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
P/L cement concrete excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size)
5.8
-
-
P/L reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
5.8
-
-
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete
41.31
-
-
Reinforcement for R.C.C. Work Using T.M.T. Bars
0.68
-
-
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position all complete.
1476
-
-
G.I. chain link fabric fencing with G.I. wire of dia 4 mm
188
-
-
12mm thick C.P. in C.M. 1 : 6 ( 1 cement : 6 fine sand )
11.09
-
-
Applying priming coat on steel work.
62.2
-
-
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade
11.09
-
-
Painting Steel work with Deluxe Multi Surface Paint to give an even shade.
62.2
-
-
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
-
-
-
Upto 35 sq. mm
900
-
-
Above 95 sq. mm and upto 185 sq. mm
500
-
-
Above 185 sq. mm and upto 400 sq. mm
800
-
-
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
-
-
-
3½ x 185 Sq.mm. (57mm).
20
-
-
3½ x 400 Sq.mm. (70mm).
10
-
-
4X 25 Sq. mm. (28 mm) (For pumps etc)
50
-
-
4X 35 sqmm (32 mm) (For pumps etc)
20
-
-
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
16
-
-
Supplying and laying 25 mm X 5 mm G.I earhting strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
640
-
-
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
6
-
-
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
380
-
-
(DG SET) 1 Nos. 625KVA
-
-
-
Providing, Installing, Testing and Commissioning of'Silent Type' Diesel Generating set having Prime Power Rating of 625 KVA, 415 volts, 50 Hz at 1500 RPM, 0.8 lagging power factor , three phase system & for 0.85 Load Factor with standard control panel andcopper control cable from DG to AMF Panel and consisting of the followings: a) Diesel Engine: Diesel engine 4 Stroke Water Cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50%RH & at 1000 Meter MSL and conforming to BS 5514,BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories.
-
-
-
b) Engine mounted Instrument Panel fitted with and having digital display for following:
i) Start-stop switch with key
ii) Water temperature indication
iii) Lubrication oil pressure indication
iv) Battery charging indication
v) RPM indication
vi) Over speed indication
vii) Low lub. Oil trip indication
viii) Engine Hours indication
-
-
-
c) Alternator:
Synchronous alternator rated at 500 KVA, 415 volts at 1500 RPM, three phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C,50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with c1ass-F/H insulation.
-
-
-
d) Base Frame & Foundation:
Both the engine and alternator shall be mounted on suitable base frame made of M.S Channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
-
-
-
acoustic enclosure with self contained hoses and other allied accessories as per specifications or as per OEM/OEA along with one number extra having suitable capacity as required .Extra Minimum 2000 Liters suitable for 12 hours continuous operation fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS . class 'C' pipes of suitable dia.
Complete with valves, level indications & accessories recommendation,
-
-
-
f) Exhaust System:
Residential exhaust silencer .
-
-
-
g) Starting System:
24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 180 AH Maintenance free battery as required or as per OEM/OEA .
-
-
-
h) Acoustic and weather proof enclosure with
arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per CPWD specification and norms of CPCB-II sound proofing done with help of high quality rock wool is further covered with fiberglass sheet and perforated powder coated sheet or as per OEM Standard design
-
-
-
(DG SET) 1 Nos. 625 KVA
1
-
-
Supplying and fixing additional exhaust gas piping of 250 mm Welded black MS, C class pipe conforming to IS : 3589 cut to required lengths and installed with necessary bends and clamps, anti- vibration mountings, insulation of exhaust system with Rockwool, 50 mm thick wire mesh & aluminum cladding, below etc., as required as per specifications.(The item shall be measured on linear basis per each run of exhaust piping from outlet of silencer to end of exhaust piping)
6
-
-
Main Essential Panel for Swimming Pool (Indoor Type)
-
-
-
Incoming 1 :- 1 Nos.(1No. from DG Set of 625KVA)
-
-
-
1000Amps. each four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS
: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for each ACB with accessories - 1 Nos.
