North Eastern Railway Tender

View complete overview of Uttarakhand NER Tender

North Eastern Railway - NER Tender

Works
Electrical and Electronics
Electrical Works
Ireps
+3Udham Singh Nagar, UttarakhandKasganj, Uttar PradeshBareilly, Uttar Pradesh
Opening Date2 Dec 2024
Closing Date30 Dec 2024
Tender Amount₹ 45,39,957.56 
Notes
Download

Costs

Summary

Electrical Work In Connection With Provision Of 600 M New Stabilizing Line, Extension Of Existing Stable Line And Washing Pit Line Upto 600 M & Making

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supply of PVC insulated multi stranded copper conductor single core HRFR cable 2.5 04 sq.mm confirming to IS: 694 (Latest version) and drawing in laid (recessed /surface) PVC Conduit pipe for wiring of point wiring/ circuit wiring /submain/main as required as per technical specification including connections, testing and commissioning complete in all respect. (Test report of NABL accredited laboratory should be submitted by firm at the time of supply of wire.)

3000

18

54000

... More
Supply of PVC insulated multi stranded copper conductor single core HRFR cable 4.0 sq.mm confirming to IS: 694 (Latest version) and drawing in laid (recessed/surface) PVC Conduit pipe 05 for wiring of point wiring/ circuit wiring /submain/main as required as per technical specification including connections, testing and commissioning complete in all respect. (Test report of NABL accredited laboratory should be submitted by firm at the time of supply of wire.)

1000

27

27780

... More
Supply of PVC insulated multi stranded copper conductor single core HRFR cable 6.0 06 sq.mm confirming to IS: 694 (Latest version) and drawing in laid(recessed/surface) PVC Conduit pipe for wiring of point wiring/ circuit wiring /submain/main as required as per technical specification including connections, testing and commissioning complete in all respect. (Test report of NABL accredited laboratory should be submitted by firm at the time of supply of wire.)

1500

38

57525

... More
Supply, Installation, testing & commissioning of Testing modular switch 10 Amps (1- way) complete in all respect as per direction of Engineer in charge.

150

58

8820

... More
Supply, Installation, testing & commissioning of modular type plug socket outlet 2/3 pin 10 Ampere complete in all respect as per Direction of Engineer in charge.

50

97

4862

... More
Supply, Installation, testing & commissioning of modular type switch 20 Amps (1- way) complete in all respect as per direction of Engineer in charge.

40

119

4799.2

... More
Supply, Installation, testing & commissioning of modular type plug socket outlet 5/3 pin 20 Ampere complete in all respect as per direction of Engineer in-charge.

40

138

5552

... More
Supply and Installation of Ceiling rose 3 plate as per IS:371/1999 (Latest version) including connections, testing and commissioning as per technical specification as per direction of Engineer in- charge.

100

13

1369

... More
Supply and Erection of white finished mounting single mounting cover plate with base frame 3 module suitable for mounting of modular type piano switches/plug socket, fan regulator and connecting to wiring complete in all respect.

100

62

6273

... More
Supply and Erection of Modular metal boxes concealed boards suitable for mounting 13 of 3 module white finish single mounting cover plate with frame and modular type piano switches/plug socket, fan regulators. Metal board boxes are to be concealed in wall complete in all respect.

100

41

4116

... More
Supply and Erection of white finished mounting single mounting cover plate with base frame 8 modules suitable for mounting of modular type piano switches/plug socket, fan regulator and connecting to wiring complete in all respect.

20

132

2650.4

... More
Supply and Erection of Modular metal boxes concealed boards suitable for mounting 15 of 8 module white finish single mounting cover plate with frame and modular type piano switches/plug socket, fan regulators. Metal board boxes are to be concealed in wall complete in all respect.

20

72

1442.8

... More
Supply and Erection of white finished mounting single mounting cover plate with base frame 12 modules suitable for mounting of modular type piano switches/plug socket, fan regulator and connecting to wiring complete in all respect.

