Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited Tender

View complete overview of Uttarakhand BRIDCUL Tender

Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited - BRIDCUL Tender

Works
Civil And Construction
Building Construction
Eprocure
Opening Date6 Apr 2022
Closing Date9 May 2022
Tender Amount₹ 32,01,62,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Supplying and filling in plinth with sand under floors, including watering, ramming, consolidating and dressing complete.

436.83

-

-

... More
Supplying chemical emulsion in sealed containers including delivery as specified.

-

-

-

... More
Chlorpyriphos/ Lindane emulsifiable concentrate of 20%

2182.5

-

-

... More
Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :

-

-

-

... More
Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a depth of 300mm including excavation channel along the wall & rodding etc. complete:

-

-

-

... More
With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration

445.12

-

-

... More
Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor:

-

-

-

... More
With Chlorpyriphos/Lindane E.C. 20% with 1% concentration

2440.75

-

-

... More
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :

-

-

-

... More
1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)

683.76

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form work for :

-

-

-

... More
Foundations, footings, bases for columns

486.83

-

-

... More
Providing and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand(zone-III) : 4 graded stone aggregate 20mm nominal size).

411.52

-

-

... More
Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square metre on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil.

411.52

-

-

... More
Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone - III) : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.

434.75

-

-

... More
Centering and shuttering including strutting, propping etc. and removal of form for :

-

-

-

... More
Foundations, footings, bases of columns, etc. for mass concrete

765.76

-

-

... More
Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.

1351.58

-

-

... More
Suspended floors, roofs, landings, balconies and access platform

7656.48

-

-

... More
Lintels, beams, plinth beams, girders, bressumers and cantilevers

10232.98

-

-

... More
Columns, Pillars, Piers, Abutments, Posts and Struts

5375.82

-

-

... More
Stairs, (excluding landings) except spiral-staircases

25.24

-

-

... More
Edges of slabs and breaks in floors and walls

-

-

-

... More
Under 20 cm wide

1414.75

-

-

... More
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.

-

-

-

... More
Thermo-Mechanically Treated bars of grade Fe-500D or more.

30308.53

-

-

... More
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level.

-

-

-

... More
Thermo-Mechanically Treated bars of grade Fe-500D or more.

462197.28

-

-

... More
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330 kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately).

-

-

-

... More
All works upto plinth level

1216.34

-

-

... More
All works above plinth level upto floor V level

3049.94

-

-

... More
Extra for providing richer mixes at all floor levels. Note:- Excess/less cement over the specified cement content used is payable /recoverable separately.

-

-

-

... More
Providing M-30 grade concrete instead of M-25 grade BMC/ RMC. (Note:- Cement content considered in M-30 is @ 340 kg/cum)

152.04

-

-

... More
Providing and fixing of expansion joint system related with floor location as per drawings and direction of Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical localtion in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminum base member designed to accommodate various project conditions and finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates / moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of Moisture Barrier Membrane in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer -in- Charge. (Material shall confirm to ASTM 6063).

-

-

-

... More
Floor Joint upto 100 mm gap

290

-

-

... More
Providing and fixing of expansion joint system related with wall joint (internal/ external) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members, self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to corner application, both new and existing construction in office Buildings & complexes with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking the multicellular to facilitate movement. (Material shall confirm to ASTM 6063).

-

-

-

... More
Wall Joint upto 100 mm gap

290

-

-

... More
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:

-

-

-

... More
Cement mortar 1:6 (1 cement : 6 coarse sand)

273.51

-

-

... More
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in :

-

-

-

... More
Cement mortar 1:6 (1 cement : 6 coarse sand)

1941.6

-

-

... More
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundations and plinth in :

-

-

-

... More
cement mortar 1:4 (1 cement : 4 coarse sand)

100

-

-

... More
Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.

-

-

-

... More
Cement mortar 1:4 (1 cement :4 coarse sand)

4166.13

-

-

... More
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.

-

-

-

... More
Granite of any colour and shade

-

-

-

... More
Area of slab over 0.50 sqm

80.66

-

-

... More
Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge.

-

-

-

... More
Granite work

124.51

-

-

... More
Extra for fixing marble /granite stone, over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive, including cleaning etc. complete.

124.51

-

-

... More
Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.

38

-

-

... More
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.

1437.17

-

-

... More
Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) non-decorative type, core of block board construction with frame of 1st class hard wood and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters:

-

-

-

... More
35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws

295.84

-

-

... More
30 mm thick including ISI marked Stainless Steel butt hinges with necessary screws

123.75

-

-

... More
Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).

419.59

-

-

... More
Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured):

-

-

-

... More
Rectangular or square

295.84

-

-

... More
Extra if louvers (not exceeding 0.2 sqm) are provided in flush door shutters (overall area of door shutters to be measured).`

-

-

-

... More
Decorative type door

295.84

-

-

... More
Providing and fixing IS : 12817 marked stainless steel butt hinges (heavy weight) with stainless steel screws etc. complete :

-

-

-

... More
125x64x2.50 mm

716

-

-

... More
Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :

-

-

-

... More
300x16 mm

206

-

-

... More
250x16 mm

152

-

-

... More
Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :

-

-

-

... More
300x10 mm

103

-

-

... More
250x10 mm

76

-

-

... More
Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.

-

-

-

... More
Single rubber stopper

76

-

-

... More
Twin rubber stopper

103

-

-

... More
Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality with necessary screws etc. complete.

179

-

-

... More
Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than 120gm/ m²) suitable for mounting 120 min Fire Rated Glazed Door Shutters. The frame shall be filled with Mineral wool Insulation having density min 96Kg/m³ . The frame will have a provision of G.I. Anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with Factory made Template for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of fire rated glazed shutter . The frame shall be finished with a approved fire resistant primer or Powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- charge . (Cost of SS ball bearing hinges is excluded).

87

-

-

... More
Providing and fixing 60 mm thick glazed fire resistant door shutters of 120 min Fire Rating confirming to IS:3614 (Part II) or EN1634-1:1999, tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, top rail & side rail 60 mm x 60 mm wide and bottom rail of 110 mm x 60 mm made out of 1.6mm thick G.I. sheet (zinc coating not less than 120gm/m²) duly filled mineral wool insulation having density min 96 kg/ m³ and fixing with necessary stainless steel ball bearing hinges of size 100x89x3mm of approved make, including applying a coat of approved fire resistant primer or powder coating not less than 30 micron etc all complete as per direction of Engineer-in-charge (panelling to be paid for seperately).

50.6

-

-

... More
Providing and fixing bright /matt finished Stainless Steel handles of approved quality & make with necessary screws etc all complete.

-

-

-

... More
125 mm

17

-

-

... More
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.

6409.2

-

-

... More
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer.

-

-

-

... More
Using M.S. angels 40x40x6 mm for diagonal braces

2.1

-

-

... More
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.

-

-

-

... More
80x1.25 mm M.S. laths with 1.25 mm thick top cover

5.84

-

-

... More
Providing and fixing ball bearing for rolling shutters.

2

-

-

... More
Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:

-

-

-

... More
Profile B

-

-

-

... More
Fixing with adjustable lugs with split end tail to each jamb

775.8

-

-

... More
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.

-

-

-

... More
In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works

2241

-

-

... More
Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer.

-

-

-

... More
M.S. tube

705

-

-

... More
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).

950.4

-

-

... More
Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).

-

-

-

... More
Light shade pigment using white cement

639.36

-

-

... More
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :

-

-

-

... More
25 mm thick

1266.02

-

-

... More
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.

151.19

-

-

... More
Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete.

758.29

-

-

... More
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete.

-

-

-

... More
Size of Tile 600x600 mm

4686.98

-

-

... More
Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete.

-

-

-

... More
Size of Tile 600x600 mm

5249.08

-

-

... More
Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.

71

-

-

... More
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.

-

-

-

... More
110 mm diameter

802.85

-

-

... More
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion.

-

-

-

... More
Coupler

-

-

-

... More
110 mm

71

-

-

... More
Single tee with door

-

-

-

... More
110x110x110 mm

71

-

-

... More
Bend 87.5°

-

-

-

... More
110 mm bend

71

-

-

... More
Shoe (Plain)

-

-

-

... More
110 mm Shoe

71

-

-

... More
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete.

-

-

-

... More
110 mm

213

-

-

... More
Providing & fixing UV stabilised fiberglass reinforced plastic sheet roofing up to any pitch, including fixing with polymer coated 'J' or 'L' hooks, bolts & nuts 8mm dia. G.I plain/bitumen washers complete but excluding the cost of purlins, rafters, trusses etc. The sheets shall be manufactured out of 2400 TEX panel rovigs incorporating minimum 0.3% ultra-violet stabiliser in resin system under approximately 2400 psi and hot cured. They shall be of uniform pigmentation and thickness without air pockets and shall conform to IS 10192 and IS 12866.The sheets shall be opaque or translucent, clear or pigmented, textured or smooth as specified.

-

-

-

... More
2 mm thick flat

292.68

-

-

... More
Providing and fixing tiled false ceiling of specified materials of size 595x595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.

-

-

-

... More
GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595 mm, and 0.5 mm thick with 8 mm drop; made of G I sheet having galvanizing of 100 gms/sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending.

446.45

-

-

... More
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge.

4401.42

-

-

... More
Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames/ opening (cut outs) having area less than 0.30 sqm.The calcium silicate ceiling tile shall have NRC value of 0.50 (Minimum), light reflection 85%, non- combustible as per B.S. 476 part IV, 100% humidity resistance and also having thermal conductivity 0.043 w/ mK.

-

-

-

... More
12 mm cement plaster of mix :

-

-

-

... More
1:6 (1 cement: 6 fine sand)

10489.75

-

-

... More
15 mm cement plaster on the rough side of single or half brick wall of mix :

-

-

-

... More
1:6 (1 cement: 6 fine sand)

7784.5

-

-

... More
18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand).

2863.42

-

-

... More
White washing with lime to give an even shade :

-

-

-

... More
New work (three or more coats)

144.81

-

-

... More
Distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre, of approved manufacturer, of required shade and colour complete, as per manufacturer’s specification.

-

-

-

... More
Two or more coats on new work

58.1

-

-

... More
Finishing walls with water proofing cement paint of required shade :

-

-

-

... More
New work (Two or more coats applied @ 3.84 kg/10 sqm)

58.1

-

-

... More
Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives.

-

-

-

... More
New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm.

5757.37

-

-

... More
Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer’s specifications including appropriate priming coat, preparation of surface, etc. complete.

-

-

-

... More
On concrete work

501.61

-

-

... More
Painting with synthetic enamel paint of approved brand and manufacture to give an even shade :

-

-

-

... More
Two or more coats on new work

473.48

-

-

... More
Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour.

-

-

-

... More
Two coats

14476.91

-

-

... More
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge.

-

-

-

... More
Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix)

20

-

-

... More
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge.

24

-

-

... More
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.

-

-

-

... More
In cement mortar

125

-

-

... More
Taking out doors, windows and clerestory window shutters (steel or wood) including stacking within 50 metres lead :

-

-

-

... More
Of area 3 sq. metres and below

15

-

-

... More
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.

-

-

-

... More
For thickness of tiles 10 mm to 25 mm

550

-

-

... More
Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:

-

-

-

... More
White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests

2

-

-

... More
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :

-

-

-

... More
W.C. pan with ISI marked white solid plastic seat and lid

66

-

-

... More
Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required :

-

-

-

... More
One urinal basin with 5 litre white P.V.C. automatic flushing cistern

24

-

-

... More
Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:

-

-

-

... More
White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps

53

-

-

... More
Providing and fixing white vitreous china laboratory sink with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required :

-

-

-

... More
Size 450x300x150 mm

2

-

-

... More
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

53

-

-

... More
Providing and fixing 600x120x5 mm glass shelf with edges round off, supported on anodised aluminium angle frame with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugs etc., complete.

53

-

-

... More
Providing and fixing toilet paper holder :

-

-

-

... More
Vitreous china

66

-

-

... More
Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms.

53

-

-

... More
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed echanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :

-

-

-

... More
For fixed portion

-

-

-

... More
Powder coated aluminium (minimum thickness of powder coating 50 micron)

21231.72

-

-

... More
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)

-

-

-

... More
Powder coated aluminium (minimum thickness of powder coating 50 micron)

7077.35

-

-

... More
Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineerin- charge.

-

-

-

... More
Pre-laminated particle board with decorative lamination on both sides

158.01

-

-

... More
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):

-

-

-

... More
With float glass panes of 5 mm thickness (weight not less than 12.50 kg/ sqm)

2092.73

-

-

... More
Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.

-

-

-

... More
With stainless steel cover plate minimum 1.25 mm thickness

52

-

-

... More
Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineerin- charge complete.

-

-

-

... More
355 X 19 mm

204

-

-

... More
Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0 mm thick & 2100 mm long with SS screws etc .complete as per direction of Engineer-in-Charge.

-

-

-

... More
Powder coated minimum thickness 50 micron aluminium tubular handle bar

576

-

-

... More
Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.

52

-

-

... More
Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of:

498.21

-

-

... More
Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound conforming to IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface.

-

-

-

... More
IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface.

-

-

-

... More
IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. per sqm of area.

-

-

-

... More
IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/sqm).

-

-

-

... More
Grading roof for water proofing treatment with

-

-

-

... More
Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size)

357.5

-

-

... More
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI- 212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage.

-

-

-

... More
For vertical surface two coats @ 0.70 kg per sqm

306

-

-

... More
For horizontal surface one coat @1.10 kg per sqm.

210

-

-

... More
Providing and applying of swellable type water stop tape, 19mm x 25mm thick in linear meter (expansive nature) for construction joints treatment of RCC structure such as raft slab, retaining walls, water storage tank and at the junctions of raft slab with the retaining walls etc.. After cleaning the surface, one coat of required primer for swellable water stop tape shall be applied throughout the length of the joint @3.78 litre per 240 running meter. Over the primed surface swellable type water stop tape shall be placed. The work shall be carried out all complete as per specification and the direction of the Engineer-In-Charge. The product performance shall carry guarantee for 10 years against any leakage.

120

-

-

... More
EXTERNAL WATER SUPPLY

-

-

-

... More
Providing and fixing in trenches the following sizes of GI class `C' (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, GI nuts, bolts and washers including excavation in all kind of soil, refilling, ramming, shoring, removing the excavated surplus material, providing adequate support to the pipe and making good the same complete as required. Rate shall include for dewatering necessary to execute the work. The pipe shall not be less than 1.0 m below ground level at any point. Pipes shall embedded all round 150 mm thick compacted silver sand and protectionto GI pipes and fitting by applying pypkote primer @ 100 gm/sqm). Thereafter wrapping 4 mm thick pypkote (AW4mm) protection coating by thermo fusion process. Overlap shall be maintained at 20 mm. The application shall be strictly as per manufacturers’ specifications.

-

-

-

... More
20 mm dia

50

-

-

... More
25 mm dia

100

-

-

... More
32 mm dia

300

-

-

... More
40 mm dia

100

-

-

... More
50 mm dia

150

-

-

... More
65 mm dia

200

-

-

... More
80 mm dia

1050

-

-

... More
Constructing masonry Chamber 60x60x75cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement : 4 fine sand) for sluice valve, with C.I surface box 100mm. top diameter,160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand : 10graded stone aggregate 40mm nominal size) and inside plastering with cement mortat 1:3 ( 1cement :3 coarse sand) 12mm thick finished with a floating coat of neat cement complete as per standard design.

-

-

-

... More
With common burnt clay F.P.S.(non modular) bricks of class designation 7.5

10

-

-

... More
Constructing masonry Chamber 60x45x50 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for water meter complete with C.I. double flap surface box 400x200x200 mm (inside) with locking arrangement and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) , i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand:10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :

-

-

-

... More
With common burnt clay F.P.S.(non modular) bricks of class designation 7.5

10

-

-

... More
Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. (The tail pieces if required will be paid separately) :

-

-

-

... More
80 mm dia nominal bore

5

-

-

... More
Effecting connection from Existing/ Municipal Water Supply line including necessary excavation & making good the same including cutting, boring and tapping the Existing line by providing and installing ferrule / Tee connections with necessary fittings as required and making good the same. The rate for this item also includes complete services from the contractor for liasoning works such as filing necessary applications, submission of forms for approval to the municipal authorities, depositing the fees / other amounts as required for getting the premises / installations, inspected and approved and all other formalities required till the water connection is obtained. All the expenses incurred in this regard shall be borne by the Contractor except for the official payments to be made for any security deposit etc. which will be reimbursed on production of original voucher.

1

-

-

... More
RAIN WATER HARVESTING & TUBEWELLS

-

-

-

... More
Supply of all labour, materials, tools and appliances for the construction of Desilting tank of 2000x1500 mm and depth as required (effective depth from IL of incoming pipe) including all civil works i.e. PCC bedding, base slab, brickwalls, baffle walls, RCC top slab cover with 2 Nos of 560mm dia heavy duty CI manhole, vent pipes, plaster, foot rest including necessary excavation, backfilling and disposal of surplus soil, complete as per approved shop drawing ( detailed shop drawing to be submitted by the contractor for approval)

-

-

-

... More
Supply of all labour, materials, tools and appliances for the construction of Rain water Harvesting tank of 3000mm dia.and 3500 mm (effective depth from IL of incoming pipe) including all civil works i.e. PCC bedding under the walls, brick/RCC wall(as per structural requirements), sand / gravel / boulder filter beds/ layer of 500mm thickness each, RCC top slab cover with 2 nos of 560mm dia (heavy duty) CI manhole cover, vent pipes, plaster, foot rests including 300mm dia boring and fixing 1 nos of 160mm dia uPVC perforated pipes (to be taken 1m below the water level) and filling with pea gravels all around the perforated pipes in the bore hole including necessary excavation, backfilling and disposal of surplus soil, complete as per approved shop drawing ( detailed shop drawing to be submitted by the contractor for approval ).

-

-

-

... More
Rate of harvesting pits

8

-

-

... More
Supply of all labour, materials, tools and appliances for the construction of TUBEWELLS of 100 M Eild Depth or as/requirements. ( including necessary excavation, backfilling and disposal of surplus soil, complete as per approved shop drawing ( detailed shop drawing to be submitted by the contractor for approval ).

2

-

-

... More
EXTERNAL SEWAGE AND STORM WATER

-

-

-

... More
Excavating trenches of required width for pipes, cables etc. including excavation for sockets and dressing of sides, ramming of bottoms, depth upto 1.5 M including getting out the excavated soil, and then returning the soil as required, in layers not exceeding 20 cms in depth including consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil.

-

-

-

... More
Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia. Metre

1200

-

-

... More
Pipes, cables etc. exceeding 300 mm dia but not exceeding 600 mm

700

-

-

... More
Providing and laying cement concrete 1:5:10 mix (1 cement: 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) upto haunches for pipes including bed concrete as per standard design.

-

-

-

... More
150 mm dia.

250

-

-

... More
200 mm dia.

320

-

-

... More
300 mm dia.

120

-

-

... More
400 mm dia.

300

-

-

... More
450 mm dia.

300

-

-

... More
Providing and laying cement concrete 1:5:10 mix (1 cement: 5 coarse sand: 10 graded stone aggregate 40 mm nominal size) all round for pipes including bed concrete as per standard design.

-

-

-

... More
150 mm dia.

211

-

-

... More
200 mm dia.

199

-

-

... More
300 mm dia.

200

-

-

... More
400 mm dia.

300

-

-

... More
450 mm dia.

293

-

-

... More
Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design :

-

-

-

... More
180x150 mm size P type

-

-

-

... More
With Sewer bricks conforming to IS : 4885

95

-

-

... More
Providing and laying non pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture cement mortar in the proportion of 1:2 (1 cement: 2 fine sand) including testing of joints etc. complete.

-

-

-

... More
150 mm dia. R.C.C. pipe

320

-

-

... More
200 mm dia. R.C.C. pipe

351

-

-

... More
300 mm dia. R.C.C. pipe

320

-

-

... More
400 mm dia. R.C.C. pipe

600

-

-

... More
450 mm dia. R.C.C. pipe

593

-

-

... More
Constructing brick masonry manhole in cement mortar 1:4 (1 cement : 4 coarse sand) RCC top slab with 1:2:4 mix ( 1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:4:8 mix (1 cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement making channels in cement concrete 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design.

