Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited Tender
View complete overview of Uttarakhand BRIDCUL Tender
Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited - BRIDCUL Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date26 Dec 2024
Closing Date7 Jan 2025
Tender Amount₹ 57,80,000
Costs
EMD
₹ 1,16,000Document Cost
₹ 5,900Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_BRID3_79199_1Tender No
2351/BRIDCUL/959/24 Dated 21/12/2024Tender Authority
Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited ViewPurchaser Address
-Website
http://uktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire.
1427
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.2 x 6 sq.mm. + 1 x 6 sq.mm. earth wire.
600
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 2 x 10 sq.mm. + 1 x 6 sq.mm. earth wire.
80
-
-
... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. 4 X 10 sq. mm + 2 X 6 sq. mm earth wire
160
-
-
... More
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
33
-
-
... More
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
24
-
-
... More
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
20
-
-
... More
Supplying and fixing brass batten/ angle holder including connection etc. as required.
25
-
-
... More
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as Required. Single pole
114
-
-
... More
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
4
-
-
... More
Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 6 Way (4 + 18), Double Door
2
-
-
... More
Supplying and Fixing Following way, Horizontal Type Three Pole and Neutral, Sheet Steel, MCB Distribution Board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 8 Way (4 + 24), Double Door
2
-
-
... More
Supplying and fixing following way, Single Pole and Neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). 12 way , Double door
2
-
-
... More
Supplying and fixing following Rating, Double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required. 40 Amps
2
-
-
... More
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as Required. 63 Amps
4
-
-
... More
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as Required.40 Amps
12
-
-
... More
Supplying and Fixing Following Size/ Modules, GI Box Alongwith Modular Base & Cover Plate for Modular Switches in Recess etc. as required. 1 or 2 Module (75 mm x 75 mm)
16
-
-
... More
Supplying and Fixing Following Modular Switch/ Socket on The Existing Modular plate & Switch Box including connections But Excluding Modular Plate etc. as required. Telephone Socket outlet.
8
-
-
... More
Supplying and Fixing Following Modular Switch/ Socket on The Existing Modular plate & Switch Box including connections But Excluding Modular Plate etc. as required. TV Antenna socket outlet.
2
-
-
... More
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm.
344
-
-
... More
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, Unarmored Telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair
160
-
-
... More
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.
38.6
-
-
... More
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable
240
-
-
... More
SITC Modular Type Computer jack RJ 45 ISI mark 1 Module on existing Mounting plate and box Complete. As per LEGRAND modular electrical switchesand accessories with Telephone JackType RJ-11(For Telephone)
LEGRAND (5734 26 ARTEOR) or equivalent
8
-
-
... More
Supply of Recess Mounted Energy Efficient, LED Luminaires 18W LED Down Light Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required. as Per ACROMAX LITES 18W Led RecessedLuminaire ACROMAX LITES (ACROMAX LITE AIPLLEDDL-18W) or equivalent.
48
-
-
... More
Supply of 40W (2x2) LED Light (Recessed) fitting suitable for 40Watt LED Light with all accessories as required. As Per ADHUNIK 40W Led RecessedLuminaire ADHUNIK (ASGPL40W2X2) or equivalent.
117
-
-
... More
Supply of Surface Mounted Energy Efficient, LED Luminaires 12W LED DOWN LIGHT Sutaible for 220v Single Phase Supply complete with driver circuit including making connections etc.as required. As Per JAILUX Cool Day Light Aluminium Square LED surface ceiling Light JAILUX (JLT-12W) or equivalent.
18
-
-
... More
Supply, of Linear & Compact 10W Mirror Light with Decorative Grey Caps, Polycarbonate Body & Ribbed Opal Diffuser. As Per BAJAJ LED Batten 10 Watts 560 mm BAJAJ R (LED BATTEN 10W) or equivalent.