20

191

3826.8

... More
Supply and Erection of Modular metal boxes concealed boards suitable for mounting 17 of 12 module white finish single mounting cover plate with frame and modular type piano switches/plug socket, fan regulators. Metal board boxes are to be concealed in wall complete in all respect.

20

116

2321

... More
Supply, making testing & commissioning of pipe earthing arrangement with GI pipe 'B' class, 40 mm dia 4.50 mtrs, long including accessories & providing masonry enclosure with cover 18 plate of 16 SWG M.S. having locking arrangement watering pipe , salt , charcoal etc. as per Drg. NO. DRM / Elect/IZN /16-89 to achieve earth resistance less than 10 ohms and connecting the equipment with 6 SWG G.I. wire as per site requirement. Earthing shall be done on the basis of code of practice for earthing as per IS: 3043/1987.

20

1375

27519.2

... More
Supply, Installation, Testing & commissioning of SPN MCB Distribution board 8 way 19 double door made with 1.2 mm thickness CRCA sheet fully powder coated of 50-70 micron with supply & fixing of 01 No. MCB 02 Pole 40 Amperes 10 KA 230 V as incoming and with supply & fixing of 02 Nos MCB of 6-25 Amp single pole 10 KA, 230 volts as outgoing Complete in all respect including connection as required.

15

2483

37249.5

... More
Digging of trench in all kinds of soil up to the depth of 750 mm and 350 mm wide forlaying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Digging of trench conforming to IS 1255).

1500

49

74205

... More
Laying of XLPE (LT) cable of different sizes in excavated cable trench and in underground pipes. (Laying of cable conforming to IS: 1255).

3000

5

17250

... More
Fixing connecting testing and commissioning of LED street light fitting 90 watt and 22 LED Flood light on existing pole/ covered shed including with supply connecting testing of 1.5 sq.mm copper wire complete in all respect as per direction of engineer in charge at site. Note: -LED streetlight fitting and LED flood light fitting will be supplied by railway at site.

100

81

8149

... More
Supply, erection and testing of hot dip galvanized tapered octagonal pole of 5.0 Mtrs. long top dia 70 mm, bottom dia 130 mm, sheet thickness 3 mm, base plate dimension (L x B x T) 200 mm x 200 mm x 12 mm & foundation bolts size (No. x dia x length) (4 x M16 x 600 mm), PCD 200 mm, anchor plate thickness 3 mm with hot dip galvanized detachable single arm bracket made by 23 48.3 mm outer dia pipe 300 mm long with 32 mm outer dia sleeve including erection & fixing on the foundation. (Octagonal pole shall confirm to IS: 2629 or latest.) Note:-1. Galvanized thickness of pole should be minimum 65 microns and test report to be submitted by the contractor at the time of supply. 2. Octagonal pole shall have flush door arrangement and suitable size & length of cable connecting plate for incoming and outgoing cables as per standard. Note: -Octagonal pole shall be inspected by the RITES as per specification at the manufacture premises and inspection cost shall be borne by the contractor.

30

6731

201948.9

... More
Supply, erection and testing of hot dip galvanized tapered octagonal pole of 5.0 Mtrs. long top dia 70 mm, bottom dia 130 mm, sheet thickness 3 mm, base plate dimension (L x B x T) 200 mm x 200 mm x 12 mm & foundation bolts size (No. x dia x length) (4 x M16 x 600 mm), PCD 200 mm, anchor plate thickness 3 mm with hot dip galvanized detachable double arm bracket made by 24 48.3 mm outer dia pipe 300 mm long with 32 mm outer dia sleeve including erection & fixing on the foundation. (Octagonal pole shall confirm to IS: 2629 or latest.) Note:-1. Galvanized thickness of pole should be minimum 65 microns and test report to be submitted by the contractor at the time of supply. 2. Octagonal pole shall have flush door arrangement and suitable size & length of cable connecting plate for incoming and outgoing cables as per standard. Note:-Octagonal pole shall be inspected by the RITES as per specification at the manufacture premises and inspection cost shall be borne by the contractor.