-

-

-

... More
Inside size 90x80 cms and 45 cms deep including CI cover with frame (Light duty) 610x455mm internal diamesions total weight of cover and frame to be not less than 38 kg ( weight of cover 23 kg and weight of frame 15 kg)

-

-

-

... More
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5

40

-

-

... More
Extra for depth for manholes : Size 90x80 cm

10

-

-

... More
Inside size 120x90 cm and 90 cm deep including C.I.cover with frame (heavy duty) 560 mm internal diameter, total weight of cover and frame to be not less than 208 kg (weight of cover 108 kg and weight of frame 100 kg) :

-

-

-

... More
With Sewer bricks conforming to IS : 4885

20

-

-

... More
Extra for depth for manholes : Size 120x90 cm

5

-

-

... More
Constructing brick masonry circular type manhole 0.91 m internal dia at bottom and 0.56m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand), inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size), and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :

-

-

-

... More
0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg., fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) :

-

-

-

... More
With Sewer bricks conforming to IS : 4885

10

-

-

... More
Extra depth for circular type manhole 0.91m internal dia (at bottom) beyond 0.91 m to 1.67 m

2

-

-

... More
Constructing brick masonry circular manhole 1.22 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement :4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand)finished with a floating coat of neat cement foundation concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and makingnecessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :

-

-

-

... More
1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade designation) 560 mm internal diameter conforming to I.S. 12592, total weight of cover and frame to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including centering, shuttering all complete. (Excavation, foot rests and 12 mm thick cement plaster at the external surface shall be paid for separately) :

-

-

-

... More
With Sewer bricks conforming IS : 4885

4

-

-

... More
Extra depth for circular type manhole 1.22 m internal dia (at bottom) beyond 1.68 m to 2.29 m :

1

-

-

... More
Constructing brick masonry circular manhole 1.52 m internal dia at bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse sand) inside cement plaster 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement, foundation concrete 1:3:6 (1cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) and making necessary channel in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement, all complete as per standard design :

-

-

-

... More
2.30 m deep with SFRC Cover and frame (heavy duty HD- 20 grade designation)560 mm internal diameter conforming to I.S. 12592, total weight of cover andframe to be not less than 182 kg. fixed in cement concrete 1:2:4 (1 cement : 2coarse sand : 4 graded stone aggregate 20 mm nominal size) includingcentering, shuttering all complete. (Excavation, foot rests and 12 mm thickcement plaster at the external surface shall be paid for separately) :

-

-

-

... More
With Sewer bricks conforming IS : 4885

4

-

-

... More
Extra depth for circular type manhole 1.52 m internal dia (at bottom) beyond 2.30 m :

-

-

-

... More
With Sewer bricks conforming IS : 4885

4

-

-

... More
Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated asper IS: 10910 on 12mm dia steel bar conforming to IS :1786 having minimun cross section as 23 mm x 25 mm and over all minimum length 263mm and width as 165mm with minimum 112mm space between protruded legs having 2mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and heaving manufacture"s permanent identification mark to be visible even after fixing " incluting fixing in manholes with 30x20x15 cm cement concrete block 1:3:6: (1 cement :3 coarse sand :6 graded stone aggregate 20mm nominal size )complete as per design.

250

-

-

... More
Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement and making necessary channels for the drain etc complete.

-

-

-

... More
For pipes 350 to 450 mm diameter

2

-

-

... More
Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design :

-

-

-

... More
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5

50

-

-

... More
Constructing brick masonry road gully chamber 110x50x77.5 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm precast R.C.C. horizontal grating with frame and vertical grating complete as per standard design :

-

-

-

... More
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5

10

-

-

... More
STP AND ETP

-

-

-

... More
Note: All works to be carried out to the relevant IS Specifications whether so mentioned in the description of works or not. Designing, Preparation of Shop Drawings, Supplying, Erection, Testing, Commissioning of all Mechanical, Electrical and other components excluding getting approval of successful test results from approved / authorized agency from Pollution & Environmental Authorities, Operating & Maintaining upto successful commissioning, commissioning of the plant with performance Guarantee for 2 years from the date of commissioning for trouble free performance for Fully automatic 150 KLD capacity Sewage Treatment Plant complete in all respects on a Turnkey Basis based on MBBR (Moving Bed Bio Reactor). The raw sewage collection sump with double bar SS screen shall be a part of the STP. All the equipment, piping, pumps, blowers and electrical Panel to be housed in a plant room also to be built below grade. M.S. puddle flange (hot dip galvanized after fabrication), inlet, outlet, overflow, vent, M.S. cover, drain channel with M.S. gratings, sump to house pumps manufacturer's design and specification. STP Plant shall be include all plant and equipment mentioned in the specification including ACF, MGF, UF etc complete.(Exclude Civil cost.)

-

-

-

... More
Design, Built, Supply Insttalation, Testing & commisioning of ETP Capacity 25 Kld along with 2 year operation & matenance based on following specification (Exclude Civil cost.)

1

-

-

... More
WTP

-

-

-

... More
Designing, Preparation of Shop Drawings, Supplying, Erection, Testing, Commissioning of all Mechanical, Electrical and 180 KLD capacity water Treatment Plant (WTP.) complete including All the equipment, piping, pumps, blowers and electrical Panel to be housed in a plant room ,pumps manufacturer's design and specification. WTP Plant shall be include all plant and equipment mentioned in the specification including ACF, MGF, UF etc complete.(Exclude Civil cost.)

1

-

-

... More
SOLAR WATER HEATING SYSTEM.

-

-

-

... More
4000 LPD FPC solar water heating system, with 2.0mm SS Inner Tank and GI Pre Coated Outer Cladding after 50mm PUF Insulation and with provision of 8x3KW Electrical Heater. The tank stand of MS Hot Dip Galvanised frame of suiltable size. With 6Nos. Flat Plate Collector shall be copper based - with copper tubes and copper fins as per MNRE specification and as per IS12933. Collector approx size 2080mmx1070mmx100mm each (100 litres/day capacity). Complete with suitable MS Powder Coated Stand. Including Non Return Valve, Three Gate Valve for Tank and Collector, Temperature Gauge, System Internal Piping and Air Vent of system with height as per cold water tank.Excluding minimum civil work of grouting for 4000LPD FPC solar water heating system. (ASSUMED.)(MAKE-Nova Energie,visuta,solahart.)

1

-

-

... More
SANITARY FIXTURES

-

-

-

... More
Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :

-

-

-

... More
W.C. pan with ISI marked white solid plastic seat and lid

69

-

-

... More
Providing and Fixing 2 Nos. support arms and backrest to mounted on the track (vertically and laterally) for handicap toilet complete as required.

4

-

-

... More
Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:-

-

-

-

... More
(a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer

62

-

-

... More
PROVIDING AND FIXING IN POSITION INDIAN MAKE (ORDINARY) LAVATORY SUITES Conisting of Lavatory in VITREOUS CHINAWARE size as given Below (to the approval of the Engineer-in-charge) including china plug for tap hole where necessary; R.S or C.I BRACKETS for building into wall including Painting; 32 mm C.P BRASS WASTER WITH C.P brass chain and rubber plug; 15 mm dia CP Brass single hole basin mixer Jamnuts or couplings best design ( as approved by the Engineer- In-charge)

-

-

-

... More
WHITE

-

-

-

... More
PROVIDING AND FIXING IN POSITION BEST INDIAN MAKE LAVATORY SUITES (WITH ANTI SPLASH RIM IN VITREOUS CHINAWARE and all other necessary fittings as fully described in item no. 30.41 above.

-

-

-

... More
Size 530 mm x 430 mm with one no. trap.

9

-

-

... More
Providing and fixing stainless steel A ISI 304 (18/8) Kitchen Sink as per IS : 13983 with CI bracket and stainless steel plug 40 mm including painting of fittings and brackets ,cutting and making good the walls wherever required:

-

-

-

... More
Kitchen sink without drain board

-

-

-

... More
610x510 mm bowl depth 200 mm (Assume for pantry)

8

-

-

... More
providing and fixing cp brass 32mm size bottle trap of approved quality & make and as per the direction of engineer-in-charg

-

-

-

... More
32 mm dia

62

-

-

... More
40 mm dia

8

-

-

... More
Providing Sink mixer (wall mounted) with 170mm long swivel spout connecting legs and wall flanges((CERA Cat. No. OCEAN F3002501 or approved equivalent) .

8

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing and fixing Braided Hoses with Two 15mm CP Brass Nuts & Rubber Washers Without Nipple (Suitable for Geysers and basins) of approved make :

-

-

-

... More
45 cm length

-

-

-

... More
15 mm nominal bore

396

-

-

... More
Providing and fixing toilet paper holder :

-

-

-

... More
CP Brass

69

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing,Fixing,testing and commissioning of CP brass twin coat hook with concealed screws.

69

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing and Fixing Health Faucet 15mmdia with CP flush pipe, CP nozzel hook complete including CP flange etc.

69

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing & fixing C.P. brass towel rail with C.P. brass wall brackets & C.P brass screws complete as requiredSIZE 600MM X200MM (CERA CAT. NO. F5004103 or approved equivalent )

-

-

-

... More
Size 600 x 20 mm size

32

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing,Fixing,testing and commissioning of CP brass towel ring hook with concealed screws.

62

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet : (CERA CAT.NO. F7020304 ) & shower arm 180 mm (CERA CAT. NO. F7040101 or approved equivalent) including all necessary fittings complete.SIZE 100 mm diameter

32

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
providing and fixing CP Brass Single lever telephonic wall mixer of quality &make as approved by engineer in charge.

-

-

-

... More
15 mm nominal bore

32

-

-

... More
Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931

-

-

-

... More
15 mm nominal bore

396

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing and fixing soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements,weighing not less than 106 gms.

71

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing fixing and testing of approved quality AUTOMATIC HAND DRYER 235X205X265mm (Stainless Steel) B2220101

26

-

-

... More
Providing and fixing horzontal/vertical Hot water geyser made of MS body with copper jacket inside with necessary inlet, outlet, drain, overflow, vent and all safety accessories etc. complete including cutting and making good the walls, wherever required.

-

-

-

... More
15 lit for Kitchen(assume for kitchen)

8

-

-

... More
25 lit for Shower

51

-

-

... More
Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.

25

-

-

... More
Providing and fixing URINAL PARTITION (CERA CAT. NO. S4090101 or approved equivalent)

32

-

-

... More
Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

71

-

-

... More
Providing and fixing C.P. brass/ SS long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms.

-

-

-

... More
15 mm nominal bore

69

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Providing and fixing C.P. brass/ SS stop cock (concealed) of standard design and of approved make conforming to IS:8931.

-

-

-

... More
15 mm nominal bore(fr drinking area)

14

-

-

... More
CERA,PLAYER,HINDWARE

-

-

-

... More
Supply installation testing and commissioning water cooler having nominal cooling capacity of 40 litres per hours, with 40 litres storage tank with 2 nos. of faucets, one on goose neck type and other one fountain type both with separate mechanical lever control with 1.5 HP electric motor for compressor to work on one phase 230 volts 50 Hz AC power supply with complete assessories including cutting and making wall as required.(Assume for drinking points)

5

-

-

... More
SOIL, WASTE, VENT & RAIN WATER PIPES

-

-

-

... More
Providing and fixing soil, waste and vent pipes :

-

-

-

... More
100mm dia

-

-

-

... More
Hubless centrifugally cast (spun) iron pipes epoxycoated inside & outside IS:15905

1406

-

-

... More
75mm dia

-

-

-

... More
Hubless centrifugally cast (spun) iron pipes epoxycoated inside & outside IS:15905( for vent )

145

-

-

... More
Approved Make- SKF,HEPCO,NECO--FOR C.I PIPE

-

-

-

... More
Providing and filling the joints with spun yarn, cement slurry and cement mortar 1:2 ( 1 cement : 2 fine sand) in S.C.I./ C.I. Pipes :

-

-

-

... More
100 mm dia pipe

320

-

-

... More
Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including cost of cutting holes and making good the walls etc. :

-

-

-

... More
100mm dia pipe

852

-

-

... More
Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete.

-

-

-

... More
100mm dia

-

-

-

... More
Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905

200

-

-

... More
Providing and fixing plain bend of required degree.

-

-

-

... More
100mm dia

-

-

-

... More
Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905

222

-

-

... More
Providing and fixing double equal plain junction of required degree.

-

-

-

... More
100x100x100x100 mm

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

105

-

-

... More
Providing and fixing single equal plain junction of required degree :

-

-

-

... More
100x100x100xmm

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

222

-

-

... More
75x75x75mm dia

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

44

-

-

... More
Providing and fixing double equal plain junction of required degree.

-

-

-

... More
100x100x75x75 mm

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

70

-

-

... More
Providing and fixing double equal plain junction of required degree.

-

-

-

... More
100x100x75

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

42

-

-

... More
Providing and fixing double equal plain junction of required degree.

-

-

-

... More
100x100x100mm

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

98

-

-

... More
Providing and fixing Hubless centrifugally cast iron offsets epoxy coated inside & outside as per IS:15905

-

-

-

... More
65mm offset

-

-

-

... More
with 100mm dia pipe

100

-

-

... More
Providing and fixing terminal guard :

-

-

-

... More
100mm

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

50

-

-

... More
Providing and fixing shielded coupling for Hubless centrifugally cast iron pipe

-

-

-

... More
100MM dia

-

-

-

... More
SS 304 grade coupling with EPDM rubber gasket

908

-

-

... More
75 mm dia

-

-

-

... More
SS 304 grade coupling with EPDM rubber gasket

180

-

-

... More
Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors :

-

-

-

... More
100 mm inlet and 100 mm outlet

-

-

-

... More
Hubless centrifugally cast (spun) ironpipes epoxy coated inside & outside IS:15905

172

-

-

... More
Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof.

247

-

-

... More
Providing and fixing heel rest sanitary bend

-

-

-

... More
100 mm dia

-

-

-

... More
Sand cast iron S&S as per IS - 3989

70

-

-

... More
75 mm dia

-

-

-

... More
Sand cast iron S&S as per IS - 3989

21

-

-

... More
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc.(For waste connection from wb/sink/ut)

-

-

-

... More
32 mm nominal bore

106

-

-

... More
40 mm nominal bore

106

-

-

... More
50 mm nominal bore

90

-

-

... More
Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work

-

-

-

... More
32 mm nominal bore

86

-

-

... More
40 mm nominal bore

86

-

-

... More
50 mm nominal bore

67

-

-

... More
Providing and fixing GI. inlet hopper of C class pipe with two or three inlets fittings, connection with saddle, to receive waste pipes from fixtures waste.

59

-

-

... More
Providing and fixing SS grating with frame including fixing to the floor with cement mortar.

-

-

-

... More
100mm dia

229.86

-

-

... More
Providing & fixing of cast brass clean out plug with suitable insert keys for opening in: brass cap, male threaded joint with threaded G.I socket fixed to HCI soil pipe or C.I.(LA) pipe joints as required complete in all respects.

-

-

-

... More
100 mm dia

140

-

-

... More
Providing and fixing floor drain points formed out of 100 X 50mm dia reducing elbow embedded in floor,all completein all respect as directed.

119

-

-

... More
Providing and fixing chlorinated polyvinyl chloride (CPVC) pipe having thermal stability for hot and cold water supply, including all CPVC plain and brass threaded fittings, including fixing i/c fixing the pipe with clamp at 1.0M spacing. this include joints of pipes and fittings with one stap CPVC solvent cement and the cost of cutting chases making good the same includind testing of joints complete as per direction of engineer in charge.

-

-

-

... More
Concealed work including cutting chases and making good the wall.

-

-

-

... More
15 mm dia nominal bore

235

-

-

... More
20 mm dia nominal bore

140

-

-

... More
25 mm diameter pipe

170

-

-

... More
32 mm diameter pipe

75

-

-

... More
Providing and fixing GI pipes complete with GI fitting and clamps i/c cutting and making good the walls. Internal work - Exposed on wall/terrace

-

-

-

... More
25 mm dia. nominal bore

230

-

-

... More
32 mm dia. nominal bore

290

-

-

... More
40 mm dia. nominal bore

220

-

-

... More
50 mm dia. nominal bore

160

-

-

... More
65 mm dia. nominal bore

110

-

-

... More
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete

-

-

-

... More
20 mm nominal bore

15

-

-

... More
25 mm nominal bore

85

-

-

... More
32 mm nominal bore.

80

-

-

... More
40 mm nominal bore

31

-

-

... More
Painting G.I. pipes and fittings with synthetic enamel white paintwith two coats over a ready mixed priming coat, both of quality for new work :

-

-

-

... More
25 mm diameter pipe

230

-

-

... More
32 mm diameter pipe

285

-

-

... More
40 mm diameter pipe

220

-

-

... More
50 mm diameter pipe

161.1

-

-

... More
65mm diameter pipe

114

-

-

... More
Providing and fixing proprietary polyshield outer mechanical protection ON nitrile rubber insulation comprising of wrapping with poly glass tape helically wound and subsequently applying 2 coats of polyshield material (resin & hardner) as per manufacturers specification and approved by Project Manager / Consultants.

-

-

-

... More
25 mm dia. nominal bore(19 mm thick insulation)(assume for pantry.)

192

-

-

... More
32 mm dia.(19 mm thick insulation)

302

-

-

... More
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required

-

-

-

... More
65 mm nominal bore

10

-

-

... More
80 mm nominal bore

6

-

-

... More
Providing and fixing C.I. dirt box strainer for bulk type water meterwith nuts, bolts, rubber insertions etc. complete conforming to IS :2373:00:00

-

-

-

... More
80 mm dia

7

-

-

... More
Providing and fixing gun metal non- return valve of approved quality (screwed end) :

-

-

-

... More
25 mm nominal bore

-

-

-

... More
Horizontal

2

-

-

... More
Vertical

-

-

-

... More
32 mm nominal bore

-

-

-

... More
Horizontal

6

-

-

... More
Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. (The tail pieces if required will be paid separately) :

-

-

-

... More
80 mm dia nominal bore

3

-

-

... More
Providing and fixing C.I. dirt box strainer for bulk type water meter with nuts, bolts, rubber insertions etc. complete conforming to IS :2373

-

-

-

... More
80 mm dia

5

-

-

... More
Disinfecting C.I. water mains by flushing with water containing bleaching powder @ 0.5 gms per litre of water and cleaning the same with fresh water, operation to be repeated three times including getting the sample of water from the disinfected main tested in the municipal laboratory.

-

-

-

... More
80 mm diameter C.I. pipe

3

-

-

... More
Providing and fixing of approved make float operated ball valve with Brass/copper heavy duty float confirming to IS 9762 & other associated accessories & works etc., complete. For 80mm dia pipe

8

-

-

... More
Below all item's bill of quantily line specification shall be followed strictly, These specification with supersede tender specifications. Any deviation required due to any causes, prior approval is required from engineering incharge.

-

-

-

... More
WIRING

-

-

-

... More
The measurement shall be given only after completing the job of points opening and laying of fish wires.

-

-

-

... More
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.

-

-

-

... More
Group C

369

-

-

... More
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.

-

-

-

... More
Group C

420

-

-

... More
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.

-

-

-

... More
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire(in minimum 20mm)

2380

-

-

... More
2 X 4 sq. mm +1 X 4 sq. mm earth wire(in minimum 20mm)

3666

-

-

... More
4 X 6 sq. mm + 2 X 6 sq. mm earth wire(in minimum 32mm)

1114

-

-

... More
4 X 10 sq. mm + 2 X 6 sq. mm earth wire(in minimum 40mm)

245

-

-

... More
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.

-

-

-

... More
3 x 1.5 sq. mm

1764

-

-

... More
3 x 2.5 sq. mm

550

-

-

... More
3 x 4 sq. mm

2746

-

-

... More
3 x 6 sq. mm

-

-

-

... More
1 x 35sq. mm

155

-

-

... More
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.

-

-

-

... More
20 mm

449

-

-

... More
25 mm

575

-

-

... More
32 mm

150

-

-

... More
40 mm

25

-

-

... More
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required.

-

-

-

... More
100 mm X 100 mm X 60 mm deep

16

-

-

... More
150 mm X 150 mm X 60 mm deep

11

-

-

... More
200 mm X 250 mm X 60 mm deep

6

-

-

... More
250 mm X 300 mm X 60 mm deep

4

-

-

... More
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.

9

-

-

... More
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.

162

-

-

... More
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/6 A modular switch, connections etc. as required. (For light plugs to be used in Labs).

176

-

-

... More
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.

222

-

-

... More
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.

293

-

-

... More
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required.

-

-

-

... More
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.

-

-

-

... More
TV antenna socket outlet

-

-

-

... More
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.

-

-

-

... More
1 or 2 Module (75mm X 75mm)

-

-

-

... More
Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required.

2

-

-

... More
Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required.

-

-

-

... More
TOTAL CARRIED SUMMARY

-

-

-

... More
DISTRIBUTION BOARDS

-

-

-

... More
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)

-

-

-

... More
8 way, Double door

-

-

-

... More
12 way, Double door

2

-

-

... More
16 way, Double door

-

-

-

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)

-

-

-

... More
6 way (4 + 18), Double door

10

-

-

... More
8 way (4 + 24), Double door

21

-

-

... More
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
Single pole

500

-

-

... More
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.