-
-
-
Outgoing ACB feeders consisting of
-
-
-
1No. Multifunction meter Neptune/ Equl with RS 485 communication port for
communication with required set of CT's.
-
-
-
1 Set. Phase indicating lamps suitable for 230 V AC fittings with back up hrc
fuse/MCB.
-
-
-
1Set. Breaker ON/OFF/TRIP/'Spring Charged', indicating lamps.
-
-
-
1No. T-N-C breaker control switch . (Trip/Neutral/Close)
-
-
-
Bus Coupler (1) :- 1 Nos.
-
-
-
1No. 1000A. four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947- 2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Busbar connection on incoming and outgoing side, complete with following accessories for ACB -
-
-
-
Motor wound spring closing mechanism - 1 No.
-
-
-
1 Set. of Breaker ON/OFF/'Spring Charged', indicating lamps.
-
-
-
1Nos. T-N-C breaker control switch . (Trip/Neutral/Close)
-
-
-
1Nos. One auto/manual selector switch
-
-
-
Control MCB 2A
-
-
-
Incoming 2 :- 1 Nos.(from DG Set of 500KVA)
-
-
-
800Amps. each four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for each ACB with accessories - 1 Nos.
-
-
-
Motor wound spring closing mechanism - 1No.
-
-
-
1No. Multifunction meter Neptune/ Equl with RS 485 communication port for communication with required set of CT's.
-
-
-
1 Set. of phase indicating lamps, Breaker ON/OFF/'Spring Charged', indicating lamps.
-
-
-
1No. T-N-C breaker control switch . (Trip/Neutral/Close)
-
-
-
1No. One auto/manual selector switch
-
-
-
Control MCB 2A
-
-
-
Bus Coupler (2) :- 1 Nos.
-
-
-
1No. 1600Amps. four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947- 2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Busbar connection on incoming and outgoing side, complete with following accessories for ACB -
-
-
-
Motor wound spring closing mechanism - 1 No.
-
-
-
1 Set. of Breaker ON/OFF/'Spring Charged', indicating lamps.
-
-
-
1Nos. T-N-C breaker control switch . (Trip/Neutral/Close)
-
-
-
1Nos. One auto/manual selector switch
-
-
-
Control MCB 2A
-
-
-
Incoming 3 :- 1 Nos. (from Future 1000KVA Transformer)
-
-
-
1600Amps. each four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for each ACB with accessories - 1 Nos.
-
-
-
Motor wound spring closing mechanism - 1Nos.
-
-
-
Microprocessor release PR122 (EMI & EMC Certified) for over current, earth fault &
short circuit protection - 1Nos.
-
-
-
1Nos. Multifunction meter Neptune-M9 Plus / Equl of EM6400 with RS 485
communication port for communication with required set of CT's.
-
-
-
1Nos. Phase indicating lamps suitable for 230 V AC fittings with back up hrc
fuse/MCB
-
-
-
1Nos. Breaker ON/OFF/TRIP/'Spring Charged', indicating lamps
-
-
-
1Nos. T-N-C breaker control switch . (Trip/Neutral/Close)
-
-
-
1Nos. auto/manual selector switch
-
-
-
1Nos. Undervoltage, Overvoltage for persisted voltage of 105-180% & 20- 95% of
rated voltage.
-
-
-
Bus Bars
-
-
-
1600/1000Amps FP Aluminium bus bars shall be colour coded and insulated by
heat shrinkable sleaves & clip on shrouds for joints.
-
-
-
Necessory Interlocking arrangement with PLC having Auto Load Management and Auto Mains Failure Feature shall be provided by the Panel Manufacturer.