30

7020

210609.9

... More
Making trench of size 300 mm x 300 mm x 1000 mm and Casting/grouting of pre-cast foundation CC 1:2:4 block size 300 mm x 300 mm x 1000 mm grouting with 20 mm size stone aggregate with cement & coarse sand including supply, fixing and removing all firm work and 25 finishing exposed surface including grouting and holding down-M 16x 450 mm- 4 Nos bolts in cement block as per requirement of pole base plate of size 200x200x12 mm and supply & fixing Double Walled Corrugated (DWC DPDE Duct Pipe, size 90/76 mm, confirming to IS:14930 (Part-II) 0.75 meter length in the centre of cement concrete block for cable entry and fixing properly with all labour, material, cement etc. complete in all respect as per direction of engineer in-charge at site.

60

1910

114624.6

... More
Design Manufactucturing Supply of L.T. Switch board panel with for provision of consisting with installation, connecting, testing and commissioning LT. switch board panel of cubical 26 type as per CPWD General specification for electrical works, Part- IV substation 2013 including made of 2.0 mm. thick CRCA sheet of suitable size with provision of water proof, hinged door, suitable locking arrangements, proper hole in the bottom for cable entry (incoming & out going cables), 05no. suitable MS channel of size should be fixed across the panel for grouting on the foundation, earthing terminals and panel shall be powder coated (paint) greenish grey shade with proper arrangement of protection against rain/water & including sub copper bus bar, CTs & others accessories consisting with the following accessories with Supply fixing connecting testing & commissioning of Incoming Main MCCB with thermal magnetic trip unit 250 Amps, 04 poles, braking capacity 25 kA. Conforms to Ics=100% Icu as per IEC 60947-2, adjustable thermal setting 0.7 x1x In. suitable for 415 volts 50Hz. AC supply-01 No, Supply fixing connecting testing commissioning of Main copper Bus Bar TPN 600 Amp.-02 Sets, Supply fixing connecting testing commissioning of LED Multifunction Meter, accuracy class 1 with RS485. Input voltage measurement range 170-520 VAC. Aux supply 90-300 VAC. flush mounted 96 x 96 mm. Parameters Model A V, A, F, PF. KW, KVA, KVAR. KWh, kVAh, kVARh. Runhours. On hours, Intrrupts, RPM. %Unbalance (VA) Phase angle, THD -06 Set with Supply fixing connecting testing & commissioning of On load Manual Change witch 63 Amps. 04 pole, site convertible fuse version for open execution, site convertible dual shaft position, staggered terminals., 415 volts, 50 Hz. complete with all respect-1 No, Supply fixing connecting testing commissioning of Indicating lamps for incoming & outgoing feeders-18 No., Supply fixing connecting testing commissioning Outgoing No MCCB DH100. 50-63 Amps. 04 poles, braking capacity 25 kA. Conforms to IS/IEC 47-2 adjustable overload setting 0.8 x 1.0 x In. suitable for 415 volts, 50 Hz, AC supply-03 Nos, Supply fixing connecting testing commissioning Outgoing MCCB 25-32 Amps. 04 poles. braking capacity 18 kA. Confirming to IS/IEC 60947-2. Adjustable overload setting 0.8 x 1.0 In. suitable for 415 Volts, 50 Hz. AC supply-02 No and Supply fixing connecting testing commissioning of providing of sub copper bus bar for connecting MCCBs for outgoing feeders with suitable size of copper lugs and cable will be connected aluminum lugs through cable glands etc as required complete in all respect as per direction of engineer- incharge at site. Note:-ALL MCCB,s/Change Over Switch should be reputed Make.