99

-

-

... More
Supplying and fixing following rating, double pole, 240 V, MCB(10kA) in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
25A

2

-

-

... More
40A

-

-

-

... More
Supplying and fixing following rating, four pole, 415 V, MCB(10kA) in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
40A

32

-

-

... More
63A

2

-

-

... More
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
25A

2

-

-

... More
40A

95

-

-

... More
63A

7

-

-

... More
Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required.

-

-

-

... More
For 10 way, Double door SPN MCBDB

2

-

-

... More
Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.

-

-

-

... More
For 6 way, Double door TPN MCBDB

10

-

-

... More
For 8 way, Double door TPN MCBDB

21

-

-

... More
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.

5

-

-

... More
Supplying and fixing 20 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.

2

-

-

... More
Design, fabrication, assembling, wiring, supply, installation, testing & commissioning of (IP:30, IK 08) minimum 1.2mm thick sheet steel DP/TP/FP MCB/ Isolator enclosure conforming to IS: 8623-1 & 3 & IEC 61439- 1&3, made out of pre-treated and powder coated (minimum 60-80 micron), 240/415 V, mount on surface / recess, complete with din bar including earthing stud etc. as standard or as suggested by Architect/Consultant. (But without MCB/RCCB/Isolator).

7

-

-

... More
Supply, fixing, testing and commissioning of single spike air terminals of 10 mm dia.of 1Meter long as required and as per site conditions. the air terminal shall be manufactured with aluminium. The terminal shall be provided with the integrated / attached threaded base support suitable for mounting the terminals as per site condition. The base support shall be minimum 3 mm thick and shall have inbuilt connector fitting for connection of lightning conductor in such a way that conductor contact area shall not be less than 40mm on all side of the conductor as per IS/IEC 62305.

10

-

-

... More
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required.(For horizontal run)

638

-

-

... More
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or on surface of wall for lightning conductor complete as required. (For vertical run)

278

-

-

... More
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc. as required.

305

-

-

... More
Supply, fixing, testing and commissioning of Lightning counter indicating date and time of last record In-addition having to see previous history of surges etc complete as required to meet requirements to IS/IEC 62561-1 etc. complete as required

3

-

-

... More
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 Nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.

18

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

-

-

-

... More
450 mm width X 50 mm depth X 2.0 mm thickness

94

-

-

... More
300 mm width X 50 mm depth X 1.6 mm thickness

78

-

-

... More
150 mm width X 50 mm depth X 1.6 mm thickness

110

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “bends” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

-

-

-

... More
450 mm width X 50 mm depth X 2.0 mm thickness

16

-

-

... More
300 mm width X 50 mm depth X 1.6 mm thickness

10

-

-

... More
150 mm width X 50 mm depth X 1.6 mm thickness

31

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Tee” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

-

-

-

... More
450 mm width X 50 mm depth X 2.0 mm thickness

9

-

-

... More
300 mm width X 50 mm depth X 1.6 mm thickness

6

-

-

... More
150 mm width X 50 mm depth X 1.6 mm thickness

39

-

-

... More
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray “Reducer” (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.

-

-

-

... More
450 mm width X 50 mm depth X 2.0 mm thickness

6

-

-

... More
300 mm width X 50 mm depth X 1.6 mm thickness

12

-

-

... More
Supply of Recess Mounted Round Led Downlighter consuming a system wattage of 12W (±10%) & the luminaire shall be with system efficacy ≥ 100 lm / W. Housing: Die Cast Aluminium. IP20 , Optics: PMMA/Polysterene Diffuser. The operating CCT shall be 5700K with CRI of ≥80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD ≤ 10% & PF ≥ 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacturer along with Photo Biological Safety Standard.

109

-

-

... More
Supply of Recess Mounted Round Led Downlighter consuming a system wattage of 18W (±10%) & the luminaire shall be with system efficacy ≥ 100 lm / W. Housing: Die Cast Aluminium. IP20 , Optics: PMMA/Polysterene Diffuser. The operating CCT shall be 5700K with CRI of ≥80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD ≤ 10% & PF ≥ 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacturer along with Photo Biological Safety Standard.

204

-

-

... More
Supply of Surface Mount Round Led Downlighter consuming a system wattage of 18W (±10%) & the luminaire shall be with system efficacy ≥ 100 lm / W. Housing: CRCA Powder Coated. IP20 , Optics: PMMA/Polysterene Diffuser. The operating CCT shall be 5700K with CRI of ≥80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD ≤ 10% & PF ≥ 0.9, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacture along with Photo Biological Safety Standard.

140

-

-

... More
Supply of 4ft Linear LED luminaire delivering an initial system lumen of 4000 lumens & the luminaire shall be with system efficacy ≥ 100 lm / W. The luminaire Housing shall be made of CRCA & the diffuser shall be of polycarbonate/PMMA. The operating CCT shall be 5700K with CRI of ≥80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD ≤ 10% & PF ≥ 0.95 , 50,000 Hrs LED Life with L70 Criteria, IP20. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacture along with Photo Biological Safety Standard.

158

-

-

... More
Supply of Bulk Head Luminare delivering an initial system lumen of 700 lumens & the luminaire shall be with system efficacy ≥ 70 lm / W. Housing: Die Cast Aluminium. IP65 , Diffuser : OPAL Polycarbonate. The operating CCT shall be 5700K with CRI of ≥70. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD ≤ 10% & PF ≥ 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacture along with Photo Biological Safety Standard.

40

-

-

... More
Supply of 2ft Linear LED luminaire delivering an initial system lumen of 903 lumens & the luminaire shall be with system efficacy ≥ 90 lm / W. The luminaire Housing shall be made of PC & the diffuser shall be of polycarbonate/PMMA. The operating CCT shall be 6500K with CRI of ≥80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD ≤ 20% & PF ≥ 0.95 , 50,000 Hrs LED Life with L70 Criteria, IP20. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacture along with Photo Biological Safety Standard. (Similar to Wipro Cat No.: LL20-111-XXX-65-NE or equivalent as per approved list of make)

267

-

-

... More
Supply of Recess mounted LED 2'x2' luminaire delivering an initial system lumen of 3300 lumens & the luminaire shall be with system efficacy ≥ 100 lm / W. Housing: CRCA, Rim: Engneering plastic / CRCA. Optics: polycarbonate/PMMA/Polysterene, IP20 Protection. The operating CCT shall be 5700K with CRI of ≥80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD ≤ 10% & PF ≥ 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79 & LM80 issued by LED manufacture along with Photo Biological Safety Standard.

357

-

-

... More
Supply of 3W LED Unidirectional Exit Signage Light with inbuilt 2hours battery back up .

13

-

-

... More
Supply of 5 star rated 1200mm sweep ceiling fan, ISI marked, along with copper wound stator, blades, capacitor, downrod etc. but without regulator complete as required.

293

-

-

... More
Supply of 300mm dia sweep PVC body, 900±10% RPM Exhaust fan with guard and mounting arrangement.

28

-

-

... More
Supply of 450mm dia sweep wall fan Hi speed with 3 speed push buttons, 1440 RPM, with guard and mounting arrangement.

10

-

-

... More
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.

1235

-

-

... More
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.

294

-

-

... More
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.

-

-

-

... More
Upto 450 mm sweep

28

-

-

... More
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required.

1161

-

-

... More
Supplying and fixing extra down rod of 10 cm length G.I. pipe,15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)

293

-

-

... More
Supplying, installation, testing & commissioning of intelligent analog addressable photothermal detector complete with mounting base complete as required.

349

-

-

... More
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required.

5

-

-

... More
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required.

160

-

-

... More
Supplying,installation,testing & commissioning of addressable manual call point complete as required.

11

-

-

... More
Supplying, installation, testing & commissioning of fault isolator complete with base as required.

14

-

-

... More
Supplying, installation, testing & commissioning of addressable fire Monitor modual complete with base as required.

6

-

-

... More
Supplying, installation, testing & commissioning of addressable fire control modual complete with base as required.

6

-

-

... More
Supplying, installation, testing & commissioning of addressable Relay module complete with base as required.

7

-

-

... More
Supplying,installation, testing & commissioning of addressable horne cum strobe complete as required.

11

-

-

... More
Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.

172

-

-

... More
Supplying, installation, testing & commissioning of 1.5/3/6W metal box ceiling/wall speakers complete as required.

172

-

-

... More
Supplying & laying of 2x1.5 sqmm fire survival armoured cable, 600/1000V rated with annealed copper conductor having glass mica fire barrier tape covered by an extruded layer of Cross Linkable Ethylene Propylene Rubber (EPR) insulation and LSZH inner bedding, steel wire armouring & LSZH outer sheath complete as required.

4755

-

-

... More
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.

-

-

-

... More
2 x 1.5 sq. mm

237

-

-

... More
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.

-

-

-

... More
25 mm

518

-

-

... More
TOTAL CARRIED SUMMARY

-

-

-

... More
IT/ NETWORKING, & CCTV SYSTEM-CONDUTING

-

-

-

... More
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.

-

-

-

... More
25 mm

11265

-

-

... More
TOTAL CARRIED SUMMARY

-

-

-

... More
IT/ NETWORKING & CCTV SYSTEM-ACTIVE & PASSIVE COMPONENT

-

-

-

... More
PASSIVE COMPONENT

-

-

-

... More
Supply , Installtion , Testing and comissioning of CAT 6A U/UTP LSZH cable solid copper conductor with Penta testing, Documentation & Certification (for DATA).

13365

-

-

... More
Supply , Installtion , Testing and comissioning of CAT6A U/UTP information outlet (I/O) for Data, & CCTV Outlet

222

-

-

... More
Supply , Installtion , Testing and comissioning of CAT6A LSZH patch cord 3 feet for rack side switch termination for Data,Wifi & CCTV Outlet

222

-

-

... More
Supply , Installtion , Testing and comissioning of CAT6A LSZH patch cord 7 feet for user termination to information outlet for for Data,Wifi & CCTV Outlet

222

-

-

... More
Supply , Installation , Testing and commissioning of Intelligent Ready loaded 24 port CAT6A U/UTP Jack Panel  for CAT6A cable termination. For DATA

9

-

-

... More
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.

-

-

-

... More
1 run of cable

333

-

-

... More
2 run of cable

499

-

-

... More
3 run of cable

665

-

-

... More
Supply , Installtion , Testing and comissioning of CAT6 U/UTP information outlet (I/O) For VOICE

60

-

-

... More
Supply , Installation , Testing and commissioning of CAT6 U/UTP LSZH patch cord 3 feet for rack side switch termination For VOICE

60

-

-

... More
Supply , Installation , Testing and commissioning of CAT6 LSZHpatch cord 7 feet for rack side switch For VOICE termination

60

-

-

... More
Supply , Installation , Testing and commissioning of Intelligent Ready loaded 24 port CAT6 U/UTP Jack Panel  for CAT6 cable termination. For VOICE

3

-

-

... More
1 or 2 Module

222

-

-

... More
Supply, Installation, Testing & Commissioning of 2 MP fixed lense IP Dome Camera Image Sensor:1/2.8" Progressive Scan CMOS, Signal System: PAL/NTSC, Min. Illumination: Color: 0.01 Lux @(F1.2; AGC ON), 0.028 Lux @(F2.0; AGC ON), Shutter time: 1/3 s to 1/100,000 s, Slow shutter: Support, Lens: 2.8 mm, horizontal FOV: 114°, vertical FOV: 62°, diagonal FOV: 135°, Lens Mount: M12, Adjustment Range: Pan: 0° to 355°, tilt: 0° to 75°, Day& Night: IR cut filter with auto switch, Wide Dynamic Range: Digital WDR, Digital noise reduction: 3D DNR, Video Compression: H.265+/H.265/H.264+/H.264/MJPEG, Video bit rate: 32Kbps~8Mbps, Max. Image Resolution: 1920 x 1080, Image Enhancement: BLC/3D DNR, ROI: 1 fixed region for main stream and sub-stream, Day/Night Switch: Auto/Scheduled/Day/Night, Alarm Trigger: Motion detection, video tampering alarm, network disconnected, IP address conflict, illegal login, HDD full, HDD error, General Function: One-key reset, Anti-Flicker, heartbeat, mirror, password protection, privacy mask, Watermark, IP address filtering, System Compatibility: ONVIF (Profile S, Profile G),ISAPI, Audio: 1 Built-in mic, mono sound, Operating Conditions: -30 °C ~ 60 °C (-22 °F ~ 140 °F) Humidity 95% or less (non-condensing), Power Consumption: 12 VDC, 0.4 A, Max: 5W, Weather Proof: IP66, IR Range: Up to 30m, Signal System: PAL/NTSC Min. Illumination: Color: 0.01 Lux @(F1.2; AGC ON), 0.028 Lux @(F2.0; AGC ON) Shutter time: 1/3 s to 1/100,000 s, horizontal field of view: 86°, vertical FOV: 46°, diagonal FOV: 102°

9

-

-

... More
Supply, Installation, Testing & Commissioning of 2 MP fixed lense IP Bullet Camera Image Sensor:1/2.8" Progressive Scan CMOS, Signal System: PAL/NTSC, Min. Illumination: Color: 0.01 Lux @(F1.2; AGC ON), 0.028 Lux @(F2.0; AGC ON), Shutter time: 1/3 s to 1/100,000 s, Slow shutter: Support, Lens: 2.8-12 mm, horizontal FOV: 114°, vertical FOV: 62°, diagonal FOV: 135°, Lens Mount: M12, Adjustment Range: Pan: 0° to 355°, tilt: 0° to 75°, Day& Night: IR cut filter with auto switch, Wide Dynamic Range: Digital WDR, Digital noise reduction: 3D DNR, Video Compression: H.265+/H.265/H.264+/H.264/MJPEG, Video bit rate: 32Kbps~8Mbps, Max. Image Resolution: 1920 x 1080, Image Enhancement: BLC/3D DNR, ROI: 1 fixed region for main stream and sub-stream, Day/Night Switch: Auto/Scheduled/Day/Night, Alarm Trigger: Motion detection, video tampering alarm, network disconnected, IP address conflict, illegal login, HDD full, HDD error, General Function: One-key reset, Anti-Flicker, heartbeat, mirror, password protection, privacy mask, Watermark, IP address filtering, System Compatibility: ONVIF (Profile S, Profile G),ISAPI, Audio: 1 Built-in mic, mono sound, Operating Conditions: -30 °C ~ 60 °C (-22 °F ~ 140 °F) Humidity 95% or less (non-condensing), Power Consumption: 12 VDC, 0.4 A, Max: 5W, Weather Proof: IP66, IR Range: Up to 30m, Signal System: PAL/NTSC Min. Illumination: Color: 0.01 Lux @(F1.2; AGC ON), 0.028 Lux @(F2.0; AGC ON) Shutter time: 1/3 s to 1/100,000 s, horizontal field of view: 86°, vertical FOV: 46°, diagonal FOV: 102°

19

-

-

... More
Supply,Installation Testing and Commissioning of Microprocessor controller Nurses station with terminal monitor with in built power supply , with charger enclosed in a powder coated cabinet . Having with Reset, alarm/ buzzer, Call acknowledge with battery back up, battery charger complete system as per technical specifications and as per required of following suitable configuration. complte as required.Make-Daksh

-

-

-

... More
24 Way

2

-

-

... More
16 Way

3

-

-

... More
Supply Installation Testing & Commissioning of Bed Call Push Button with LED indication and Flexiable Cord with button , Call Reset , Call Indication, station for each Bed complete as required.Make-Daksh

172

-

-

... More
Supply Installation Testing & Commissioning of LED Indicators Module at Outside of each ward complete as required.Make-Daksh

4

-

-

... More
Supplying & Laying of 4-pair Unshielded twisted pair with a cross filler (+), meeting Category 6 standards as per TIA-568C.2, The cable should be tested till 250 MHz , Shall be Fire-Retardant, Low-Smoke & Zero-Halogen as per IEC 60332-1, IEC 61034-2 & IEC 60754-1 respectively in the existing surface/ recessed Steel/ PVC conduit as required.

4950

-

-

... More
S& F 20mm rigid non mettalic PVC conduit exclusive of Boxes ( Juntion/terminal) but inclusive of all Tee's, bends, elbows, reducers, bell mouth tube ends and fixing acessories such as couplers, lock nuts, saddles, pipe hooks etc.

2150

-

-

... More
S & F junction box ( 1 to 4 way) 20mm external dia

6

-

-

... More
S & F modular metal flush box 1/2Module

172

-

-

... More
External electrical

-

-

-

... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.

84

-

-

... More
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke and salt as required.

33

-

-

... More
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.

330

-

-

... More
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

374

-

-

... More
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.

319

-

-

... More
Providing and fixing 32 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required.

60

-

-

... More
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.

8250

-

-

... More
Providing and fixing 32 mm X 6 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.

150

-

-

... More
Supply of following sizes of Power Cables multi stranded Aluminium conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath , Armour, FRLS at outer sheath,1100V grade as per IS 7098(Part 1) 1988 with upto date amendments.

-

-

-

... More
4 CORES

-

-

-

... More
4 x 10 sq.mm.

450

-

-

... More
3.5 CORES

-

-

-

... More
3.5 x 50 sq.mm.

431

-

-

... More
3.5 x 70 sq.mm.

58

-

-

... More
3.5 x 95 sq.mm.

414

-

-

... More
3.5 x 120 sq.mm.

771

-

-

... More
3.5 x 150 sq.mm.

575

-

-

... More
3.5 x 185 sq.mm.

1679

-

-

... More
3.5 x 300 sq.mm.

1518

-

-

... More
Supply of following sizes of Power Cables multi stranded Copper conductor, XLPE Insulated, cores laid up PVC tape / Extruded Inner sheath , Armour, FRLS at outer sheath,1100V grade as per IS 7098(Part 1) 1988 with upto date amendments.

-

-

-

... More
4 CORES

-

-

-

... More
4x 4 sq.mm.

2450

-

-

... More
4x 6 sq.mm.

144

-

-

... More
4x 10 sq.mm.

2013

-

-

... More
4x 16 sq.mm.

1438

-

-

... More
2 CORES

-

-

-

... More
10 sq.mm. Cu Ar. XLPE cable

125

-

-

... More
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on cable tray as required.

-

-

-

... More
Upto 35 sq. mm (clamped with 1mm thick saddle)

6170

-

-

... More
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)

489

-

-

... More
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)

585

-

-

... More
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)

415

-

-

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required.

-

-

-

... More
Upto 35 sq. mm

450

-

-

... More
Above 35 sq. mm and upto 95 sq. mm

200

-

-

... More
Above 95 sq. mm and upto 185 sq. mm

2430

-

-

... More
Above 185 sq. mm and upto 400 sq. mm

980

-

-

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required

-

-

-

... More
3½ X 50 sq. mm (35mm)

12

-

-

... More
3½ X 70 sq. mm (38mm)

4

-

-

... More
3½ X 95 sq. mm (38mm)

8

-

-

... More
3½ X 120 sq. mm (45 mm)

6

-

-

... More
3½ X 150 sq. mm (50 mm)

18

-

-

... More
3½ X 185 sq. mm (57mm)

16

-

-

... More
3½ X 300 sq. mm (70mm)

40

-

-

... More
Supplying and making end termination with brass compression gland and copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required.

-

-

-

... More
2C X 10 sq. mm (19mm)

8

-

-

... More
4C X 10 sq. mm (25mm)

120

-

-

... More
4C X 4 sq. mm (25mm)

180

-

-

... More
4C X 6 sq. mm (25mm)

12

-

-

... More
4C X 16 sq. mm (28mm)

80

-

-

... More
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.

-

-

-

... More
63 mm dia (OD-63 mm & ID-51 mm nominal)

500

-

-

... More
120 mm dia (OD-120 mm & ID-103 mm nominal)

50

-

-

... More
160 mm dia (OD-160 mm & ID-135 mm nominal)

75

-

-

... More
200 mm dia (OD-200 mm & ID-175 mm nominal)

40

-

-

... More
Supply of 11kV (E) 3Core 240 sq. mm Stranded Compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with extruded Semi Conducting Compound in combination with Copper Tape (0.2kA for 1 sec/Core), cores laid up, innersheath/Outer of FRLS PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed Cable conforming to IS 7098 / (PART-II) 1985 with latest amendments.

70

-

-

... More
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 kV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc. as required.

-

-

-

... More
Above 120 sq. mm and upto 400 sq. mm

70

-

-

... More
Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 kV grade as required.