-
-
-
Outgoing
-
-
-
1000Amps. FP EDO with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, MDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for Busbar connection on incoming and cable termination of outgoing side, complete with following for each ACB with accessories - 1 Nos. (For Competition Pool Panel)
-
-
-
800Amps. FP EDO with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, MDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for Busbar connection on incoming and cable termination of outgoing side, complete with following for each ACB with accessories - 1 Nos. (For Diving Pool Panel)
-
-
-
2 Nos. 250 amp 4P MCCB with Thermal Magnetic based release for O/C & S/C Release, Breaking Capacity 36KA, Ics=100%Icu. (1 Nos. for Practice pool Panel & 1 Nos. Spare)
-
-
-
Outgoing MCCB feeders consisting of
-
-
-
4Nos. Breaker ON/OFF, indicating lamps.
-
-
-
Main Essential Panel for Swimming Pool (Indoor Type) , as described
above
1
-
-
Competition Pool Panel (Indoor Type)
-
-
-
Incoming 1 :- 1 Nos.
-
-
-
1000Amps. four pole with 100% neutral horizontal drawout type air circuit breaker
of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V
), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS
: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for ACB with accessories - 1 Nos.
-
-
-
1No. Multifunction meter Neptune/ Equl with RS 485 communication port for
communication with required set of CT's.
-
-
-
1 Set. Phase indicating lamps suitable for 230 V AC fittings with back up hrc
fuse/MCB.
-
-
-
1Set. Breaker ON/OFF/TRIP/'Spring Charged', indicating lamps.
-
-
-
1No. T-N-C breaker control switch . (Trip/Neutral/Close)
-
-
-
Bus Bars
-
-
-
1250Amps TPN Aluminium bus bars shall be colour coded and insulated by heat
shrinkable sleaves & clip on shrouds for joints.
-
-
-
9 Nos. 160 amp 4P MCCB with Thermal Magnetic based release for O/C & S/C Release, Breaking Capacity 36KA, Ics=100%Icu. (7 Nos. 46.3KWPumps + 2 Nos.Spare)
-
-
-
9 Set Breaker ON/OFF, indicating lamps for each Outgoing.
1
-
-
Supplying of one No. XLPE insulated, PVC Sheathed, armoured aluminium conductor power cable of 1.1KV grade of following size in the ground
-
-
-
3½ x 185 Sq. mm.(For Panels)
600
-
-
3½ x 400 Sq.mm.(For DG Set, transformer and panels)
900
-
-
4X 25 Sq. mm./ 4X 35 sqmm (For pumps etc)
1000
-
-
For Competetion Pool - Water Volume 2700 m3
-
-
-
Supply, Installation, Testing and Commissioning of Outdoor Heat Exchange Pump Unit for heating and cooling swimming pool from an outdoor air temprature upto -7°C . Extremly Silent, made in metal with Titanium Heat Excahngers, Flowswitch, Defrost by Cycle Inversion (4 Way Valve), Water PumpControl and Electronic controller with LCD panel. Output 210 kW, Input - 46.3 kW.with 4 Nos of Rotary compressors
, Vertical exhaust fan direction . Input/ Output water connections of 110mm dia PVC Type with water flow of 40m3/hour/50m3/hour Maximum capacity of pool temprature shall be 32°C, Optimised as per standard
7
-
-
Plumbing for Complete System
-
-
-
Supply, Laying and Fixing of PVC U type Pipes with their respective fittings i.e. elbow , tee, sockets etc of various sizes. All includes. Suction Water Pressure Header - 2 Nos. Delivery Water Pressure Heder - 2 Nos. Bypass Pipelines from Main Delivery Line to Suction Pressure Header of suitable sizes Pipe from Suction Pressure Header to Each Heat pumps of suitable sizes -7 Nos Pipes from Heat pump to Delivery Pressure Header of suitable sizes - 7 Nos Bypass Pipelines from Delivery Pressure Header to Main Delivery Line to Pool. All Including high pressure Flow Control Valves , Flanges, Butteryfly Valves etc complete as required.
1
-
-