1

126100

126100

... More
Supply, installation, Testing and Commissioning 16-meter long high mast lighting system complete with the following works:-1.1 Supply of 16-meter high mast system:- The mast shaft shall be in two sections hot dip galvanized inside and outside in single dip, suitable for wind velocity as per IS:875 part 3. There shall be only one longitudinal seam weld per section and no circumferential weld. It shall also include accessories for high mast including head frame, 2 point suspension system with stainless steel wire rope tralling cable, connector, 6 mm dia double drum winch, galvanized lantern carriage arrangement suitable for 08 luminaries LED type symmetrically arranged. The mast shall have an integral power tool motor, manual handle, junction box at the base compartment for its operation. 1.2 Supply of foundation bolts manufactured from special steel along with nuts, washers, anchor plates & common template (Set 01) 1.3 Supply, fixing, testing and commissioning of LED flood light fixture 250 watt, power factor not less than 0.95 and LED driver should be constant voltage & current and fitting should be IP 66-08 Nos.LED fitting shall conform to BIS specification No. 10322 (Pt.5/sec. 1)/2012 or latest. 1.4 Supply of LED type single dome aviation obstruction light. 1.5 Design & making of outdoor stand mounted feeder pillar control panel with 63 Amps TPN MCB incomer, single dial time switch, 45 Amps TP contractor for the automatic switching 27 of luminaries, power tool control with 02 no. 9 Amps contractors and raise lower push button, incoming 35 mm & outgoing 16 & 2.5 mm2 terminals. (set 01) 2. Erection Part:-2.1 Design construction & erection of suitable shallow foundation with M20 concrete for the high mast considering the safe soil bearing capacity at site as 10 T/ sq.mtr at 2 mtr depth with all material & labour (Job-01) 2.2 Erection of the high mast with the help of suitable equipment and wiring of luminaries with all wiring material like PVC insulated, PVC sheathed flexible cable of suitable copper conductor, cable lugs, MCB etc and all labours. 2.3 Provision of G.I. pipe earthing arrangement for high mast with 4.5 M long 40 mm dia G.I. pipe including connection to high mast earth terminal with 25 x 3 mm G.I. earth strip with all materials and labour as per Drg. No. DRM/Elec./IZN/16-89 (Nos 02) 2.4 Installation, testing and commissioning of control panel on suitable foundation including all material & labour (Job 01).Note:-1. High mast system should be as per enclosed specification. Note:- Complete High Mast system with LED flood light shall be inspected by the RITES as per specification at the manufacture premises and inspection cost shall be borne by the contractor. (Successful Tenderer shall submit WARRANTEE GUARANTEE (WG) @ 10% of the Contract Value of this item in the prescribed proforma before claiming the payment for this item.) Note: - Complete High Mast and LED flood light fixture 250 Watt shall be guaranteed/warranted for a period of 60 months from the date of commissioning for satisfactory performance.

1

395746

395746.68

... More
Making of hexagonal platform foundation with Rail post and including all accessories 28 for high mast lighting tower in in yard and goods siding as per CEE's Drg No. L/CEE/GKP/2010/2 as enclosed with all materials. Note:-1. Only rail pole will be supplied by the railway.2. Cutting of rail post 1750 mm length (each) is included in the scope of work.