-

-

-

... More
240 sq. mm

5

-

-

... More
TOTAL CARRIED SUMMARY

-

-

-

... More
Supply of LED street light with high pressure die cast Aluminium/ standard alloy/ CRCA housing with Polycarbonate diffuser with integral constant current driver input operating voltage range 150V – 270V 50Hz AC supply, prewired upto the terminal block. System lumen output ≥ 4500 lumens with luminaire efficacy ≥ 100lm/W, lumen maintainence of 70% at the end of 50000 burning hours, CCT of 5700K - 6500K, PF≥0.95, CRI≥70, THD10%, surge proctection of ≥ 10kv and IP≥65 protected with separate optics and control gear compartment, toughened glass protector, permanently sealed and a removable control gear plate, , mounting spigot suitable for horizontal mounting (Ø 32 – 42mm) with tilt flexibility of (+)(-) 10 degrees. LM 79 report to be submitted for luminaire from NABL accrediated lab and LM 80 for LED source issued by LED manufacture. LED shall have reverse polarity, open and short circuit protection.

30

-

-

... More
Supplying of Solar street light with IP 65 LED fixture having a system wattage of 40W with 4000 lumen system output, 160Wp high efficiency Poly crystalline solar panel certified IEC 61215 and 100Ah tubular VRLA gel battery with BIS approval. LED system lumen efficacy shall be at least 100 lumens / watt and the LED driver should have 90% efficiency operating on 12V DC.The battery shall not be discharged beyond 75% of capacity. The solar charge controller should be of Microprocessor Based MPPT make with 94% efficiency and enclosed in IP 65 box. The charge controller shall provide all safety protections and temperature compensated charging of the battery. The battery should be housed in a box made from galvanized steel and epoxy polyester powder coated so that it withstands corrosion.The solar system should be mounted on a 7.0m height Octagonal galvanized pole of 4mm thickness which shall be secured with foundation bolts and nuts.

6

-

-

... More
Supply of LED Bollard having lumen not less than 855 lumens with luminaire efficacy of not less than 95 lumens per watt, lumen maintainence of 70% at the end of 50000 burning hours with constant current driver output, Power Factor ≥0.95 & THD 10%, CRI70,neutral white light and made of GI pipe bottom housing the control gear speen Aluminium dome shaped type cover with cylindrical dome shaped top cover, overall lenght of bollard to be minium of 600 mm, operating range 150V – 270V, 50Hz AC supply, inbuilt driver with surge protection ≥10KV. The luminaire shall be minimum IP:65 protected. LM 79 report to be submitted for luminaire from NABL accrediated lab and LM 80 for LED source issued by LED manufacture. LED shall have reverse polarity, open and short circuit protection.

15

-

-

... More
Installation of 7m high M.S. street light pole including including installation of street light fitting (Cost of fitting not to be considered here) with all accessories and supply & making foundation of reinforced cement concrete 1:3:6 (1 cement :3 coarse sand : 6 graded stone aggregate 40mm nominal size) including 2Nos. supply and laying of 50mm PVC pipe from ground to terminal box including excavation and refilling, including positioning of template & foundations bolts (supplied with pole to match with pole base plate) complete as required and as specified.

30

-

-

... More
Supply, installation, testing and commissioning of 40kVA/ 32kW ( Input 3Phase / output 3 Phase) Floor Mount Type, Compact & modulat design, Conforming to IEC EN 62040 (All Parts), ISO 9001 certified, True On-Line, double conversion, IGBT on the input and output with multiple digital signal processor controlled for Rectifier/ charger, Battery, 2 Level IGBT Inverter, Static Switch, with parallel redundent, compatible with 0.7 lagging to 0.7 leading PF loads without deration, power factor 0.8, THDi 3-5%, Input voltage 380-415V, Output voltage 415V, 50Hz frequency, efficiency 95%, 0-40 deg C, with inbuilt overload, short circuit, Input low voltage, output over voltage, battery over charging, battery over discharging protections, Parallel kit, 30 min battery back-up with 12 V Maintenance Free Sealed Lead Acid batteries alongwith Powder Coated M.S. Rack with unidirectional wheels for housing the Batteries alongwith all accessories including interconnecting cables, lugs, Base Frames, Battery Rack & Battery Circuit breaker complete as required.

2

-

-

... More
Supply, installation, testing and commissioning of 20kVA/ 16kW ( Input 3Phase / output 3 Phase) Floor Mount Type, Compact & modulat design, Conforming to IEC EN 62040 (All Parts), ISO 9001 certified, True On-Line, double conversion, IGBT on the input and output with multiple digital signal processor controlled for Rectifier/ charger, Battery, 2 Level IGBT Inverter, Static Switch, with parallel redundent, compatible with 0.7 lagging to 0.7 leading PF loads without deration, power factor 0.8, THDi 3-5%, Input voltage 380-415V, Output voltage 415V, 50Hz frequency, efficiency 95%, 0-40 deg C, with inbuilt overload, short circuit, Input low voltage, output over voltage, battery over charging, battery over discharging protections, Parallel kit, 30 min battery back-up with 12 V Maintenance Free Sealed Lead Acid batteries alongwith Powder Coated M.S. Rack with unidirectional wheels for housing the Batteries alongwith all accessories including interconnecting cables, lugs, Base Frames, Battery Rack & Battery Circuit breaker complete as required.

3

-

-

... More
TOTAL CARRIED SUMMARY

-

-

-

... More
11 KV HT Switchboard ( 4 VCB's switchboard Panel Expendable )

-

-

-

... More
SUBSTATION 11KV/433KV

-

-

-

... More
Supply, delivery, erection, testing and commissioning of a Four panel ( one incomer +three outgoing) indoor duty totally enclosed sheet steel clad floor mounting, vermin proof, fully interlocked vertical isolation, extensible, horizontal draw out, air insulated, metal clad switchboard having double isolation features complete with circuits as detailed below. The switchboard would be complete with necessary PVC insulated copper busbars, small wiring, labels, cable eyes, cable termination to receive XLPE cables, foundation bolts and suitable for operation on 11 kV 3 phase, 50 cycle, earthed system with a rupturing capacity of 350 MVA .This HT panel must be extendable for future requirement in such a manner not to disrupt ongoing services at the point of use during extension.

-

-

-

... More
All Incoming and outgoing feeders shall have fault trip auxiliiary contacts for wiring to annunciation fault trip indication panel

-

-

-

... More
One Incoming panel equipped with :

-

-

-

... More
1- Air insulated metal clad housing

-

-

-

... More
1- set of 3 phase PVC insulated copper busbars 630 amps rating

-

-

-

... More
6- single pole cluster type isolating contacts i.e. plug and switches

-

-

-

... More
1- Triple pole draw out truck mounted 11kV 350 MVA, 630 amps Vacuum circuit breaker fitted with arc control devices.

-

-

-

... More
6 NO/NC contacts for remote ON/OFF/TRIP status at BMS

-

-

-

... More
1- Trip free 230 V AC, motor charged spring release closing mechanism complete with necessary auxiliary switches, emergency hand trip device and mechanical 'OFF' & 'ON' indicator.

-

-

-

... More
1 - 24 Volt DC shunt trip coil

-

-

-

... More
3 - Dual Core Cast resin Current transformers of ratio 75-120/5A Class 5P10 and Class 1.0, 15 VA burden for protection & metering.

-

-

-

... More
1- 3 Phase cast resin horizontal draw out line potential transformer ratio 11 KV/√3:110/√3 Volt, class 1.0, 200 VA connected star/star with H.V. and L.V. connections, H.V.fuses and LV MPCB of adequate rating to withstand fault level in PT circuit, isolating plugs for H.V. and L.V. connection.

-

-

-

... More
1- Strip heater to prevent absorption of moisture

-

-

-

... More
The instrument and relay panel fitted with :

-

-

-

... More
1- Square voltmeter of 96 x 96 mm scaled 0-15000 volt with 3 way and OFF selector switch.

-

-

-

... More
1- Square Ammeter of 96 x 96 mm scaled 0-150 amps with 3 way and OFF selector switch.

-

-

-

... More
1 no. energy analyser to measure voltage, current, power factor, frequency,kW/kVA, kWh, kVArh, kVAh,Real time,date with communication module.

-

-

-

... More
1 - no. circuit breaker control switch for electrical (T/N/C)

-

-

-

... More
1- Triple pole numerical I.D.M.T. overcurrent & earth fault relay with two outer elements connected for overcurrent protection and the middle element for earth fault protection overcurrent setting 50% - 200% Earth fault setting 20% - 80% (51 and 51N)

-

-

-

... More
1 - Electro mechanical Master trip relay (86)

-

-

-

... More
1 - Electro mechanical Anti pumping relay (94)

-

-

-

... More
1 - Trip Circuit supervision relay.

-

-

-

... More
1- set of Red/Green indicating lamps for close and open position

-

-

-

... More
1- Amber indicating lamp for auto trip

-

-

-

... More
1- clear indicating lamp for trip circuit healthy

-

-

-

... More
1- set of white indicating lamps one per phase

-

-

-

... More
1 - blue indicating lamp for spring charged

-

-

-

... More
1 - push button on front door for emergency trip

-

-

-

... More
1- Four window annunciation display to indicate fault trip of incoming and outgoing feeders including audio alarm hooter with accept push button, internal wiring,protection fuses etc. complete.

-

-

-

... More
1- cable box suitable for cable termination to receive 11 KV XLPE Cable 3 Core 240 sqmm.

-

-

-

... More
1 Set of Power Pack 220 Volt A.C. / 24 Volt D.C. complete & suitable as required for th complete item.

-

-

-

... More
THREE NOS OUTGOINGS TRANSFORMER FEEDERS EACH EQUIPPED WITH:

-

-

-

... More
1- Air insulated metal clad housing

-

-

-

... More
1- set of 3 phase PVC insulated copper busbars 630 amps

-

-

-

... More
6- Single pole cluster type isolating contacts; i.e. plug and switches

-

-

-

... More
1- Triple pole drawout truck mounted 11 kV 350 MVA, 630 amps Vacuum circuit breaker fitted with arc control devices.

-

-

-

... More
1- Trip free 230 V AC, motor charged spring release closing mechanism complete with necessary auxiliary switches emergency hand trip device and mechanical 'OFF' and 'ON' indicator.

-

-

-

... More
6 NO/NC contacts for remote ON/OFF/TRIP status at BMS

-

-

-

... More
1 - 24 volts DC shunt trip coil

-

-

-

... More
3 - Dual Core Cast resin Current transformers of ratio 40/5 Class 5P10 and Class 1.0, 15 VA burden for protection & metering.

-

-

-

... More
1- Strip heater to prevent absorption of moisture

-

-

-

... More
The instrument and relay panel fitted with

-

-

-

... More
1- Square Ammeter 96 mm x 96 mm scaled 0-35 amps with 3 way and OFF selector switch

-

-

-

... More
1- Triple pole numerical I.D.M.T. over current and earth fault relay, with two outer elements connected for over current and the middle element for earth fault protection over current setting 50% - 200% Earth fault setting 20% -80% and with instantaneous element on all 3 pole settings 500-2000% on over current and 200-800% on earth fault (51, 50, 51N & 50N)

-

-

-

... More
1 - Electro mechanical Master trip relay (86)

-

-

-

... More
1 - Electro mechanical Anti pumping relay (94)

-

-

-

... More
1 - Trip Circuit supervision relay.

-

-

-

... More
1 - set of electro mechanical auxiliary relay for OLTC

-

-

-

... More
1- set Electro mechanical auxiliary relay for transformer fault ALARM for winding temperature conditions (63x)

-

-

-

... More
1- set Electro mechanical auxiliary relay for transformer fault TRIP for winding temperature conditions (63x)

-

-

-

... More
1 - no. circuit breaker control switch for electrical (T/N/C)

-

-

-

... More
1- set of Red/Green indicating lamps for close and open position

-

-

-

... More
1- Amber indicating lamp for auto trip

-

-

-

... More
1- clear indicating lamp for trip circuit healthy

-

-

-

... More
1- set of white indicating lamps one per phase

-

-

-

... More
1 - blue indicating lamp for spring charged

-

-

-

... More
1- cable termination suitable for cable joint to receive 11 KV XLPE cable 3 core 240 sqmm .

-

-

-

... More
The switchboard shall be complete with all interconnections, label wiring, etc as required and as per direction

-

-

-

... More
Supplying,Installation,Testing & Commissioning Rate for 11 kV HT Panel as described above

1

-

-

... More
Supply, erection, testing and commissioning of 230V, single phase 2 wire AC to 24V DC Batteries charger with semiconductor/IGBT fullwave rectifier with auto /manual float cum boost facility complete with 24V DC, 120 AH sealed maintenance free batteries including one no. distribution board having 63 Amps DP MCCB as incomer and 12 Nos. 20/16A DP MCB's (D.C. duty) as outgoing complete as required and as per technical specifications.

1

-

-

... More
11kV/0.433kV ONAN WITH OFF LOAD TAP CHANGER WITH BUCHHOLZ, OTI , WTI RELAYs

-

-

-

... More
Design, Manufacture, Supply at site, inspection of Consultant's/client at Factory at your cost of following rating continuous duty cycle, 11kV/0.433kV, 3 phase, 50Hz, Dyn-11 vector group, step down, outdoor type, copper wound, ONAN type transformers with Off Load Tap changer & with all fixing accessories including complete as per specifications. Tap changing range shall be +5% to -10% in steps of 2.5%. Class 'A' of Thermal insulation Suitable for Maximum Ambient temperature 45º C. Maximum winding temprature 105º C

-

-

-

... More
The Following Fittings Shall Be provided with all required accessories:- Rating & Terminal Marking Plate, Earthing Terminals, Lifting Lugs For Main Tank & Top Cover, Filter Valve , Drain Cum Sampling Valve, Thermometer Pocket, Dial Type Oil Temperature Indicator, Air Release Plug, Silica Gel Breather, oil conservator, Explosion Vent, Inspection Cover, Arcing Horn, Radiators Mounted on Tank, 4 Nos. bi-directional Rollers, First Filling of Transformer Oil as per IS:335, Magnetic Oil Level Gauge, Buchholz Relay, Oil Temperature Indicator, Winding Temperature Indicator, Marshalling Box, Epoxy Bushing, PU Paints, Palm, LV Bus Bar, Radiator Valves, Cable Box on LT side & Cable Box on HT side. Transformer shall Compliance to IS:1180 & IS:2026 all parts latest as on date whichever is higher. complete with all accessories

-

-

-

... More
The transformer shall be delivered along with after complete factory tests and temprature rise test, Operational & Maintenance manual and test certificate of unconditional guaranteed against manufacturing defects for a period of 18 months from the date of supply.

-

-

-

... More
1250kVA Losses as per IS:1180 Level-2

1

-

-

... More
TOTAL CARRIED SUMMARY

-

-

-

... More
DIESEL GENERATORs

-

-

-

... More
Providing, Installing, Receiving, unloading, shifting to Sub-Station, storing, handling, Testing and Commissiong of 'Silent Type' Diesel Generating set alongwith Prime Power Rating 1010 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 433V suitable for 50 Hz, 3 phase system & for 0.80 Load Factor and consisting of the followings:

-

-

-

... More
Diesel Engine:

-

-

-

... More
Diesel engine 4 stroke radiator Cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 50 Degree C, 50% RH & at 1000 Meter MSL and conforming to BS 5514, BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continous operation. The engine will be fitted complete with electronic Governer and all the required accessories.

-

-

-

... More
Engine mounted Instrument Panel fitted with and having digital display for following:

-

-

-

... More
(i) Start-stop switch with key

-

-

-

... More
(ii) Coolant temperature indication

-

-

-

... More
(iii) Lubrication oil pressure indication

-

-

-

... More
(iv) Lubrication oil temperature indication

-

-

-

... More
(v) Battery charging indication

-

-

-

... More
(vi) RPM indication

-

-

-

... More
(vii) Over speed indication

-

-

-

... More
(viii) Low lub. Oil trip indication

-

-

-

... More
(ix) Engine Hours indication

-

-

-

... More
(x) Engine protection unit and sensors for winding & bearing temperature monitoring

-

-

-

... More
(xi) Remote Monitoring Module

-

-

-

... More
Alternator

-

-

-

... More
Synchronous alternator rated at 1010KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.80 lagging power factor at 50 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having microprocessor based controller with BMS compatibility, SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with class-F/H insulation.

-

-

-

... More
Cable termination Box suitable to receive 1600A, TPN Busduct Sandwich or air insulated type.

-

-

-

... More
Base Frame & Foundation:

-

-

-

... More
Both the engine and alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and antivibration mountings arrangement as per recommendations of manufacturer.

-

-

-

... More
Fuel Tank: (External)

-

-

-

... More
Daily service fuel tank of 990 liters capacity fabricated out of 3 mm thick M.S./CRCA sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications.

-

-

-

... More
Exhaust System:

-

-

-

... More
Dry exhaust mainfold with hospital exhaust silencer and catalytic convertor.

-

-

-

... More
Starting System:

-

-

-

... More
DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries (25 plates, 2 x 160 AH, 12V capacity SMF lead acid type) as required as per specifications.

-

-

-

... More
Accoustic for weather and noice proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per CPCB-II Norm & technical specifications.

1

-

-

... More
D.G. EXHAUST PIPE

-

-

-

... More
Supplying and fixing of exhaust gas piping of 250mm dia. for 1010kVA rating D.G. Set welded black MS, 'B' Class pipe conforming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, the work include necessary cladding of exhaust pipe work using wiremesh, 50mm thick Loosely bound resin(LBR)mattress / mineral wool/ Rockwool, density not less than 150kg/m and aluminium cladding (0.6mm thick min.) for temperature up to 450°C, complete portion complete as required as per specifications.

50

-

-

... More
Note- Contractor / Vendor to check the diaMeter of the exhaust pipes w.r.t. back pressure calculations & confirm the exhaust pipe sizes & suggest changes if required. This is to be done before supply of material / at the time of tendering. The contractor to measure actual pipe lengths as per site conditions & then confirm the suitability of pipe dia Meters supported by back pressure calculations.

-

-

-

... More
INSULATION OF SILENCER FOR 1010KVA D.G. SET

-

-

-

... More
Supplying and fixing of insulation around the silencer including necessary cladding work using wiremesh, 50mm thick Loosely bound resin(LBR)mattress / mineral wool/ Rockwool, density not less than 150kg/m and aluminium cladding (0.6mm thick min.) for temperature up to 450°C, complete portion complete as required as per specifications.

1

-

-

... More
CORRUGATED BELLOW

-

-

-

... More
Supplying & fixing of Stainless Steel Expansion Joints, Corrugated bellow of 250 dia Meter to fit in exhaust pipe.

4

-

-

... More
MAIN LT PANEL/ SUB LT PANEL/ MDB & SDB

-

-

-

... More
Supplying, installation, testing & commissioning of Totally Type Tested Panels complying IEC 61439 -1/2 cubical with Internal arc withstand and impact resistance IK10 as per ICE62262. The panel shall be tested for an internal arc of 50kA for minimum 0.4 seconds. The degree of protection of minimum IP 42 for indoor and IP 65 for outdoor use. Suitable for 415V, 3Phase, 4 Wire 50 Hz Ac supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of minimum 2 mm thick for load bearing member and 1.6mm for Non load bearing member, 3mm thick for gland, plates i/c cleaning & finishing complete, having extensible type aluminium bus bars of high conductivity, SMC bus bar supports, with short circuit withstand capacity of 50kA for 1 Sec., bottom frame shall be 100mm Height as per OEM standard, fabrication shall be done in transportable sections, Entire panel shall have a common aluminium earth bar of size 32mm x 6mm or as specified below at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al with form-4B construction. bus bars and control wiring with suitable size of PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :-

-

-

-

... More
The Bus bars will be Copper purity 99.9% / electrolytic grade E91 Aluminium. Panels will be powder coating (60-80micron as per IS:13871 for indoor and 90-100 micron for outdoor), include one size higher terminal block in cable alley and interconnecting wires between bus bars and terminals via MCB. All Bus-Bar alley and relay compartments shall be provide fully automtic control thermotate with strip heater.

-

-

-

... More
Also, refer to General Notes and Specifications for Panels/ Boards.

-

-

-

... More
Contractor to submit manufacturer's Total discrimination curves prove the same, insulation material & corners cover on bus-bars for approval. Feeders should be totally bolted structure with interchangeable feeder.

-

-

-

... More
All live accessible parts shall be shrouded and all equipment shall be finger touch proof. SMC shrouds bus bar supports shall be used. Padlocking facility shall be provided on all MCCB feeder doors and switch handles shall be lockable in OFF position.

-

-

-

... More
Sealing Arrangement :- PE Foam Rubber Gasket

-

-

-

... More
Bus Bars Supports - Non-Hygroscopic, Non Carbonising, Corrosion Resistant, SMC Supports

-

-

-

... More
1Set of connector (Phase+Neutral) shall be provided in cable alley for all outgoing with interconnection wires between MCB and Connector.