13
-
-
... More
Supply of 9W LED BULB with all accessories as required. As Per JAILUX Self Ballasted LED Lamps for General Lighting Service 9 Watts 3 Star JAILUXR
(JLT-9W) or equivalent
25
-
-
... More
Supply of LED Luminaires BATTEN 20W LED Tube Light of Box Type Prewired Indoor Luminaire with Energy Efficient Electronic Ballast, with End Caps Complete as Required. As Per havells 20 Watt/2000 lumen 5700 KLED Tubelight havells or equivalent
9
-
-
... More
Supply of Following sweep exhaust fan with guard suitable operation on single phase 230 V, 50Hz. AC Supply, with lowers / shutters in the existing opening. As per GANESH Capacitor Type propeller type ac ventilating fan-exhaust
GANESH (GANESH-300/4) or equivalent. 300 mm Sweep 900 rpm
13
-
-
... More
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
19
-
-
... More
Installation, testing and commissioning of pre-wired, fluorescent fitting /compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as Required.
230
-
-
... More
Installation of Exhaust fan in the existing opening, including making good the damage, Connection, Testing, Commissioning etc. as Required. Upto 450 mm sweep
13
-
-
... More
Extra for Fixing the Louvers/ Shutters Complete with Frame for a Exhaust Fan of all sizes.
13
-
-
... More
Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing
19
-
-
... More
Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.INCOMER : 125 AMP FP MCCB BUS BAR : 160 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp.The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature. OUT GOINGS : 1 No 63 AMP 4P MCB Including Indication Lights (Ground Floor Power DB's) 1 No 63 AMP 4P MCB Including Indication Lights (Ground Floor Light DB's) 1 No 40 AMP DP MCB Including Indication Lights (UPS DB) 1 No 63 AMP 4P MCB (Spare) 1 No 40 AMP DP MCB (Spare)1 No 40 AMP DP MCB (Spare) complete panel as above and complete
1
-
-
... More
MAIN DISTRIBUTION PANEL for library ,Design, manufacture, supply, installation, testing and commissioning of Floor Mounting Distribution Panel cubicle type panel fabricated out of CRCA sheet steel , floor mounted totally enclosed switchbaord suitable for use of 415 volts , 3 phase, 50 HZ complete with aluminium bus bar and all accessories including supply and fixing of following incoming and outgoing switchgears, Panel Should Have Double Earthing Provision which connected to the nearest earth grid.INCOMER : 100 AMP FP MCCB BUS BAR : 125 AMP, 500 Volts, 3 phase 50 HZ 4P high conductivity electrolytic Aluminium bus bar of suitable length, insulated by heat shrinkable sleeves. The current density of bus bar shall be minimum 0.8 sq mm/amp. The Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient TemperatureThe Maximum allowable temperature for the Bus bar to be restricted to 90 deg C. The temperature rise should be restricted to 45 deg C above ambient Temperature OUT GOINGS : 1 No 63 AMP 4P MCB Including Indication Lights (Ground Floor Power DB's) 1 No 63 AMP 4P MCB Including Indication Lights (Ground Floor Light DB's) 1 No 40 AMP DP MCB Including Indication Lights (UPS DB) 1 No 63 AMP 4P MCB (Spare)1 No 40 AMP DP MCB (Spare) complete panel as above and complete
1
-
-
... More
Supplying of Following Sizes of 1.1 KV Grade Multicore Aluminium Conductor XLPE Power Cable Insulated armoured cable conforming to IS:7098 (Part - I) or as per Relevant IS Code complete with all Amendments etc and should be NABL certified as required.3.5 C X 35 Sq.mm Al. XLPE arm.
75
-
-
... More
Laying of One Number PVC Insulated And PVC Sheathed / XLPE Power Cable of 1.1 kV Grade of Following Size Direct in Ground Including Excavation, Sand Cushioning, Protective Covering and Refilling the Trench etc. as required. Upto 35 sq. mm
75
-
-
... More
Supplying and Making End Termination With Brass Compression Gland and Aluminium lugs for Following Size of PVC Insulated and PVC Sheathed / XLPE Aluminium Conductor Cable of 1.1 kV Grade as Required. 3½ X 35 sq. mm (32mm)
4
-
-
... More
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
2
-
-
... More
Providing and fixing Shock Treatment Chart
2
-
-
... More
SITC of First aid box as approved by Indian red cross conforming to IS : 2217.