1

10256

10256.24

... More
Supply of LED Pit Light luminaire of 16 Watt (as per CAMTECH specification) complete with Power Factor >0.9, input Voltage 48 V AC +10%, Frequency Range 50 Hz, LED matrix 12 LED matrix, Approximate light output 1300-1400 lumens, LED Driver- High brightness driver system, Source- PWM constant current, Reverse polarity protection, Short circuit protection, Open circuit protection, Material and insulation of driver - Fire retardant material (ABS & Polycarbonate), Diffuser- P12 prismatic polycarbonate & toughened glass, Tj (Junction temperature) - Less than 90 degree 29 centigrade of each LED after continuous operation of 12 hours, The whole luminaire fixture shall beprovided with high impact resistance i.e. IK10, The whole luminaire fixture shall ensure tightness level of IP67 and all accessories of luminaire shall be prewired upto the terminal block and the connecting lead shall be 3 core (phase, neutral & earth), PVC insulated of suitable size and minimum 1.0 metre long, Luminaire shall be locking & mounting arrangement. The approximate dimension of luminaire shall be 290 mm long, 210 mm width and 72 mm deep. Note:-LED fitting shall have replacement guarantee for satisfactory performance & manufacturing defects for a period of 60 months from the date of commissioning. (Successful Tenderer shall submit WARRANTEE GUARANTEE (WG) @ 10% of the Contract Value of this item in the prescribed Performa before claiming the payment for this item.) Note: - Complete LED Pit Light luminaire 16 watts shall be inspected by the RITES as per specification at the manufacture premises and inspection cost shall be borne by the contractor.

120

2703

324402

... More
Supply of LED Catwalk Light luminaire of 22 Watt (as per CAMTECH specification) complete with Power Factor > 0.9, input Voltage 48 V AC +10%, Frequency Range 50 Hz, LED matrix 15 LED matrix, approximate light output 1600-1700 lumens, LED Driver- High brightness driver system, Source- PWM constant current, Reverse polarity protection, Short circuit protection, Open circuit protection, Material and Insulation of driver - Fire retardant material (ABS & Polycarbonate), Diffuser- P12 prismatic polycarbonate & toughened glass, Tj Junction temperature) - Less than 90 degree Centigrade of each LED after continuous operation of 12 hours, The whole luminaire fixture shall be provided with high impact resistance I.e. IK10, The whole luminaire fixture shall ensure 30 tightness level of IP67 and all accessories of luminaire shall be prewired upto the terminal block and the connecting lead wire shall be 3core (phase, neutral & earth), PVC insulated of suitable size and minimum 1.0 metre long. Luminaire shall be provided with suitable mounting arrangement and shall be suitable for semi flush/fully flush/surface mounting and locking arrangement- The top cover of the luminaire shall be fitted with allen screws to avoid theft. The approximate dimension of luminaire shall be 320 mm long, 210 mm width and 72 mm deep. Note: - LED fitting shall have replacement guarantee for satisfactory performance & manufacturing defects for a period of 60 months from the date of commissioning. (Successful Tenderer shall submit WARRANTEE GUARANTEE (WG) @ 10% of the Contract Value of this item in the prescribed Performa before claiming the payment for this item.) Note:-Complete LED catwalk Light luminaire 22 watt shall be inspected by the RITES as per specification at the manufacture premises and inspection cost shall be borne by the contractor.

120

3128

375460.8

... More
Fixing, connecting, testing and commissioning of LED Pit Light luminaire 16 watt and 31 catwalk light luminaire of 22 Watt on the washing pit column with the help of G.I. Strip clamps & bolt fastener and making anti-theft arrangement of LED washing pit light including with all material as per direction of engineer in-charge at site.

240

592

142080

... More
Fixing, testing and commissioning of Cable junction box of size 205 x 255 x 112 mm 32 on the wall/structure as per the direction of site supervisor. All material (bracket, clamp, bolt fastener etc. and other accessories) required for fixing shall be done by the contractor. Note: Cable junction box of size 205 x 255 x 112 mm will be supplied by the Railway at site.

4

350

1400

... More
Fixing, testing and commissioning of Cable junction box of size 104x104x70 mm on 33 the wall/structure as per the direction of site supervisor. All material (bracket, clamp, bolt fastener etc. and other accessories) required for fixing shall be done by the contractor. Note: Cable junction box of size 104x104x70 mm will be supplied by the Railway at site.