-

-

-

... More
Minimum Air Clearances between bus bars shall be as per IEC 61439 Clause 8.2.5;

-

-

-

... More
Panel Power and control Wiring all ZHLS PVC insulated

-

-

-

... More
AC voltage circuit-1.5 sqmm Red,Yellow,Blue &Black

-

-

-

... More
Current circuit-1.5 sqmm Red,Yellow,Blue &Black

-

-

-

... More
AC Control circuit-1.5 sqmm White for Phase & Black for Neutral

-

-

-

... More
DC Control circuit-2.5 sqmm Grey

-

-

-

... More
Power circuit- Red,Yellow,Blue for Phase &Black for Neutral

-

-

-

... More
Labeling- Computerised Laminated Aluminium Name Plate with White letters on Blue/Black Background For Each Feeder and Panel Itself.

-

-

-

... More
1) If mentioned fault and Automatic transfer switch rating is unavailable consider nearby upside rating

-

-

-

... More
2) A separate compartment for Minimum 20% spare space of Panel shall be provided for outgoings in future and busbars shall be drilled accordingly.

-

-

-

... More
3) Total Discrimination of system shall be checked and required setting shall be made. If any component required to change will change free of cost. The switch-gear & Panel manufacturer (jointly) will submit discrimination check report duly checked and signed on company letter head.

-

-

-

... More
GENERAL NOTES FOR ACB's:

-

-

-

... More
ACB shall be with 4 NO + 4 NC Auxiliary contacts.

-

-

-

... More
Safety Shutter.

-

-

-

... More
Door Sealing Frame.

-

-

-

... More
Inbuilt Ethernet Port

-

-

-

... More
Inbuilt TRIP LED indication.

-

-

-

... More
ON/ OFF/ TRIP status on Ethernet

-

-

-

... More
Ics = Icu = Icw for 1 sec. for the breakers.

-

-

-

... More
With built in micro-processor based releases: ( digitally upgradable)

-

-

-

... More
Adjustable over current with time setting.

-

-

-

... More
Adjustable short circuit with time setting.

-

-

-

... More
Instantaneous short circuit.

-

-

-

... More
Adjustable earth fault with time setting.

-

-

-

... More
Power wiring with one size higher terminals / bus bars for termination of cables as specified.

-

-

-

... More
There shall be no deration upto 50 degree celcius.

-

-

-

... More
ACBs shall be provided with both side terminal adaptors (Preferably Hr Vr)

-

-

-

... More
All the ACBs must be equipped with features like ZSI, Thermal Memory, last 10 trip histories, current & Voltage Metering, % loading Bar graph, LED fault differentiation, display of per phase energy & Total Harmonics Distortion

-

-

-

... More
GENERAL NOTES FOR MCCB's:

-

-

-

... More
MCCB's shall be of TPN (3P with solid neutral link) or 4P as called for in the BOQ.

-

-

-

... More
Ics = Icu = 100% or more for the breakers.

-

-

-

... More
All Thermal Magnetic MCCB's shall have adjustable over current and Fixed short circuit if used as outgoing and when used as incomer short circuit rating shall be adjustable.

-

-

-

... More
All micro-processor based MCCB's shall have adjustable over current with time setting, adjustable short circuit and Adjustable earth fault with indication due to earth fault.

-

-

-

... More
MCCB's shall be with extended rotary handle with Phase spreaders & Phase Barriers at both sides

-

-

-

... More
MCCB's shall have auxiliary contacts for BMS compatibility.

-

-

-

... More
All MCCBs above 250A shall be microprocessor based. Thermal Magnetic MCCBs shall have modular external earth fault protection.

-

-

-

... More
All the MCCBs in Main Panel to communicate ON/OFF/TRIP status on Ethernet.

-

-

-

... More
GENERAL NOTES FOR MCB's:

-

-

-

... More
MCB's shall be of minimum 10kA breaking capacity for 1 sec.

-

-

-

... More
Use 'B' curve MCB's for lighting & small power circuits, 'C' curve for motor duty i.e. for pumps, AC motors, AHU motors, window and split AC's etc. & 'D' curve for UPS DB's i.e. for computers/ PC's circuit. Main Incomer & outgoing circuit MCB's shall be selected accordingly i.e. type B,C & D. as per the nature of the circuit/ load.

-

-

-

... More
Exact MCB rating & category is to be calculated by the electrical contractor based on the final load of the circuit, its nature and fault current.

-

-

-

... More
(Note:The contractor may select the next higher fault rating of MCCB if it is not readily available ,without any extra cost ,as the figure indicated within the bracket are required maxmum fault level of the panel.)

-

-

-

... More
MAIN LT PANEL

-

-

-

... More
Main LT Cum DG Panel (Indoor use located at Ground floor on a plain civil foundation with cable entry from top or Cable trench with bottom & top both cable entry) / Outdoor use located in external area on Rock or soft Soil as case may be with bottom cable entry.

-

-

-

... More
INCOMER FROM TRANSFORMER-I (500 kVA Existing TR Stand-By)

-

-

-

... More
1 No. 800 Amps 4P EDO type Air circuit breaker built-in self powered micro-processor based releases for O/L,S/C,I/G&E/F of fault breaking capacity 50KA (Ics=Icu=Icw upto 415V manually operated, Inbuilt Shunt Trip indication. fitted with interlocked door, door sealing frame, automatic safety shutters and frame earthing contact, additional min. 4NO + 4NC Auxiliary contacts, the ACBs must be provided with terminal adaptors (Hr Vr), ACB conforming to IS-1397-2 (1993) and complice RoHS as amended up-to-date complete with following accessories for each complete with following accessories for each ACB. Terminals suitable for Bus duct connections on incomer side and bus bar connection at output sides.(Where interlocking is required between incomers)

-

-

-

... More
INCOMER FROM DG SET-I (500 kVA Proposed DG Stand-By)

-

-

-

... More
1 No. 800 Amps 4P EDO type Air circuit breaker built-in self powered micro-processor based releases for O/L,S/C,I/G&E/F of fault breaking capacity 50KA (Ics=Icu=Icw upto 415V manually operated, Inbuilt Shunt Trip indication. fitted with interlocked door, door sealing frame, automatic safety shutters and frame earthing contact, additional min. 4NO + 4NC Auxiliary contacts, the ACBs must be provided with terminal adaptors (Hr Vr), ACB conforming to IS-1397-2 (1993) and complice RoHS as amended up-to-date complete with following accessories for each complete with following accessories for each ACB. Terminals suitable for Bus duct connections on incomer side and bus bar connection at output sides.(Where interlocking is required between incomers)

-

-

-

... More
INCOMER FROM TRANSFORMER-II (1250 kVA Proposed TR Working)

-

-

-

... More
1 No. 2000 Amps 4P EDO type Air circuit breaker built-in self powered micro-processor based releases for O/L,S/C,I/G&E/F of fault breaking capacity 50KA (Ics=Icu=Icw upto 415V manually operated, Inbuilt Shunt Trip indication. fitted with interlocked door, door sealing frame, automatic safety shutters and frame earthing contact, additional min. 4NO + 4NC Auxiliary contacts, the ACBs must be provided with terminal adaptors (Hr Vr), ACB conforming to IS-1397-2 (1993) and complice RoHS as amended up-to-date complete with following accessories for each complete with following accessories for each ACB. Terminals suitable for Bus duct connections on incomer side and bus bar connection at output sides.(Where interlocking is required between incomers)

-

-

-

... More
INCOMER FROM DG SET-II (1010 kVA Proposed DG Set Working)

-

-

-

... More
1 No. 1600 Amps 4P EDO type Air circuit breaker built-in self powered micro-processor based releases for O/L,S/C,I/G&E/F of fault breaking capacity 50KA (Ics=Icu=Icw upto 415V manually operated, Inbuilt Shunt Trip indication. fitted with interlocked door, door sealing frame, automatic safety shutters and frame earthing contact, additional min. 4NO + 4NC Auxiliary contacts, the ACBs must be provided with terminal adaptors (Hr Vr), ACB conforming to IS-1397-2 (1993) and complice RoHS as amended up-to-date complete with following accessories for each complete with following accessories for each ACB. Terminals suitable for Bus duct connections on incomer side and bus bar connection at output sides.(Where interlocking is required between incomers)

-

-

-

... More
INCOMER FROM TRANSFORMER-III (500 kVA Existing TR Stand-By)

-

-

-

... More
1 No. 800 Amps 4P EDO type Air circuit breaker built-in self powered micro-processor based releases for O/L,S/C,I/G&E/F of fault breaking capacity 50KA (Ics=Icu=Icw upto 415V manually operated, Inbuilt Shunt Trip indication. fitted with interlocked door, door sealing frame, automatic safety shutters and frame earthing contact, additional min. 4NO + 4NC Auxiliary contacts, the ACBs must be provided with terminal adaptors (Hr Vr), ACB conforming to IS-1397-2 (1993) and complice RoHS as amended up-to-date complete with following accessories for each complete with following accessories for each ACB. Terminals suitable for Bus duct connections on incomer side and bus bar connection at output sides.(Where interlocking is required between incomers)

-

-

-

... More
BUS - COUPLER

-

-

-

... More
2 No. 800 Amps 4P EDO type Air circuit breaker without protection release of fault breaking capacity 50KA (Ics=Icu=Icw upto 433V manually operated, Inbuilt Shunt Trip indication. fitted with interlocked door, door sealing frame, automatic safety shutters and frame earthing contact, additional min. 4NO + 4NC Auxiliary contacts, the ACBs must be provided with terminal adaptors (Hr Vr), ACB conforming to IS-1397-2 (1993) and complice RoHS as amended up-to-date complete with following accessories for each complete with following accessories for each ACB, terminals suitable for Bus bar connections on both sides.

-

-

-

... More
METERING, INDICATOR AND RELAYs

-

-

-

... More
E-Series R,Y,B phase indication lamps with 4Nos. SP HRC fuses as per fault requirement for each Incomer.

-

-

-

... More
Provide 4Nos indicating lamps on each ACB for status indication "ON","OFF" , tripped Due to Earth fault & Trip circuit healty and true operation counter for all ACB

-

-

-

... More
ON/OFF/TRIP Due to E/F or ELR' Indication lamps each with MCB HRC fuses for each outgoing and buscoupler.

-

-

-

... More
All ACBs incomer and outgoing in main LT panel shall surely be provided with zone selective interlocking. The releases shall be suitable to communicate between incomer breaker and outgoing breakers enabling zone selective interlocking. The manufacturer shall supply all equipment like ZSI module, power supply and wiring connectors to implement ZSI.It shall be provided only when ACB is an incomer and atlest one ACB outgoing is used.

-

-

-

... More
Wherever 4 Pole ACBs used, it shall have fully rated neutral equal to rating of the breaker & shall be protected against over-load faults with provisions for settings neutral unprotected, neutral protection at 0.5In and neutral protection at 1.0 In to ensure precise neutral protection.

-

-

-

... More
Provide seprate 3Nos. Dual ratio dual tape Resin cast CTs, Class-1, in each transformer Incoming for single to capacitor panel APFCR.

-

-

-

... More
CT-Operated Enersol make- MFR-4810 Multi Function Panel mounted Meter - (96 mm x 96 mm) covering Load Manager MF 48 with Import/Export & RS485 port all electric basic, Power & Energy parameters 4 quadrant including THD% V& A phasewise for all incommers with class - 1.0 accuracy.

-

-

-

... More
CT-Operated Enersol make- MF-4210 Multi Function Panel mounted Meter - (96 mm x 96 mm) covering Load Manager MF 42 without RS 485 Port , All electric basic, Power & Energy parameters including THD% V& A phasewise for all outgoing with class-1.0 accuracy.

-

-

-

... More
OR

-

-

-

... More
Provide 3Nos. Resin cast CTs, Class-1.0 and MFM with min. features of Class 0.2 revenue accuracy in Power & Energy Metering, On board Ethernet port supporting TCT/IP protocol, Supports MODBUS TCP/IP, RS:485 port with MODBUS-RTU protocol, Measurement: KW/KVA/Voltage & current & Hz & Apparent Power & active Power min/max , 6th level THD - upto 29th Harmonics. Three rows of min. 8 - digits, 4 relay outputs for alarm & trip limits, Event definition and logging, data logging of all parameters for load pattern analysis. 2MB internal memory, USB 2.0 port inport/export parameters provide with all incomer breakers. Refer to Cat no. - Trinity - SLM102/ Schneider- PM5560/ Socomec- DIRIS A60 or eq.

-

-

-

... More
Provide 3Nos. Resin cast CTs, Class-1.0 and Dual source MFM with min. features of True RMS measurements, CT and PT Ratio site selectable, Measurement of all A,V,Hz,KVA,KW, KVAR,KVAh, KWh and KVARh, system/individual PF, Individual Odd Harmonics upto 15th THD, Odd Harmonic data as Histogram for each individual current and voltage, Individual A, V Waveforms for each phase, RS-485 port for SCADA/BMS, Two relay contacts for alarm/trip with class-1.0 accuracy for all outgoing feeder. Refer to Cat no. - Trinity-XPERT/ Schneider- PM5110/ Socomec- DIRIS A40 or eq.

-

-

-

... More
Single phase preventer, Under/Over voltage relay for each transformer & D.G. set Incomer with indicator for trip and hooter for alarm.

-

-

-

... More
Reverse power relay for each D.G. set Incomer with indicator for trip and hooter for alarm

-

-

-

... More
Phase Reversal relay for each Transformer incomer with indicator for trip and hooter for alarm.

-

-

-

... More
Provide control accessories like automatically controlled constant voltage constant current, 24/12 V DC battery charger with battery charging indication, battery charged indication, Over charged battery protection, low battery protection, High Voltage protection, charger on - AC, DC Ammeter, DC Voltmeter, 8 window fault annunciater with inbuilt P.B and Hooter, trip alarm and reset etc. for each D.G. Set incomer

-

-

-

... More
Provide 8 window annunciator with hooter , 2 Window for over Current & Earth fault, 2 Window for OTI alarm & Trip, 2 Window for WTI alarm & Trip & 2 Window Bucholz alarm & Trip ( If applicable) for each Transformer incomer

-

-

-

... More
Provide emergency stop Push Button Station for Emergency stop Head with Switching position indicator and yellow anti-lock collar, push to lock and turn to release. Legend - Emergency Contact - 1 NC. Metric knock outs for Cables entry Ref. Cat Number- Hensel PBS 0101 for each incomer ACB/MCCB

-

-

-

... More
TVSS & BUSBARS SECTIONS (Sectiob=I,II & III)

-

-

-

... More
2200 Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars mount on SMC supports. All interconnections shall be as follows; a). Upto 63A, FRLS PVC insulated copper flexible colour coded wires b). 64Amp to 200Amp Copper Bus-bars and c). 201Amp and above Aluminium Bus-bars , current density of bus-bars shall not be less than 1 Amps/sq.mm for Aluminium and 2 Amps/sq.mm for copper cross sectional area of Bus Bar.

-

-

-

... More
Each Bus Section with 1 No Surge protection device Type 1 ( Class B),true status indication, 7 Mode, spark gap type suitable for 10/ 350µs surge,Voltage Protection level Up 4.0kV, Operating Temperature -40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral & 3Nos. phase to earth and 1Nos. neutral to earth with discharge Current Imax. ≥ 50KA Per mode & In ≥ 25kA per Mode. Make & Model: Argos-AG-415-40T1-E or eq. SPD with 125A 4P HRC fuses of 100kA breaking capacity. For connecting SPD minimum 16sqmm copper wire must be used & length of connecting leads shall not be more than 500mm for per mode connection with each busbar including all necessary accessories. The SPD shall complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.

-

-

-

... More
OUTGOINGS CONNECTED AS SHOWN IN SLD:

-

-

-

... More
1 Nos. 800A TP+NL MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
2 Nos. 630A TP+NL MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
8 Nos. 400A TP+NL MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
2 Nos. 315A TP+NL MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
5 Nos. 250A TP+NL MCCB built in microprocessor based release (adjustable O/L,S/C&E/F) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
3 Nos. 200A TP+NL MCCB built in thermal magnetic based release (adjustable O/L, adjustable S/C & adjustable E/F) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
3 Nos. 160A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
7 Nos. 100A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
2 Nos. 63A TP+NL MCCB built in thermal magnetic based release (adjustable O/L & fixed S/C) of fault breaking capacity 35KA (Ics=Icu=100%) upto 415V manually operated with extended rotary handle with castle lock for door interlock with Phase spreader & Phase Barriers at both sides. MCCB shall conforming to IS-1397-2 1993 as amended

-

-

-

... More
Earth leakage protection relay with 300mA to 3000mA with ZCT for each outgoing MCCB.

-

-

-

... More
PLC FOR INTERLOCKING, SYNCHRONISING & LOAD MANAGEMENT

-

-

-

... More
PLC based Automatic / Manual Synchronisation and check synchronising Panel with auto and manual operation and Load Manager for both Mains and DG power, whose function will be to determine the Load, decide how many DG sets to be synchronised, perform Synchronisation and supply power to the load. Supplier to submit the Bill of materials for the above functions also provide motorised potential meter for each generator for voltage correction.

-

-

-

... More
Including Electrical & Mechanical interlocking between each Incomers and buscouplers as shown in SLD, Auto D.G. selection and Start/Stop, Load management including PLC Expansion Module, Sheild wire, NC01 cable, PLC restart/refreash, Power Supplies, arrangement Nesecarry arrangments, Softwere and Hardwares need to be provided for interlocking.

-

-

-

... More
1kVA online UPS with minimum 15 minutes backup, built in battery for PLC system.

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described main LT Panel

1

-

-

... More
Note: Incomers for Transformer, D.G. sets & Bus couplers shall be electrically & mechanically interlocked and quoted price shall be inclusive of all .

-

-

-

... More
400 kVAR Capacitor Panel: Automatic Power Factor Correction : WITH DETUNED HARMONICS REACTORS CONTACTOR BASED SWITCHING (INDOOR PANEL-IP:42)

-

-

-

... More
The capacitor banks in tier formation, Each capacitors specifications shall be MPP HEAVY duty cylindrical construction Oil Filled capacitors, 430Volts, 50 hz, Temp. Class-'D', Operating losses - 0.0025 (TAN DELTA), Over current withstand capability, 1.3 times rated current, 200 x In Inrush current withstand capability rated current, Operating life - 30,000 hours, Having over pressure disconnector switch, Number of switching, 3000 operations per year, conforming to IEC 60831-1+2/IS 13340-42. Provide Thermostat controlled panel mounted heavy duty exhaust fan in each Capacitor Compartment and space heater in Bus bar alley. It has to be ethernet enabled and OEM factory assembled panel.

-

-

-

... More
Automatic Power Factor Correction Relay

-

-

-

... More
12 steps 3 phase, Microcontroller based Power factor correction Intelligent controller equivalent to Schneider- VARSET model, having PF monitoring and correction of individual phase, with multi functional display. The relay shall be sensitive to pick up 1% of rated current and correct the P.F accordingly. The relay should have Autosense feature to senses the size of each capacitor bank connected on each stage automatically. Should be able to Correct lagging power factor and leading power factor.

-

-

-

... More
1Set of R,Y,B phase indication lamps with 4Nos. SP HRC fuses as per fault requirement for each Incomer.

-

-

-

... More
2Nos. Flashing Buzzer Over / Under Compensation

-

-

-

... More
1Set of alarm and indication if the power factor goes lagging below from 0.85 and leading above from 1.0 also if life cycle to complete of capacitor panel.

-

-

-

... More
BUS BARS

-

-

-

... More
1000Amps TP+N, 50kA, 500volts grade busbar chamber of suitable length with Aluminium busbars. All interconnections shall be with Aluminium Bus-bars, current density of bus-bars shall not be less than 1.3 Amps/sq.mm for Aluminium cross sectional area of Bus Bar.

-

-

-

... More
OUTGOINGS WITH THYRISTOR SWITCH

-

-

-

... More
Each below capacitor bank feeder shall be with thyristor Switching Module of same required kVAR, TP semiconductor fuse, door mount toggle Switch & light for each capacitor compartment, control wiring and backed up HRC Fuse.

-

-

-

... More
Each below Capacitor Bank of required kVAR with 7% detuned reactor.

-

-

-

... More
In case of capacitor bank with detuned reactor, the operating voltage of capacitor shall be 430V minimum as per capacitor OEM recommondations.