2
-
-
... More
SITC of CO2 Fire Extinguishers 4.5 kg capacity complete in all respect ISI : 15683 marked.
2
-
-
... More
SITC of ABC FIRE EXTINGUISHER 4 KG capacity complete in all respect ISI : 15683 marked.
2
-
-
... More
SITC of Fire Bucket stand made of M S angle suitable for and with 4 Nos Fire Buckets of 9.5 Ltrs capacity.
2
-
-
... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required.
4
-
-
... More
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
100
-
-
... More
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
40
-
-
... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement) 150 mm width X 50 mm depth X 1.6 mm thickness
30
-
-
... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required. (Cable Tray Bends as per Requirement)300 mm width X 50 mm depth X 1.6 mm thickness
20
-
-
... More
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required. Above 4.5 metre and upto 6.5 metre
12
-
-
... More
Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape , Hole Seeling to be done complete as required. 32 mm dia
120
-
-
... More
Supply , Installation, Testing & Commissioning of Integrated Post Top Lantern With 30W LED Lamp including Pole & connection with 3 x 2.5 sq.mm single core PVC insulated copper conductor cable from junction box to fixture as required.
2
-
-
... More
Supply , Installation, Testing & Commissioning of 50 W LED with complete with pot optic reflector connection with 3x2.5sq.mm single core PVC insulated copper conductor cable from junction box to fixture as required
12
-
-
... More
Supply, Installation, Testing and Commissioning of 200x160x70 Polycarbonate thermoplastics enclosure - junction box with I.P - 66 Protection
12
-
-
... More
Supplying of ADP Octagonal Pole Single Arm 6 m ADP, Material of Octagonal pole : Grade ISH430LA as perIS:5986:2017 latest, Base plate material : Grade: E250, Quality:BR(as per IS:2062:2011 latest)
12
-
-
... More
Supplying of Following sizes 1100 volt grade XLPE insulated PVC sheathed aluminium conductor armoured cables as per specification in existing laid in ground including cost of digging upto required depth, 150 mm sand all around the cable, brick protection and back filling, clamped to wall with suitable clamps including saddles fixing bolts, Connection Testing and commissioning as Required. 2x6 sqmm
350
-
-
... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering. Upto 35 sq. mm
300
-
-
... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
50
-
-
... More
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. 3 core 2.5 sq.mm (for Poles)
96
-
-
... More
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
20
-
-
... More
Providing and fixing of lightning conductor finial, made of 25mm dia 300mm long, G.I tube, having single prong at top with 85mm dia 6mm thick G.I base plate including holes etc. complete as required.
4
-
-
... More
Providing and fixing G.I tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (for horizontal run)
200
-
-
... More
Providing and fixing G.I tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (for vertical run)
80
-
-
... More
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
8
-
-
... More
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
4
-
-
... More
Supplying, installation, testing and commissioning of 100 KVA 33kV/0.433kV or 11kV/0.433 kV substation equipments comprising HT Panel, Dry type/Oil type Transformers, HT cable, Bus trunking from Transformer to LT Panel, LT Panel, Automatic Power factor correction panel, Active Harmonic Filters, TVSS (Transient Voltage suppression system),SPD (Surge protection system), Essential panel, Earthing, required inter-connections,substation safety equipments including LT cabling from sub station to the buildings fed by the sub station.
1
-
-
... More
Supplying, installation, testing and commissioning of 50 KVA Silent Type DG Sets,AMF Panel, Bus Ducting/ Cables from DG Sets to Essential Panel, Synchronizing Panel where required, DG Set enclosure room sound insulation/ventilation/smoke exhaust as required, Earthing of DG Set system, control cabling, Fuel tank/piping, DG set Exhaust piping/ Exhaust Chimney as per CPCB norms, Civil works connected with DG Sets including Foundation Complete as required.
1
-
-
... More
Supplying, installation, testing and commissioning of 5 KVA online 3 phase UPS System with 30 minutes back up including batteries, interconnecting cables, battery racks etc. Complete as Required
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%