240

100

24000

... More
Supply, Installation, testing & commissioning of train lighting battery charger 300 34 Amps, output 110 Volts to 150 volts DC, Input voltage 415 Volts, 3 phase, 50 Hz, AC supply complete with outgoing MCB/MCCB of suitable capacity, incoming voltmeter 0-500 volts, outgoing voltmeter 0- 400 volts with selector switch, outgoing Ampere meter of suitable capacity with CT and LED indicating lamps for incoming supply complete in all respect.

1

177000

177000

... More
Design, supply, installation, connecting, testing and commissioning of step down 3 KVA transformer wall/pole mounting type, input voltage single phase 220 volts ± 10%, 50 Hz, AC 35 supply and output voltage 48 volts ± 10%, AC supply with volt meter, ampere meter, indication lamp, high & low voltage and short circuit protection including made by CRCA sheet 1.6 mm thick with hinged cover locking arrangement and making hole in the bottom for cable entry with cable glands and supply & fixing of cable connector terminals etc as required as per site required.

4

22000

88000

... More
Laying, threading & fixing of MS/GI pipe 25/50/ 80/100 mm dia including socket, fixing on CC flooring by suitable size of G.I clamps with bolts, fastener etc as required.

-

-

36

... More
Supply of M.S. pipe 50 mm dia A class confirming to IS: 1239 (Part-1) (2004) for laying of cable through it as required complete in all respect. Make: -Jindal, TATA, swastik.

100

623

62304

... More
Supply, Fixing of distribution box in foundation, connecting testing and commissioning of LT distribution box made of 1.6 mm thick cold rolled steel sheet of size 600 mm (L) x 450 mm (W) x300 mm (D) with provision of water proof , hinged door, suitable locking arrangements, proper hole in the bottom for cable entry (incoming & out going cables) -05 Nos suitable and MS channel of size 75mm x 40mmx 4mm should be fixed across the panel for grouting on the foundation, earthing 38 terminals and panel shall be powder coated (paint) greenish grey shade with TPN Copper Busbar of 600 Amps with provision of water proofing and installation on Providing and making foundation to double door feeder pillar box (cubical type L.T. panel) in CC 1:2:4 with stare aggregate. [Size 1220 mm high x 800 mm length and 600 mm width (610 mm under the earth & 610 mm above the earth) with fine finish to exposed surface, two coats white washing including excavation of foundation, making proper size hole for incoming and outgoing cables. Grouting of holding down bolt in CC (size of bolt 150 mm long 16mm dia.) includes fixing of sub distribution box on CC foundation and as per direction of engineer in charge at site.

2

11658

23316

... More
Supply, erection and testing of hot dip galvanized tapered octagonal pole of 5.0 Mtrs. long top dia 70 mm, bottom dia 130 mm, sheet thickness 3 mm, base plate dimension (L x B x T) 200 mm x 200 mm x 12 mm & foundation bolts size (No. x dia x length) (4 x M16 x 600 mm), PCD 200 mm, anchor plate thickness 3 mm with hot dip galvanized detachable double arm bracket made by 01 48.3 mm outer dia pipe 300 mm long with 32 mm outer dia sleeve including erection & fixing on the foundation. (Octagonal pole shall confirm to IS: 2629 or latest.) Note:-1. Galvanized thickness of pole should be minimum 65 microns and test report to be submitted by the contractor at the time of supply. 2. Octagonal pole shall have flush door arrangement and suitable size & length of cable connecting plate for incoming and outgoing cables as per standard. Note: -Octagonal pole shall be inspected by the RITES as per specification at the manufacture premises and inspection cost shall be borne by the contractor.