-

-

-

... More
CAPACITOR

-

-

-

... More
2 Nos. 100 KVAR Capacitor Bank Feeders

-

-

-

... More
1 Nos. 50 KVAR Capacitor Bank Feeders

-

-

-

... More
4 Nos. 25 KVAR Capacitor Bank Feeders

-

-

-

... More
2 Nos. 15 KVAR Capacitor Bank Feeders

-

-

-

... More
1 Nos. 10 KVAR Capacitor Bank Feeders

-

-

-

... More
2 Nos. 5 KVAR Capacitor Bank Feeders

-

-

-

... More
Each Bus Section with 1 No Surge protection device Type 2 ( Class C), 4 Mode, MOV type suitable for 8/ 20µs surge,Voltage Protection level Up 1.8kV, Operating Temperature -40 deg 'c' - +80 deg 'C', Connected Between 3Nos. phase to neutral and 1Nos. neutral to earth with discharge Current Imax. ≥ 40KA Per mode & In ≥ 20kA per Mode. Make & Model: Argos-AG-230-40T2-E or eq. SPD with 63A 4P HRC fuses of 100kA breaking capacity. For connecting SPD minimum 10sqmm copper wire must be used & length of connecting leads shall not be more than 500mm for per mode connection with each busbar including all necessary accessories. The SPD shall complience with IEC 61643-11 and certified by TUV,CE,ROHS,UL94V-O.

-

-

-

... More
400kVAR Capacitor Panel as described above.

1

-

-

... More
MDB-1 LAB CUM FACULTY BLOCK (GROUND FLOOR) (B-1)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.400 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-400A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 500A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
2 Nos. 200A TPN MCCB

-

-

-

... More
3 Nos. 100A TPN MCCB

-

-

-

... More
1 Nos. 63A TPN MCCB

-

-

-

... More
6 Nos. 40A TPN MCB

-

-

-

... More
1 Nos. 32A TPN MCB

-

-

-

... More
13 Nos. 25A TP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
SDB-1 LAB CUM FACULTY BLOCK (FIRST FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.200 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-200A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 300A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
6 Nos. 40A TPN MCB

-

-

-

... More
1 Nos. 32A TPN MCB

-

-

-

... More
20 Nos. 25A TP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
SDB-2 LAB CUM FACULTY BLOCK (SECOND & THIRD FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.100 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-400A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 150A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
6 Nos. 40A TPN MCB

-

-

-

... More
1 Nos. 32A TPN MCB

-

-

-

... More
5 Nos. 25A TP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

2

-

-

... More
MDB-2 OPD BLOCK (B-2) (GROUND FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.400 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-400A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 500A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
1 Nos. 250A TPN MCCB

-

-

-

... More
1 Nos. 100 A TPN MCCB

-

-

-

... More
1 Nos. 63A TPN MCB

-

-

-

... More
8 Nos. 40A TPN MCB

-

-

-

... More
1 Nos. 32A TPN MCB

-

-

-

... More
13 Nos. 25A TP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
MDB-3 NUCLEAR MEDICIEN BLOCK (B-4) (GROUND FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.400 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-400A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 500A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
1 Nos. 200 A TPN MCCB

-

-

-

... More
2 Nos. 125 A TPN MCCB

-

-

-

... More
2 Nos. 100 A TPN MCCB

-

-

-

... More
6 Nos. 40A TPN MCB

-

-

-

... More
2 Nos. 32A TPN MCB

-

-

-

... More
13 Nos. 25A TP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
SDB-1 RADIO THERAPY BLOCK (B-5) (GROUND FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.200 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-400A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 300A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
3 Nos. 125 A TPN MCCB

-

-

-

... More
1 Nos. 63A TPN MCB

-

-

-

... More
7 Nos. 40A TPN MCB

-

-

-

... More
13 Nos. 25A TP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
MDB-4 WARD BLOCK (B-6) (GROUND FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.250 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-250A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 400A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
2 Nos. 125 A TPN MCCB

-

-

-

... More
1 Nos. 100 A TPN MCCB

-

-

-

... More
1 Nos. 63A TPN MCB

-

-

-

... More
17 Nos. 40A TPN MCB

-

-

-

... More
13 Nos. 25A TP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
MDB-5 RAIN BASERA (B-7) (GROUND FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.200 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-200A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 300A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
1 Nos. 100 A TPN MCCB

-

-

-

... More
1 Nos. 63A TPN MCB

-

-

-

... More
15 Nos. 40A TPN MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
MDB-6 SERVICE BLOCK (B-8) (GROUND FLOOR)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.160 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-200A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 200A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
4 Nos. 63A TPN MCB

-

-

-

... More
4 Nos. 40A TPN MCB

-

-

-

... More
5 Nos. 25A TP MCB

-

-

-

... More
4 Nos. 25A DP MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
MDB UPS Input panel-1 (LAB CUM FACULTY BLOCK-B1)

-

-

-

... More
INCOMER

-

-

-

... More
2 No.125 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 set of R,Y,B phase indicating lamps

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-125A) Ammeter with ASS with 3 nos. 320/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 400A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
2 No. 125A TPN MCCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
MDB UPS output panel (LAB CUM FACULTY BLOCK-B1)

-

-

-

... More
INCOMER

-

-

-

... More
2No. 125A 4P MCCB (25 kA)

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 set of R,Y,B phase indicating lamps

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-125A) Ammeter with ASS with 3 nos. 160/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 300A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
2 Nos. 100A TPN MCCB

-

-

-

... More
10 Nos. 63A TPN MCB

-

-

-

... More
8 Nos. 40A TPN MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
MDB UPS output panel

-

-

-

... More
INCOMER

-

-

-

... More
2No. 63A 4P MCCB (25 kA)

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 set of R,Y,B phase indicating lamps

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-125A) Ammeter with ASS with 3 nos. 160/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 300A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
6 Nos. 63A TPN MCB

-

-

-

... More
8 Nos. 40A TPN MCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

3

-

-

... More
EXTERNAL LIGHTING FEEDER PILLAR (IP 65)

-

-

-

... More
INCOMER

-

-

-

... More
1 Nos. 40A 4P MCB .

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 100A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
Outgoing

-

-

-

... More
2 Set each having (2 x 4 way TPN DB 6 No. 10 amps SP MCB per phase as outgoing with 2 x 3 No. 32 amps DP RCCB of 30 mA leakage current, 2 No. 32 amps TP Contactor, push button etc. controlled through 2 No. 0-24 hour timer, photo sensor complete as required).

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

2

-

-

... More
MDB-1 MEDICAL EQUIPMENT LAB CUM FACULTY BLOCK (GROUND FLOOR) (B-1)

-

-

-

... More
INCOMER

-

-

-

... More
1 No.400 4P MCCB

-

-

-

... More
METERING & INDICATION

-

-

-

... More
1 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB

-

-

-

... More
1 No. (0-400A) Ammeter with ASS with 3 nos. 500/5A CT's

-

-

-

... More
BUS-BAR

-

-

-

... More
1 Set of 500A TPN Aluminium Bus Bar with colour coded PVC Sleeves

-

-

-

... More
OUTGOINGS

-

-

-

... More
4 Nos. 160A TPN MCCB

-

-

-

... More
8 Nos. 100A TPN MCCB

-

-

-

... More
3 Nos. 63A TPN MCCB

-

-

-

... More
Supplying,Receiving, fixing, testing & commissioning of above described Panel

1

-

-

... More
TOTAL CARRIED TO SUMMARY

-

-

-

... More
SAFETY EQUIPMENTS

-

-

-

... More
Supply and Erection of MS angle iron bucket stand which include 6 Nos. fire bucket with 9 ltr. Capacity with sand filling including cost of fabrication, welding and painting of complete stand & buckets with one coat of red oxide and two coats of approve paint of red color written with fire on the buckets as per fire protection with all labour and petty material required to complete the job in all respect upto the entire satisfaction of Engineer in Charge of work.

2

-

-

... More
Providing & fixing in position 1000 mm wide , Electrical Insulating Mats as per IS 15652:2006, 3mm thick, suitable for 11 KV , fire retardant, no effect of acids, alkalies and transformer oils, moisture proof, high tensile strength and texture finish / cloth impression (Anti slip , marking on top) .

10

-

-

... More
Providing & fixing in position 1000 mm wide , Electrical Insulating Mats as per IS 15652:2006, 2mm thick, suitable upto 3.3 KV , fire retardant, no effect of acids, alkalies and transformer oils, moisture proof, high tensile strength and texture finish / cloth impression (Anti slip , marking on top) .

85

-

-

... More
Supply and fixing in position approved shock treatment chart written in English, Hindi and local language. These charts shall be framed in wooden frame and covered with clear glass.

2

-

-

... More
Supply of First aid box as approved by St. John Ambulance Brigade /Indian Red Cross society conforming to IS : 2217 - 1963.

1

-

-

... More
Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.

20

-

-

... More
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.

4

-

-

... More
Supplying of Rubber gloves of 11 KV grade as per IS 4770-68.

1

-

-

... More
Supplying and fixing of MS sheet board of size 500mm x 300mm of 16 SWG with 'Entry Restricted to Authorised Person Only" near the main entrance of the Sub- Station. The lettering shall be black painted on yellow base or as approved by engineer incharge.

1

-

-

... More
Supply and fixing safety instruction chart both in Hindi & English duly framed with 3 mm thick glass as required. (approximate front area 1.00 sq. Meter)

1

-

-

... More
INTELLIGENT FIRE ALARM SYSTEM

-

-

-

... More
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the sc accessories . The panel shall be compatible for IBMS systemhedule of work under SH: PA System) and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.

-

-

-

... More
Ten Loop Panel

1

-

-

... More
Supply, installing, testing and commissioning of Repeater panel with minimum 6 inch / 160 character LCD Display complete with accessories as required.

1

-

-

... More
Supplying, installation, testing & commissioning of central graphical fire alarm management system to centrally monitor and operate the fire alarm system complete as required.

1

-

-

... More
Supplying, installation, testing & commissioning of interface unit BACnet/ Modbus protocol i.e. Supplying communication links between building management system and fire alarm control panel complete as required.

1

-

-

... More
Supplying, installation, testing & commissioning 2X250 W Class-D Amplifier with 1 independent channel and can provide automatic re-settable overcurrent, overload, overheating, overvoltage, under-voltage and DC protection

2

-

-

... More
Supplying, installation, testing & commissioning command keypad 6 zone, with microphonecomplete as required.

1

-

-

... More
Providing, laying, jointing, testing and commissioning of following sizes of m.s. pipes conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia GI fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Providing two coats of synthetic enamel paint of approved shade over two coats of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow as per the approval of the Project Manager. GIpipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects.

-

-

-

... More
Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete :

-

-

-

... More
25 mm dia

22

-

-

... More
Providing, fixing, testing & commissioning of butterfly valve (PN 1.6) (suitable for test pressure of 24 kg / sqcm) with flanges, nut bolts, gaskets, painting and necessary pad locking arrangement complete required.

-

-

-

... More
100 mm dia

9

-

-

... More
150 mm dia

8

-

-

... More
Providing, fixing, testing & commissioning of swinging type First Aid hose reel in red colour drum with 36.5 mts. long and 20 mm dia heavy duty rubber water hose, 20 mm dia Ball valve stop cock, terminating with G.M coupling & nozzle of 6mm outlet with shut off valve confirming to IS 8090 - 1976 complete with MS socket for tap-off, drum and brackets (including painting) for fixing on wall with anchor fastner, bolts & nuts conforming to IS:884-1969 complete as required.

19

-

-

... More
Providing, fixing, testing & commissioning of perlocating, rubber reinforced lined fire hose pipe (as per IS : 636, Type A) of 63 mm dia and length as described below. The hose shall be rated for brust pressure of 35.7 Kg/sqcm. Hose shall be complete with ISI marked brass male & female coupling (IS:903) bound & rivetted to hose pipe with copper rivets & 1.5 mm copper wire. (Internal fire hydrant)

38

-

-

... More
Providing, fixing, testing & commissioning of 63 mm dia instantaneous pattern branch short stainless steel pipe, 19 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required.

19

-

-

... More
Providing, fixing, testing & commissioning of standard firemans axe with heavy rubber handle.

19

-

-

... More
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required

19

-

-

... More
Providing, fixing, testing & commissioning of MS air cushion tank on top of each riser fabricated from 6mm thick MS plate, 200 mm in diameter and 1.2 m in height with dished ends fabricated from 6 mm thick MS plate with Air release valve & stop cock, flanged inlet connection with all accessories as required and conforming to IS 4736-1968. (The cushion tank should be suitable for rated working pressure.

16

-

-

... More
Providing, fixing, testing & commissioning of automatic Air release valve with 15mm dia stop cock, flanged inlet connection, pressure gauge with gun metal stop cock complete with all accessories as required and conforming to IS IS : 12992 (Part 1).

12

-

-

... More
Providing, fixing, testing & commissioning of indoor type hose lockable cabinet frames fabricated from 40 x 40 x 5 angle iron sections and 16 gauge MS sheet with full front glass door and locking arrangement, suitable to accommodate landing valves, 15 m long hoses, first-aid hose reel and branch pipe nozzle & fire mans’ axe. The cabinet frame shall be painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade, as required (Approx 2.1 m (high) x 0.9 m (wide). The item shall be complete of MS housing with front door.

-

-

-

... More
(Cost shall be inclusive of providing break glass box containing key for the cabinet along with hamer).

19

-

-

... More
Total

-

-

-

... More
Portable Chemical Fire Extinguishers

-

-

-

... More
Supply, installation, testing and commissioning of following types of extinguisher with provision of wall bracket (fixed with anchor fastner).

-

-

-

... More
Providing & fixing ISI marked portable chemical fire extinguisher, water (gas pressure) type capacity 9 litres conforming to IS: 15683:2006 with gun metal cap and nozzle and complete in all respects including initial fill and wall suspension brackets

64

-

-

... More
Providing & fixing ISI marked (IS:15683:2006) portable CO2 type fire extinguisher type 4.5 kg capacity. Including valve, discharge hose of not less than 10 mm dia & 1 M long complete in all respects including initial filled with CO2 gas confirming to IS:307-1966 & filled to a filling rate of not more than 0.667 and wall suspension bracket.

70

-

-

... More
Providing & fixing of ABC Type, Portable Fire Extinguisher, dry powder type (Gas Cartridge) conforming to IS: 15683 : 2006 with cylinder initially fully charged with dry powder, ISI marked confirming to IS:15683 : 2006 complete with standard discharge valve with tube, CI bracket for wall mounting.

-

-

-

... More
4 Kg

70

-

-

... More
Mechanical Foam type Fire Extinguisher. In HP Mild Steel Cylinders ISI marked / approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged complete in all respects including wall suspension bracket / trolley mounted and confoming to IS: 15683 : 2006

-

-

-

... More
50 Litres (trolley mounted)

4

-

-

... More
Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet confoming to IS: 2546, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters “FIRE” in black and gold. Cost shall be inclusive of providing MS stand duly painted over a coat of primer.

27.22

-

-

... More
Total

-

-

-

... More
SPRINKLER, PIPING & ACCESSORIES

-

-

-

... More
Providing, laying, jointing, testing and commissioning of following sizes of pipes conforming to IS-1239 with all accessories like all fittings (for pipes upto 50mm dia threaded forged steel fittings and for pipes above 50 mm dia GI fitting with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers (using anchor fastners) as per specification. Providing two coats of synthetic enamel paint of approved shade over two coats of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow as per the approval of the Project Manager. GIpipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls / floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, RCC work and making good the same to original conditions complete in all respects.

-

-

-

... More
All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and the supply of the same shall also be included in rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted.

-

-

-

... More
For Sprinkler system - MS `C' Heavy class pipe

-

-

-

... More
32 mm dia

230

-

-

... More
40 mm dia

155

-

-

... More
50 mm dia

95.94

-

-

... More
65 mm dia

85

-

-

... More
100 mm dia

574

-

-

... More
150 mm dia

266

-

-

... More
Providing, fixing, testing & commissioning of butterfly valve (PN 16) (suitable for test pressure of 24 kg / sqcm) with flanges, nut bolts, gaskets, painting and necessary pad locking arrangement complete required.

-

-

-

... More
100 mm dia

5

-

-

... More
150 mm dia

4

-

-

... More
Providing, fixing, testing & commissioning of brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows :

-

-

-

... More
Pendent /UPRIGHT (68 °C) sprinkler

1

-

-

... More
Providing, fixing, testing & commissioning of inspectors test assembly complete with test valve, sight glass sectional drain valve, union with corrosion resistant orifice all complete strictly as per drawing.

3

-

-

... More
Providing, fixing, testing & commissioning of dial type (100 mm) pressure gauge with isolation ball valve suitable for working pressure of 250 PSI with no Syphon. Cost shall be inclusive of providing any short pieces, nipples, elbows etc as required.

6

-

-

... More
Supply, installation, testing and commissioning of electrically operated water flow switches (Vane type) including all accessories, complete required.

1

-

-

... More
Providing & Fixing of Installation Control Valve with turbine type automatic Alarm Gong to be connected with control valve, drain & test valve and all other necessary components as per manufacturer's specifications complete as required.

-

-

-

... More
150 mm dia

1

-

-

... More
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required

-

-

-

... More
150mm dia

1

-

-

... More
EXTERNAL FIRE SYSTEM

-

-

-

... More
Providing and fixing in trenches the following sizes of MS class `C' (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, GI nuts, bolts and washers including excavation in all kind of soil, refilling, ramming, shoring, removing the excavated surplus material, providing adequate support to the pipe and making good the same complete as required. Rate shall include for dewatering necessary to execute the work. The pipe shall not be less than 1.0 m below ground level at any point. Pipes shall embedded all round 150 mm thick compacted silver sand and protectionto MS pipes and fitting by applying pypkote primer @ 100 gm/sqm). Thereafter wrapping 4 mm thick pypkote (AW4mm) protection coating by thermo fusion process. Overlap shall be maintained at 20 mm. The application shall be strictly as per manufacturers’ specifications.

-

-

-

... More
MS `C' Heavy class pipe

-

-

-

... More
150 mm dia

1250

-

-

... More
Providing & fixing stainless steel fire brigade inlet connection (suction collecting head) consisting of 4 Nos. 63 mm dia instantaneous type male couplings with built-in check valves, 1 No. 150 mm dia sluice valve, and 150 mm dia flanged outlet complete with bolts, nuts and rubber insertions as required and as per IS:904-1963.

4

-

-

... More
Providing & fixing gun-metal fire brigade suction hose coupling (draw-out connection) with nut for female coupling as per IS: 902-1992 (Reaffirmed 2007) complete with 150 mm dia GI suction pipe and 150 mm dia foot valve (to be connected to static tank). Provision of GI drop pipe and foot valve shall be made in all the fire water static storage tanks (___Nos) (GI pipe to be paid separately through appropriate item while cost of foot valve to be included).

1

-

-

... More
Providing, fixing, testing and commissioning of Stainless Steel fire hydrant single landing valve with 80 NB flanged inlet, brass spindle controlled 63 mm dia female instantaneous outlet type. G.M coupling, blank cap, chain, twist release type lug & all accessories. Conforming to IS:5290. Including fixing with anchor fastner and flanged tapping from wet riser and providing pressure gauge with ball valve with all accessories, nuts, bolts, gaskets, painting complete as required.

36

-

-

... More
Providing, fixing, testing & commissioning of perlocating, rubber reinforced lined fire hose pipe (as per IS : 636, Type A) of 63 mm dia and length as described below. The hose shall be rated for brust pressure of 35.7 Kg/sqcm. Hose shall be complete with ISI marked brass male & female coupling (IS:903) bound & rivetted to hose pipe with copper rivets & 1.5 mm copper wire. (Internal fire hydrant)

34

-

-

... More
Providing, fixing, testing & commissioning of butterfly valve (PN 1.6) (suitable for test pressure of 24 kg / sqcm) with flanges, nut bolts, gaskets, painting and necessary pad locking arrangement complete required.

-

-

-

... More
80 mm dia

17

-

-

... More
150 mm dia

8

-

-

... More
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required

8

-

-

... More
Providing, fixing, testing & commissioning of automatic Air release valve with 15mm dia stop cock, flanged inlet connection, pressure gauge with gun metal stop cock complete with all accessories as required and conforming to IS IS : 12992 (Part 1).

4

-

-

... More
Constructing masonry Chamber 60x60x75cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement : 4 fine sand) for sluice valve, with C.I surface box 100mm. top diameter,160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand : 10graded stone aggregate 40mm nominal size) and inside plastering with cement mortat 1:3 ( 1cement :3 coarse sand) 12mm thick finished with a floating coat of neat cement complete as per standard design.

-

-

-

... More
With common burnt clay F.P.S.(non modular) bricks of class designation 7.5

8

-

-

... More
Providing and fixing Fire Hose Cabinet made up of fully welded construction of size 750 x 600 x 250 mm, fabricated from 14 SWG GI sheet, having hinged double front door with locking arrangements and partially glazed with 5 mm thick glass. Cabinet must have Stove enamelled Fire Red finish with "FIRE HOSE" written on front and must be suitable for housing 2 Nos. 15m long synthetic Hose with couplings, 1 No. Branch Pipe, Fire Man Axe complete as specified in drawing.