50

7020

351016.5

... More
Making trench of size 300 mm x 300 mm x 1000 mm and Casting/grouting of pre-cast foundation CC 1:2:4 block size 300 mm x 300 mm x 1000 mm grouting with 20 mm size stone aggregate with cement & coarse sand including supply, fixing and removing all firm work and 02 finishing exposed surface including grouting and holding down-M 16x 450 mm- 4 Nos bolts in cement block as per requirement of pole base plate of size 200x200x12 mm and supply & fixing Double Walled Corrugated (DWC DPDE Duct Pipe, size 90/76 mm, confirming to IS:14930 (Part-II) 0.75 meter length in the centre of cement concrete block for cable entry and fixing properly with all labour, material, cement etc. complete in all respect as per direction of engineer in-charge at site.

50

1910

95520.5

... More
Fixing connecting testing and commissioning of LED street light fitting 90 watt and 03 LED Flood light on existing pole/ covered shed including with supply connecting testing of 1.5 sqmm copper wire complete in all respect as per direction of engineer incharge at site. Note:-LED street light fitting and LED flood light fitting will be supplied by railway at site.

100

81

8149

... More
Digging of trench in all kinds of soil up to the depth of 750 mm and 350 mm wide for 04 laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Digging of trench conforming to IS 1255).

3000

49

148410

... More
Laying of XLPE (LT) cable of different sizes in excavated cable trench and in underground pipes. (Laying of cable conforming to IS: 1255).

5000

5

28750

... More
Supply, Installation, Testing & commissioning of SPN MCB Distribution board 4 way 06 double door made with 1.2 mm thickness CRCA sheet fully powder Coated of 50-70 micron with supply & fixing of 01 No MCB 02 pole 40 Amperes 10 KA 230 V as incoming and with supply & fixing of 02 Nos MCB of 6-25 Amp single pole 10 KA, 230 volts as outgoing complete in all respect including connection as required.

4

1028

4115.6

... More
Supply, making testing & commissioning of pipe earthing arrangement with GI pipe 'B' 07 class, 40 mm dia 4.50 mtrs, long including accessories & providing masonry enclosure with coverplate of 16 SWG M.S. having locking arrangement watering pipe , salt , charcoal etc. as per Drg. NO. DRM / Elect/IZN /16-89 to achieve earth resistance less than 10 ohms and connecting the equipment with 6 SWG G.I. wire as per site requirement. Earthing shall be done on the basis of code of practice for earthing as per IS: 3043/1987.

14

1375

19263.44

... More
All work pertaining to Horizontal Directional Drilling (HDD)/Boring and trench less cabling. It includes supply, transportation and insertion of self-lubricated HDPE pipe and laying of 08 cable in boring under the track/road by using different sizes of pipes depending on total number of cables will be crossed. The depth of horizontal boring should be 3 mtrs from rail flange/road level. This item will be used for track crossing of running lines.) By using self-lubricated HDPE pipe of 108.60 mm inner dia and 125 mm outer dia (PN-6) as per IS:4984 or latest in the bore and the laying of cables in the track/road.

150

1056

158482.5

... More
Digging of trench in all kinds of soil up to the depth of 750 mm and 350 mm wide for 01 laying of cable with supply and placing of second-class bricks, approx. 10 bricks per meter, refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trench. (Digging of trench conforming to IS 1255).

2000

49

98940

... More
Laying of XLPE (LT) cable of different sizes in excavated cable trench and in underground pipes. (Laying of cable conforming to IS: 1255).

4000

5

23000

... More
Supply, Installation, Testing & commissioning of SPN MCB Distribution board 4-way 03 double door made with 1.2 mm thickness CRCA sheet fully powder Coated of 50-70 micron with supply & fixing of 01 No. MCB 02 pole 40 Amperes 10 KA 230 V as incoming and with supply & fixing of 02 Nos MCB of 6-25 Amp single pole 10 KA, 230 volts as outgoing Complete in all respect including connection as required.

30

1028

30867

... More
Supply, making testing & commissioning of chemical earthing arrangement with 04 proper length earthing electrode to achieve earth resistance less than 2.5 ohms and connecting the equipment complete as per site requirement. Earthing shall be done on the basis of code of practice for earthing as per IS: 3043/1987.