17

-

-

... More
Total

-

-

-

... More
FIRE PUMPS AND EQUIPMENTS

-

-

-

... More
Supply, installation, testing and commissioning of terrace fire pump comprising of the following:

-

-

-

... More
Horizontal mono-block centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply.

-

-

-

... More
The pump casing shall be CI, shaft shall be CS & impeller / shaft sleeve / casing wearing ring shall be bronze. The system shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side. (The pump should meet the condition and shall be gotten approved by the Local fire Authority).

-

-

-

... More
Squirrel cage induction motor TEFC type for operation on 415 V, 3 phase 50 HZ AC supply for the above pump with speed of 2900 R.P.M.

-

-

-

... More
Suitable cement concrete foundation with plaster, (design and drawing to be provided by the Contractor while the foundation will be done by others) complete with Antivibration arrangement of cushy foot mounting.

-

-

-

... More
For pump defined above & of duty as follows :

-

-

-

... More
Flow : 900 LPM (On each tower.)

-

-

-

... More
Head : 35 mts

7

-

-

... More
Supply, installation, testing and commissioning of electrically driven high pressure centrifugal fire hydrant / sprinkler pump, suitable for automatic operation consisting of the following:

-

-

-

... More
Horizontal end suction / high pressure single, centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and S.S. (304) Shaft with mechanical seal, capable for delivering 2850 LPM at outlet head of 70 mts to ensure a minimum pressure of 3.5 Kg/Sqcm at the farthest or topmost hydrant / sprinkler. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side. (The pump should be tested for bench mark at factory and shall be gotten approved by the Local fire Authority).

-

-

-

... More
Pump shall be capable of furnishing not less than 150% of rated capacity at a head of not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head.

-

-

-

... More
Squirrel cage induction motor, TEFC type suitable for operation on 415 volts, 3 phase 50 HZ A.C supply, for the above pump with synchronous speed of 2900 RPM, conforming to IP 55 protection & class F insulation. The motor shall conform to IS 325-1978 (up to date) with flexible coupling and coupling guard, complete as required.

-

-

-

... More
c. Common base plate for (a) and (b) from M.S. Channel for required size.

-

-

-

... More
d. Suitable cement concrete foundation with cement concrete plaster (design and drawing to be provided by the Contractor while the foundation will be done by others) complete with anti-vibration arrangement of cushy foot mountings.

-

-

-

... More
For pump defined above & of duty as follows :

-

-

-

... More
Flow : 2850 LPM

-

-

-

... More
Head : 70 mts

1

-

-

... More
Supply, installation, testing and commissioning of Diesel Engine driven fire pump suitable for automatic operation comprising of the following and conforming to BS 649/IS 10002 all amended upto date.

-

-

-

... More
Horizontal end suction / high pressure single / multistage, centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and S.S. (304) Shaft with mechanical seal, capable for delivering 2850 LPS at outlet head of 70 mts to ensure a minimum pressure of 3.5 Kg/Sqcm at the farthest or topmost hydrant / sprinkler. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side. (The pump should be tested for bench mark at factory and shall be gotten approved by the Local fire Authority).

-

-

-

... More
Pump shall be capable of furnishing not less than 150% of rated capacity at a head of not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head.

-

-

-

... More
b. Heat exchanger cooled (secondary cooling) diesel engine of speed 1500 RPM suitable for the above pump with automatic starting mechanism and other accessories including fuel tank (fabricated from 3mm MS sheet, painted with two coats of synthetic enamel paint over a coat of primer) of capacity adequate to sustain pump operation for 8 hours continuous working. The tank shall be fitted with Magnetic oil level indicator, MH with cover, drain valve, air vent including structural supports (painted with approved shade), 2 Nos. x 12 volt battery, heat exchanger with necessary piping connections & fittings, flexible coupling, coupling guard & exhaust pipe connection complete as required.

-

-

-

... More
c. Common base plate for (a) and (b) from M.S. channel of required size.

-

-

-

... More
d. Suitable cement concrete foundation with plaster, (design and drawing to be provided by the Contractor while the foundation will be done by others) complete with antivibration arrangement of cushy foot mountings.

-

-

-

... More
For pump defined above & of duty as follows :

-

-

-

... More
Flow : 2850 LPM

-

-

-

... More
Head : 70 mts

1

-

-

... More
Supply, installation, testing and commissioning of jockey pump (pressurisation pump) comprising of the following:

-

-

-

... More
a. Vertical Multistage, centrifugal pump, suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with Flexible coupling and coupling guard, complete as required. Jockey pump shall be of stainless steel construction.

-

-

-

... More
The pump head and base shall be CI GG20 construction and impellers, diffusers, shaft sleeve, seal bush & pump shaft shall be in SS 304 material. The pump shall be provided with mechanical seal The system shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side (The pump should meet the condition and shall be gotten approved by the Local fire Authority).

-

-

-

... More
b. Squirrel cage induction motor TEFC type for operation on 415 V, 3 phase 50 HZ AC supply for the above pump with a synchronous speed of 2900 R.P.M. with flexible coupling and coupling guard etc. as required.

-

-

-

... More
c. Common base plate for (a) and (b) from M.S. channel as required size.

-

-

-

... More
d. Suitable cement concrete foundation with plaster, (design and drawing to be provided by the Contractor while the foundation will be done by others) complete with Antivibration arrangement of cushy foot mounting.

-

-

-

... More
For pump defined above & of duty as follows :

-

-

-

... More
comman jocky

-

-

-

... More
Flow : 180 LPM

-

-

-

... More
Head : 70 mts

1

-

-

... More
Providing & fixing MS Class ‘C’ diesel engine exhaust pipe (including all fittings, clamps, steel support) of 100mm dia for the engine. The pipe shall be insulated with 100 mm thick mineral wool insulation wrapped in chicken mesh and clad with 24 gauge aluminium sheet.

10

-

-

... More
Providing, fixing, testing & commissioning of Air release valve with 25mm dia stop cock, flanged inlet connection, pressure gauge with gun metal stop cock complete with all accessories as required and conforming to IS IS : 12992 (Part 1).

10

-

-

... More
Providing, fixing, testing & commissioning of dial type (100 mm) pressure gauge with isolation ball valve suitable for working pressure of 250 PSI with no Syphon. Cost shall be inclusive of providing any short pieces, nipples, elbows etc as required.

20

-

-

... More
Providing, fixing, testing & commissioning of forged brass ball valve with forged brass ball suitable for test pressure of not less than 37.5 kg / sq.cm of the following size with nuts, bolts, gaskets, necessary accessories, etc as required.

-

-

-

... More
(Cost shall be inclusive of providing necessary union / flange connection).

-

-

-

... More
25 mm dia

20

-

-

... More
Providing, fixing, testing & commissioning of butterfly valve (suitable for test pressure of 37.5 kg / sqcm) with flanges, nut bolts, gaskets, painting and necessary pad locking arrangement complete required.

-

-

-

... More
65 mm dia

4

-

-

... More
80 mm dia

2

-

-

... More
100 mm dia

10

-

-

... More
150 mm dia

12

-

-

... More
Providing, fixing, testing and commissioning of dual plate C.I. wafer type check valve of pressure 37.5 Kg/sq.cm with flanges, Nut,bolts & washers, painting etc. complete as required.

-

-

-

... More
100 mm dia

2

-

-

... More
150 mm dia

10

-

-

... More
Providing, fixing, testing and commissioning of CI `Y' strainer for pressure of 37.5 kg / sq.cm with bronze perforated sheet basket including rubber gasket, flanges, nuts, bolts and washers, panting of the same complete as required and suitable for system pressure.

-

-

-

... More
150 mm dia

10

-

-

... More
Providing, fixing, testing and commissioning of heavy class MS suction & delivery headers of required length conforming to IS:3589 with welded joints standard MS Fittings and with end flange connections having inlet & outlet flanged connections and painting of two coats of synthetic enamel paint over two coats of primer as per specification including GI supports from wall, floors & ceiling complete as required. Cost should be inclusive of all supports/clamps / brackets, anchor fastner, expansion bellows etc. as required (all in GI).

-

-

-

... More
For hydrant system - MS `C' Heavy class pipe

-

-

-

... More
25 mm dia

809

-

-

... More
80 mm dia

299

-

-

... More
200 mm dia

25

-

-

... More
HVAC EQUIPMENT

-

-

-

... More
DOUBLE SKIN AIR HANDLING UNITS

-

-

-

... More
Supply, Installing, testing and commissioning of Double skin construction Air Handling Units as per specification. All AHU's shall be draw thru type, complete with filter section, minimum 8/6 row deep (8 row deep for TFA, 6 row deep for all others, unless specified otherwise in BOQ below) chilled water coil of copper tube & aluminium fins, squirrel cage induction motor suitable for use with variable frequency drive, primary & secondary condensate drain pans duly insulated, forward/backward curved, centrifugal fan(s), belt drive, vibration isolators. Fan Motor shall be suitable for 415±10% volts & confirm to EFF1, 50 Hz, 3 phase AC supply and shall have high efficiency motors. AHU shall be selected for a maximum face velocity of 500 FPM across cooling coil and across filters. Minimum thickness of AHU casing shall be 25mm as per specification for ceiling suspended and 43 mm for AHU. The CSU's noise level shall be NC 40 for all the areas.The height of the ceiling suspended AHU's should not be more tha 650 mm.

-

-

-

... More
Air handling capacities shall be as follows:

-

-

-

... More
DESCRIPTION

-

-

-

... More
GROUND FLOOR

-

-

-

... More
MINOR OT- Dehum CFM-2400 ,TR--2.5,Static MM-30,Kw-1.10 ,Type-CS AHU

1

-

-

... More
TFA AHU-Dehum CFM-1390,TR--10.9,Static MM-30,KW-0.05,Type-CS AHU

1

-

-

... More
FIRST FLOOR

-

-

-

... More
TFA AHU-Dehum CFM-150,TR--1.2,Static MM-20,KW-0.37,Type-CS AHU

1

-

-

... More
SECOND FLOOR

-

-

-

... More
*ICU BLOCK-Dehum CFM-13000,TR--17.2,Static MM-30,KW-7.50,Type-FM AHU

2

-

-

... More
DRUG STORE+CHANGE ROOMS-Dehum CFM-4600,TR--6,Static MM-30,KW-2.2,Type-FM AHU

1

-

-

... More
PRIVATE ROOMS CORRIDOR-Dehum CFM-3400,TR--3.6,Static MM-30,KW-2.2,Type-CS AHU

1

-

-

... More
TFA AHU-Dehum CFM-1600,TR--12.8,Static MM-30,KW-.05,Type-CS AHU

1

-

-

... More
*ICU AHU shall be provided with pre+Microvee filters

-

-

-

... More
CS AHU - CEILING SUSPENDED AIR HANDLING UNIT

-

-

-

... More
FM AHU - FLOOR MOUNTED AIR HANDLING UNIT

-

-

-

... More
TFA AHU - TREATED FRESH AIR AIR HANDLING UNIT

-

-

-

... More
Supplying & installation of 6 row deep Chilled Water Cooling Coils, making connections with MS Chilled Water pipe and removal of existing DX Coils from existing AHU's. Chilled Water Cooling coils shall be minimum 12.5 mm dia tubes, minimum 0.4 mm thick with sine wave aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame. Face and surface areas shall be such as to ensure rated capacity from each unit and such that the air velocity across the coil shall not exceed 150 meters per minute. The coil shall be pitched in the unit casing for proper drainage. The coil shall have copper header with chilled water supply & return connections protruding out of AHU casing by minimum 150 mm and fitted with dielectric coupling for connection with MS pipes. Each coil shall be factory-tested at 21 kg per sq. m air pressure under water. Tube shall be hydraulically / mechanically expanded for minimum thermal contact resistance with fins. Fin spacing shall be 4 - 5 fins per cm. Water pressure drop in coil shall not exceed 10 PSIG. The Price quaoted should be inclusive of servicing & commissioning of existing AHU's

-

-

-

... More
MODULAR OT+BONE MARROW-CFM-3000,TR-10.6,FM AHU

3

-

-

... More
FAN COIL UNITS

-

-

-

... More
Supply,installing, testing and commissioning of vertical ,horizontal powder coated Fan Coil Units, blow thru type, each complete with 3 rows deep chilled water coil & one or more centrifugal fans, aluminium/synthetic cleanable filters, primary & secondary condensate drain pans duly insulated, casing, coil, piping connections through copper pipes, condensate drain connection, wiring, control wiring in conduit upto the thermostat boxes. All fan coil units shall be suitable for 220±6% volts, 50 cycles single phase power supply. Fan coil unit shall be of following arrangement and refrigeration capacity. All Fan Coil units shall be with 3 to 5mm wg external static pressure. The nosie level shall be NC 37 for all rooms.

-

-

-

... More
3.0 TR nominal capacity

2

-

-

... More
2.5 TR nominal capacity

5

-

-

... More
2.0 TR nominal capacity

7

-

-

... More
1.5 TR nominal capacity

2

-

-

... More
CONTROL PANEL FOR AIR HANDLING UNITS

-

-

-

... More
Supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels. Wiring and earthing terminating into MCCB in each panel shall be provided by the electrical contractor.

-

-

-

... More
All internal wiring and Aluminium earthing of air handling unit motors from the panel shall be included.

-

-

-

... More
All terrace control panel shall be suitable for outdoor application IP 55/65

-

-

-

... More
The panel shall include the following components and accessories.

-

-

-

... More
Suitable rating incoming MCCB/MCB

-

-

-

... More
Suitable rating AC-3 duty contactor(s), overload relay with builtin single phasing preventor, star delta timer (For S/D starters).

-

-

-

... More
96 sq. mm. digital voltmeter, ammeter, selector switches, CTs & control MCBs.

-

-

-

... More
Phase indicating lights & control MCBs.

-

-

-

... More
Push buttons for manual start/stop of motor

-

-

-

... More
ON status indicating light for starter with control MCB.

-

-

-

... More
Minimum 2 pole auto/manual selector switch .

-

-

-

... More
Time delay relay for delayed restart of motor.

-

-

-

... More
220/24V control transformer for 2 way motorized valve.

-

-

-

... More
Interlocking terminals & wiring for fire damper, motorized dampers etc. as per control scheme.

-

-

-

... More
All panels with more than one outgoing starter feeder shall be provided with separate MCCB/MCB for incoming & outgoing.

-

-

-

... More
The number of AHU control panels shall be as follows.

-

-

-

... More
25 amps MPCB, upto 7.5 HP DOL starter.

8

-

-

... More
Note: The selection contactor and relay shall be done as per Type-2 coordination chart

-

-

-

... More
AXIAL FLOW FANS

-

-

-

... More
Supply, installation, testing and commissioning of Tube/Vane Axial Fans (Fans shall be AMCA certified), complete with TEFC motor, drive and vibration isolators. Motor shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase AC supply and shall be High efficiency class EFF1 for all the fans. The fan shall be low RPM and selected for low noise level. Fan capacities based on 30-35 mm WC static pressure, shall be as follows :

-

-

-

... More
Note: Fan installed in open area shall be provided with weather cowl. Cowl shall be molded to cover and overlap the entire fan casing and base support to protect it from adverse condition.

-

-

-

... More
DESCRIPTION

-

-

-

... More
OPD BLOCK

-

-

-

... More
LIFTWELL PRESSURIZATION-CFM-10600, Type/ Insulation-Vane/Class F, Motore-7.5 HP

2

-

-

... More
SERVICE BLOCK

-

-

-

... More
CENTRAL KITCHEN EXHAUST-CFM-7300, Type/ Insulation-Vane/Class F, Motore- 5 HP

1

-

-

... More
CENTRAL KITCHEN SUPPLY-CFM-6600, Type/ Insulation-Vane/Class F, Motore- 5 HP

1

-

-

... More
AC PLANT ROOM/SUBSTATION EXT-CFM-11400, Type/ Insulation-Vane/Class F, Motore- 7.5 HP

1

-

-

... More
AC PLANT ROOM/SUBSTATION SUPP-CFM-11400, Type/ Insulation-Vane/Class F, Motore- 7.5 HP

1

-

-

... More
LIFTWELL PRESSURIZATION-CFM-9850, Type/ Insulation-Vane/Class F, Motore- 7.5 HP

1

-

-

... More
LAUNDARY EXHAUST-CFM-7400, Type/ Insulation-Vane/Class F, Motore- 5 HP

1

-

-

... More
LAUNDARY SUPPLY-CFM-7400, Type/ Insulation-Vane/Class F, Motore- 5 HP

1

-

-

... More
PLUMBING PLANT RM EXHAUST-CFM-4000, Type/ Insulation-Vane/Class F, Motore-3 HP

1

-

-

... More
PLUMBING PLANT RM SUPPLY-CFM-4000, Type/ Insulation-Vane/Class F, Motore-3 HP

1

-

-

... More
STP ROOM EXHAUST-CFM-9700, Type/ Insulation-Vane/Class F, Motore-7.5 HP

1

-

-

... More
STP ROOM SUPPLY-CFM-9700, Type/ Insulation-Vane/Class F, Motore-7.5 HP

1

-

-

... More
WARD BLOCK

-

-

-

... More
LIFTWELL PRESSURIZATION-CFM-10600, Type/ Insulation-Vane/Class F, Motore-7.5 HP

1

-

-

... More
AHU FAN SECTION

-

-

-

... More
Supply, installation, testing and commissioning of FAN SECTION Double Skin Casing shall be Double Skin Inner and Outer Panel Shall be made out of 24 Guage GI with 25 mm Thick Puff Insulation, The filter shall have 90% down to 10 microns filtration efficiency BLOWER DIDW Backward Curved Aerofoil Blade, 225 mm Dia Fan Heavy Duty Centrifugal Blower, Casing shall be 16 G GI upto 1000mm Dia and 14 G MS above 1000mm Dia , DIDW (Double Inlet Double width) class I construction, Non over loading Type with backward Aerofoil blade and mounted on EN 8 Shaft duly dynamically and statically balanced.. 0.5 HP/4 Pole, Class F Motor Motor shall be suitable for 415 Volts, 50 Cycles,3 Phase AC Power Supply, Extra Fan Accessories: Vibration Isolator, Damper and Canvass Connection at Blower Outlet. Fan Model-ACD-225,CFM-1100(CMH-1870),Pressure.-40,O.Velocity.- 6.3, RPM-2296,BHP.-0.3, Motor: 0.5 HP/4 Pole, Sound Level At 3 mtr. (db) -44.

-

-

-

... More
Fan capacities shall be as follows:

-

-

-

... More
DESCRIPTION

-

-

-

... More
TOILET EXHAUST, GRID 19-21/GF TO SF-CFM-4160,Motor HP-3

1

-

-

... More
TOILET EXHAUST, GRID 15/GF TO SF-CFM-970,Motor HP-1

1

-

-

... More
TOILET EXHAUST, GRID 09/GF TO SF-CFM-970,Motor HP-1

1

-

-

... More
TOILET EXHAUST, GRID 01/GF TO SF-CFM-3540,Motor HP-3

1

-

-

... More
CONTROL PANELS FOR FANS

-

-

-

... More
Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.

-

-

-

... More
All wiring and copper earthing of motors from the panel shall be included.

-

-

-

... More
All outgoing shall be provided with stop / manual / auto/ selector switch to facilitate operation through BAS. All starters shall be provided with potential free contact for connections to Building Automation System.

-

-

-

... More
The panel shall include the following components & accessories.

-

-

-

... More
Suitable rating incoming MCCB/MCB

-

-

-

... More
Suitable rating AC-3 duty contactor(s), overload relay with builtin single phasing preventor, star delta timer (For S/D starters).

-

-

-

... More
96 sq. mm. digital voltmeter, ammeter, selector switches, CTs & control MCBs.

-

-

-

... More
Phase indicating lights & control MCBs.

-

-

-

... More
Push buttons for manual start/stop of motor.

-

-

-

... More
ON status indicating light for starter with control MCB.

-

-

-

... More
Minimum 2 pole auto/manual selector switch & 1 NO + 1 NC potential free aux. contacts for use by Building automation system.

-

-

-

... More
Time delay relay for delayed restart of motor

-

-

-

... More
Interlocking terminals & wiring for fire damper, motorized dampers etc. as per control scheme.

-

-

-

... More
The number of control panels shall be as follows:

-

-

-

... More
25 amps MPCB, upto 7.5 HP DOL starter.

18

-

-

... More
INLINE FANS

-

-

-

... More
Supplying, installing, testing and commissioning of INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10% volt single phase 50 cycles AC supply.