30

2900

87000

... More
All work pertaining to Horizontal Directional Drilling (HDD)/Boring and trench less cabling. It includes supply, transportation and insertion of self-lubricated HDPE pipe and laying of 05 cable in boring under the track/road by using different sizes of pipes depending on total number of cables will be crossed. The depth of horizontal boring should be 3 mtrs from rail flange/road level. This item will be used for track crossing of running lines.) By using self-lubricated HDPE pipe of 108.60 mm inner dia and 125 mm outer dia (PN-6) as per IS:4984 or latest in the bore and the laying of cables in the track/road.

200

1056

211310

... More
Supply, Fixing of distribution box in foundation, connecting testing and commissioning of LT distribution box made of 1.6 mm thick cold rolled steel sheet of size 600 mm (L) x 450 mm (W) x300 mm (D) with provision of water proof , hinged door, suitable locking arrangements, proper hole in the bottom for cable entry (incoming & out going cables) -05 Nos suitable and MS channel of size 75mm x 40mmx 4mm should be fixed across the panel for grouting on the foundation, earthing 06 terminals and panel shall be powder coated (paint) greenish grey shade with TPN Copper Busbar of 600 Amps with provision of water proofing and installation on Providing and making foundation to double door feeder pillar box (cubical type L.T. panel) in CC 1:2:4 with stare aggregate. [Size 1220 mm high x 800 mm length and 600 mm width (610 mm under the earth & 610 mm above the earth) with fine finish to exposed surface, two coats white washing including excavation of foundation, making proper size hole for incoming and outgoing cables. Grouting of holding down bolt in CC (size of bolt 150 mm long 16mm dia.) includes fixing of sub distribution box on CC foundation and as per direction of engineer in charge at site.

10

11658

116580

... More
Design fabrication supply and erection of metal box of size 600 mm x 300 mm x 300 mm made by CRCA sheet 1.6 mm thick suitable for 2 Nos, 70 watt LED flood light fitting including fixing of LED flood light fitting complete in all respect with hinged cover with plain glass of thickness 5 mm duly protected with expanded metal jali 20 mm x 60 mm with adequate mechanical support with locking arrangement, lock & key and making hole in bottom for cable entry with cable glands and supply and fixing of cable connector terminal set 10/16 sqmm, 6/5 Nos inner side of the box, The metal box shall be nicely finished with at least two coat of epoxy based powder and last touch up painting including supply of material for fixing of box i,e. clamp, nut, bolts minor masonry work etc. as per site requirement.

30

3900

117000

... More
Supply & erection of MS angle 50 x 50 x 6 mm, 1200 mm long (04 Nos) in cement 08 concrete 1:3:6 (1 cement, 3 coarse sand graded stone aggregate 25 mm nominal size) foundation including excavation and refilling etc as required along with painting of M.S. angle by one coat primer & two coats enamel paint 450 mm M.S. angle will be grouted in the ground and welded metal box on M.S. angle as above item no. 15 as per direction of Engineer incharge at site complete in all respect.

30

700

21000

... More
Supply of G.I pipe 50 mm dia B class confirming to IS: 1239 (Part-1) (2004) for laying of cable through it as required complete in all respect. Make:-Jindal, TATA, swastik.

200

630

126000

... More
Laying, threading & fixing of GI pipe 50/80/100 mm dia including socket, fixing on CC flooring by suitable size of G.I clamps with bolts fastener etc as required.

200

194

38800

... More
Supply & fixing of G.I pipe 25 mm dia B class confirming to IS: 1239 (Part-1) (2004) for laying of cable through it as required complete in all respect. Make:-Jindal, TATA, swastik.

200

389

77800

... More
Supply & Fixing of GI Tee reducer 50/25 mm dia B class confirming to IS:1239 (Pt- 1)/1990 for laying of cable complete in all respect as per direction of engineer in-charge.

200

297

59400



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.