-

-

-

... More
Fan capacities shall be as follows:

-

-

-

... More
DESCRIPTION

-

-

-

... More
OPD BLOCK

-

-

-

... More
TOILET EXHAUST/GF-CFM-800,Static-10

2

-

-

... More
TOILET EXHAUST-PUBLIC TOILET/GF-CFM-1600,Static-10

1

-

-

... More
PANTRY EXHAUST /GF-CFM-300,Static-10

1

-

-

... More
SERVICE BLOCK

-

-

-

... More
TOILET EXHAUST/GF-CFM-1000,Static-10

1

-

-

... More
TOILET EXHAUST/FF-CFM-1000,Static-10

1

-

-

... More
WARD BLOCK

-

-

-

... More
PANTRY EXHAUST, GRID 20/GF-CFM-500,Static-10

1

-

-

... More
PANTRY EXHAUST, GRID 20/FF-CFM-220,Static-10

1

-

-

... More
PANTRY EXHAUST, GRID 01/FF-CFM-255,Static-10

1

-

-

... More
PANTRY EXHAUST, GRID 20/SF-CFM-220,Static-10

1

-

-

... More
PANTRY EXHAUST, GRID 01/SF-CFM-255,Static-10

1

-

-

... More
PROPELLER FANS

-

-

-

... More
Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows :

-

-

-

... More
225 mm dia 900 RPM fan suitable for 220±6% volts 50 cycles, 1 phase AC supply.

31

-

-

... More
AIR COOLED SPLIT AIR CONDITIONING UNITS

-

-

-

... More
Supply, installing, testing and commissioning of ceiling mounted/high wall mounted Air Cooled Split Air conditioning Units as described in specifications. The unit shall be complete with fan coil unit and external condensing unit, complete in all respects, inclusive of copper refrigerant piping, GI condensate drain piping (10m), refrigerant piping length (15m), valves and insulation. Quoted price shall include cost of cooling thermostat, wiring, control wiring and earthing. The unit capacities shall be as follows :

-

-

-

... More
2.0 TR split air conditioning units as described above

4

-

-

... More
1.5 TR split air conditioning units as described above

2

-

-

... More
PACKAGE UNITS

-

-

-

... More
COOLING/HEATING THERMOSTAT

-

-

-

... More
Supply, installation, testing and commissioning of THERMOSTAT (AHU) cooling/heating. The thermostat shall be electronic room temperature controller with digital display & fan speed control, capable of providing individual space temperature control for cooling/heating application. The controller shall produce output to cooling/heating coils in response to load change in rooms. The controller shall be designed to modulate two control devices such as 2 way motorized valves for chilled/hot water duty.

8

-

-

... More
Supply, installation, testing and commissioning of snap acting THERMOSTAT (FCU) cooling/heating. The thermostat shall be electronic room temperature controller with digital display & fan speed control, capable of providing individual space temperature control for cooling/heating application. The controller shall produce output to cooling/heating coils in response to load change in rooms. ( Including wiring from Thermostat to Actuator).

16

-

-

... More
Total Carried to Summary

-

-

-

... More
PIPING - CHILLED WATER

-

-

-

... More
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation)

-

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.

-

-

-

... More
100 mm dia

30

-

-

... More
80 mm dia

250

-

-

... More
65 mm dia

100

-

-

... More
50 mm dia

140

-

-

... More
40 mm dia

110

-

-

... More
32 mm dia

50

-

-

... More
25 mm dia

145

-

-

... More
20 mm dia

100

-

-

... More
INSULATED VALVES

-

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.

-

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified

-

-

-

... More
50 mm dia

6

-

-

... More
40 mm dia

2

-

-

... More
32 mm dia

2

-

-

... More
25 mm dia

4

-

-

... More
20 mm dia

2

-

-

... More
Providing and fixing the following Ball valves without strainer in position conforming to technical specifications :

-

-

-

... More
25 mm dia

7

-

-

... More
20 mm dia

9

-

-

... More
Supply, installation, testing & commissioning of Ball valve with strainer For details refer spec.

-

-

-

... More
25 mm dia

7

-

-

... More
25 mm dia

9

-

-

... More
Supply, installation, testing & commissioning of Globe Valve For details refer spec.

-

-

-

... More
25 mm dia

7

-

-

... More
20 mm dia

9

-

-

... More
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.

-

-

-

... More
50 mm dia

3

-

-

... More
40 mm dia

1

-

-

... More
32 mm dia

1

-

-

... More
25 mm dia

2

-

-

... More
20 mm dia

1

-

-

... More
Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modualating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum.

-

-

-

... More
50 mm dia

3

-

-

... More
40 mm dia

1

-

-

... More
32 mm dia

1

-

-

... More
25 mm dia

2

-

-

... More
20 mm dia

1

-

-

... More
Supply,installation, testing and commissioning of TWO WAY MODULATING (FCU) provided with spring return function in chilled water lines at each fan coil unit. The actuator of the motorized valve shall have required shut off capability of minimum 4 bar rating WITH 230 V / 24 V transformer duly encased and wired. The valves shall be suitable for following pipe sizes

-

-

-

... More
Pressure rating - PN-16

-

-

-

... More
25 mm dia

16

-

-

... More
20 mm dia

6

-

-

... More
Supplying, installation, testing and commissioning of 19 mm Auto air vents

6

-

-

... More
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required

16

-

-

... More
Providing & fixing in position the mercury in glass industrial type thermometers.

16

-

-

... More
Providing and fixing in position the Drain- Cock with ball valve 25 mm dia

12

-

-

... More
Providing and fixing in position the following uPVC pipes for Drain, cut to required lengths and installed with all screwed joints, and providing and fixing in position the necessary elbows, tees and reducers as per specifications.

-

-

-

... More
32 mm dia pipes

30

-

-

... More
25 mm dia pipes

130

-

-

... More
20 mm dia pipes

280

-

-

... More
Total Carried to Summary

-

-

-

... More
AIR DISTRIBUTION

-

-

-

... More
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.

-

-

-

... More
Thickness 0.63 mm sheet (24 Gauge)

1235

-

-

... More
Thickness 0.8 mm sheet (22 Gauge)

160

-

-

... More
Thickness 1.0 mm sheet (20 Gauge)

465

-

-

... More
Thickness 1.25 mm sheet (18 Gauge)

10

-

-

... More
Supply, fabrication, installation and testing the Flexible connections constructed of fire resistance flexible double canvas sleeve as per the approved shop drawings.

14

-

-

... More
Supply, installation and testing of galvanised steel construction Louver dampers within ducts to be provided with suitable ducts lever and quadrants for manual control of volume of air flow and for proper balancing of the air distribution system.

18

-

-

... More
Supplying, fixing testing commissioning of Supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.

28

-

-

... More
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.

23

-

-

... More
Supply, installation, testing and balancing of powder coated Extruded Aluminium supply Air Grilles with volume control dampers in accordance with the approved shop drawings and specifications.

11

-

-

... More
Supply, installation, testing and balancing of Air Grilles without volume control dampers for return/exhaust air in accordance with the approved shop drawings and specifications.

10.3

-

-

... More
Supplying, installation, testing and commissioning of GI construction fresh air louvers with bird screen painted in baked enamel shade with metallic frame work complete as per specification approved drawings and schedules. Louvers need to be suitable in order avoid rain water entry in to spaces @ 15 degree deflection with bird screen complete as per specification approved drawings and schedules.

15.1

-

-

... More
Supplying , Installing, testing and commissioning of powder coated extruded aluminium exhaust air louvers with bird screen with metallic frame work & fixing accessories , to be fixed on external wall to exhaust air from respective area to ambient, it shall be suitable for exhausting required air in CFM . Louvers need to be suitable in order avoid rain water entry in to spaces @ 15 degree deflection with bird screen complete as per specification approved drawings and schedules.

15

-

-

... More
Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.

-

-

-

... More
Fire Damper

4.2

-

-

... More
Actuator

8

-

-

... More
Supply, installation, testing and commissioning of back draft dampers in pressurization fans

4

-

-

... More
Supply, Installation, Testing and Balancing of powder coated extruded aluminium construction Linear Grilles with removable core as per approved shop drawings and specifications.

2.4

-

-

... More
Total Carried to Summary

-

-

-

... More
THERMAL INSULATION

-

-

-

... More
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications.

-

-

-

... More
25 mm thick

195

-

-

... More
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.

-

-

-

... More
19 mm

569.97

-

-

... More
25 mm

30

-

-

... More
Supplying, installing and testing of 19 mm thick insulation with protective coating on chilled water and condensate drain piping and fitting like valves, flanges union, etc. as per the approved shop drawings and specifications, the 'R' value should be minimum R-0.35:

-

-

-

... More
32 mm dia condensate drain pipes.

31.2

-

-

... More
25 mm dia condensate drain pipes.

130

-

-

... More
20 mm dia condensate drain pipes.

280

-

-

... More
HVAC EQUIPMENT

-

-

-

... More
WATER COOLED CHILLED WATER UNITS

-

-

-

... More
Supply, Installation, testing, connection and participation in commissioning of SCREW WATER CHILLING UNITS each complete with 100 TR actual capacity (200 TR PLANT CAPACITY ) at specified conditions, scroll compressor, motor, starter panel machine mounted, water cooled condenser, insulated chiller, flow switch at chiller and condenser, vibration isolators, integral refrigerant piping and wiring, accessories as required and called for, automatic and safety controls mounted in central micro-processor based console panel and all mounted on a steel frame complete as per specifications. Motor shall be suitable for 415±10% 50 cycles. 3 phase AC supply. Refrigerant used shall be Ozone friendly R-134a/R-123 as detailed in specifications. The chilling unit shall be compatable with BMS system.

-

-

-

... More
CHILLER

-

-

-

... More
Chilled Water IN 54 DEG F

-

-

-

... More
Chilled Water OUT 44 DEG F

-

-

-

... More
Fouling Factor 0.0005

-

-

-

... More
CONDENSER

-

-

-

... More
Condenser Water IN 90 DEG F

-

-

-

... More
Condenser Water OUT 100 DEG F

-

-

-

... More
Fouling Factor 0.001

-

-

-

... More
Minimum COP 5.3

-

-

-

... More
IKW/TR 0.82

-

-

-

... More
should confirm to ARI 550/590-1998

-

-

-

... More
REFRIGERANT

-

-

-

... More
R-134a

-

-

-

... More
Chilling units as described above OF CAPACITY 100TR

2

-

-

... More
PUMPS

-

-

-

... More
Supplying, installing, testing and commissioning of PN16 rated Axial Split Coupled Vertical Inline Pump complete with CI Casing, Bronze impeller (as per specifications), SS Shaft, mechanical seal(should be easily replaceable without disturbing the pump shaft and motor shaft). The pump motor shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply. The motor selected shall be energy efficient having efficiency (Class I) at full load ranging between 91.5% to 94% in accordance with motor rating as per specification. Minimum pump efficiency shall be 70%. The motor of pumps shall be suitable for operation on variable frequency drive and confirm to EFF1/IE2. Variable Application Pump to be provided with motor mounted factory integrated IP55 VFD for sensorless/wireless control and VFD should be capable to vary till 60Hz to meet the desired duty parameters.2 Nos of Wireless sensors must be considered for each zone and if any wiring required to pump controller shall be included in cost.Motor Mounted Integrated VFD should be pre-wired to motor from the OEM factory for unit responsibility and VFD must display dynamic flow and head of each operating pump all the time. All pumps shall be properly aligned at manufacturer's facility. The pumps are compatable with BMS system. Separate Wireless Controller with IP54 protection to be provided for maintaining the redundancy of Variable Speed Pumping System(VSPS). The quoted price shall include cost of thermal insulation and cladding for chilled water Pumps. Pumps shall be selected as per following parameters;

-

-

-

... More
Primary chilled water Pumps (including one as standby)

-

-

-

... More
Flow rate = 240 USGPM

-

-

-

... More
Pump Head = 15M of water column

-

-

-

... More
Pump Motor HP = 5.0 HP

3

-

-

... More
Condenser Water Pumps (including one as standby)

-

-

-

... More
Flow rate = 300 USGPM

-

-

-

... More
Pump Head = 20 M of water column

-

-

-

... More
Pump Motor HP = 10 HP

3

-

-

... More
Secondary chilled water Pumps suitable for operation with Motor Mounted IP55 rated VFD and IE5 Motor (including one as standby) for Zone A (Lab Block, Nuclear Therapy Block, Radiotherapy Block)

-

-

-

... More
Flow rate = 250 USGPM

-

-

-

... More
Pump Head = 30M of water column

-

-

-

... More
Pump Motor HP = 10 HP

2

-

-

... More
Secondary chilled water Pumps suitable for operation with Motor Mounted IP55 rated VFD and IE5 Motor(including one as standby) for Zone B for OPD Block

-

-

-

... More
Flow rate = 256 USGPM

-

-

-

... More
Pump Head = 22M of water column

-

-

-

... More
Pump Motor HP = 7.5 HP

2

-

-

... More
COOLING TOWER

-

-

-

... More
Supply, installation, testing and commissioning of Induced Draft Cooling Towers for air conditioning system. Each tower shall be complete with FRP basin, mounted on structural steel rail supports with spring vibration isolators. casing, distribution system, twin cell, filling, louvers, OSHO approved access ladders & platforms, electronic water level control, fan and motor. Motor shall be with VFD and rated for 415±10% volts, 50 cycles, 3 phase power supply, Isolator panel at cooling tower and earthing, shall also be included. The noise level shall not exceed 60 dBA at a distance of 15 meter from the cooling tower and it must be ensured that no noise & vibrations under any circumstances gets transmitted surroundings. Tower for airconditioning system shall be selected on the basis of water temperature 90-100° F, ambient wet bulb 80° F and nominal capacity shall be as follows.

-

-

-

... More
Cooling tower for 125 TR having flow rate of 300 USGPM each @ 90-100° F water temperature

2

-

-

... More
HOT WATER GENERATOR

-

-

-

... More
Supply, installation, testing and commissioning of Electric Hot Water Generator of following capacity conforming to BIS standards at the flow rates and hot water in let / out let temperature of 100 / 120 Deg.F complete as per specificaitons with following accessories.

-

-

-

... More
Matching electrical immersion heater banks.

-

-

-

... More
All automatic and safety controls such as manual reset, high temperature cut off, step controller and recycling relay, thermostats, pilot light, low water cut off and other controls.

-

-

-

... More
Electrical panel mounted on generator frame complete with internal wiring, contractors, switches, digital ammeter with C.T.s etc.

-

-

-

... More
Interconnecting cables between panel and heater.

-

-

-

... More
Thermometers and pressure gauges at inlet and outlet of electric hot water generator.

-

-

-

... More
CHILLED/HOT WATER EXPANSION TANK

-

-

-

... More
Supplying, installing, testing and commissioning of MS construction OPEN TYPE EXPANSION TANK (installed at the terrace of AHU room roof at OPD block) of 1mx1mx1m with valves along with necessary accessories.

1

-

-

... More
MAIN HVAC PANEL-PLANT ROOM

-

-

-

... More
Design, manufacturing, supply, installation, testing & commissioning of the following panels suitable for operation on 415V, 3 phase, 4 wire, 50 Hz. supply system. The panel shall be indoor, free standing, floor/wall mounted, sheet metal enclosed, cubicle type, dust & vermin proof, fully compartmentalized(Form-4B) made out of 14 SWG CRCA sheet steel complete with aluminium/copper bus bars, powder coating, necessary wiring, cable glands, GI Earth Bus through the panel, etc in IP-43 ingress rating in Seimens Grey Color RAL 7032. The scope of work also include necessary power & control cabling, complete interlocking between all equipments as per sequence of operation, earthing of equipments, cable trays, end terminations etc. The Panel shall be suitable for TOP and Bottom Entry both. Cabling & earthing on to the incomer Supply shall be provided by the electrical contractor. All motor feeder incomers shall be suitable for motor duty application. All starter feeders shall be equipped with minimum 2 pole auto/manual selector switch & 2 NO + 2 NC potential free aux. contacts for use by Building automation system & comprising of the following:

-

-

-

... More
INCOMER -1 & 2 For Section -1 & Section -2 (From different sections of Main LT Distribution Panel)

-

-

-

... More
630 amps (50kA) 4P microprocessor based MCCB (Icu= 100% Ics) with door loock interlock mechanism and pad locking system.

-

-

-

... More
Multifuction meter of accuracy class-I, with 3 Nos. 600/5 amps, CL-1, 10VA CTs to measure and display the following electrical quantities :

-

-

-

... More
Real Time

-

-

-

... More
Total active energy (KWH/MWH)

-

-

-

... More
Maximum demand (KVA/MVA) (KW/MW)

-

-

-

... More
Instantaneous power factor

-

-

-

... More
Current

-

-

-

... More
Voltage

-

-

-

... More
Frequency / Harmonics

-

-

-

... More
Breaker ON / OFF / TRIP indicating lights with control 2A SP MCB’s.

-

-

-

... More
BUS BAR (FOR SECTION - 1 & 2)

-

-

-

... More
800 amps TPN (50 KA), 91E grade Aluminium bus bars with insulated colour coded heat shrinkable insulating sleeves having current density of 0.80 Amps / 1.0 sq.mm. --- 2 Sets (Section -1 and Section -2)

-

-

-

... More
BUS COUPLER (BETWEEN SECTION - 1 & 2 OF BUS BAR)

-

-

-

... More
630 amps (50kA) 4P microprocessor based MCCB (Icu= 100% Ics) with door loock interlock mechanism and pad locking system having ON-OFF and phase indication lamps.

-

-

-

... More
OUTGOINGS

-

-

-

... More
SECTION - 1

-

-

-

... More
Two(2) Nos. 250 amps TPN, MCCB, 50KA, TO 80KW starter of 100TR chiller. Each of these compartment shall contain CT operated digital Multifunction (0-250A) of amps range, CT's(CL-1, 10VA) and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status. There shall be space to accommodate the VFD in compartment for future provision.(1W+1S).

-

-

-

... More
One(1) No. 250 amps TPN, MCCB,50KA, TO 100KW Hot Water Generator (HWG) Pump. Each of these compartment shall contain CT operated digital Multifunction (0-250A) of amps range, CT's(CL-1, 10VA) and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status. (1S).

-

-

-

... More
One(1) No. 25 amps, TPN MPCB's To 5.0 HP as an outgoing feeders to 1 No. Primary Chilled water pump (PCHWP) motors (3.7W) with DOL starter, contactor, relay, timer, single phase preventor, complete as required for each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motor. (1W).

-

-

-

... More
One(1) No. 32 amps, TPN MPCB's To 10 HP VFD complete as required as an outgoing feeders to 1 No. Secondary Chilled water pump (SCHWP) motors (7.5W) each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch, and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motors. VFD shall be in the scope of HVAC Vendor / Contractor. (1W For ZONE - A).

-

-

-

... More
One(1) No. 32 amps, TPN MPCB's To 7.5 HP VFD complete as required as an outgoing feeders to 1 No. Secondary Chilled water pump (SCHWP) motors (5.6W) each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch, and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motors. VFD shall be in the scope of HVAC Vendor / Contractor. (1W For ZONE - B).

-

-

-

... More
One(1) Nos. 32 amps TPN MPCB's , 10 HP, as an outgoing feeders to 1 No. Condensor water pump (CDWP) motors (7.5W) with Star-Delta starter, contactor, relay, timer, single phase preventor, complete as required for each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motor.(1W).

-

-

-

... More
One(1) No. 40 amps TPN MPCB's , 15 HP, as an outgoing feeders to 1 No. Cooling Tower (CT) motors (12.5W approximate) .There shall be space in the panel to accommodate the VFD in compartment for future provision. (1W).

-

-

-

... More
SPARES

-

-

-

... More
Spare Space for One(1) No. 250 amps TPN, MCCB, 50KA, There shall be space to accommodate the VFD in compartment.

-

-

-

... More
One(1) Nos. 63 amps TPN MPCB's for space to accommodate 15 HP Star Delta starters.

-

-

-

... More
Two(2) Nos. 32 amps TPN MPCB's for space to accommodate DOL starters.

-

-

-

... More
One(1) Nos. 25 amps TPN MPCB's for space to accommodate DOL starters.

-

-

-

... More
SECTION - 2

-

-

-

... More
One(1) No. 250 amps TPN, MCCB, 50KA, TO 80KW starter of 100TR chiller. Each of these compartment shall contain CT operated digital Multifunction (0-250A) of amps range, CT's(CL-1, 10VA) and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status. There shall be space to accommodate the VFD in compartment for future provision.(1W).

-

-

-

... More
One(1) No. 250 amps TPN, MCCB,50KA, TO 100KW Hot Water Generator (HWG) Pump. Each of these compartment shall contain CT operated digital Multifunction (0-250A) of amps range, CT's(CL-1, 10VA) and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status. (1W).

-

-

-

... More
Two(2) Nos. 25 amps, TPN MPCB's To 5.0 HP as an outgoing feeders to 1 No. Primary Chilled water pump (PCHWP) motors (3.7W) with DOL starter, contactor, relay, timer, single phase preventor, complete as required for each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motor. (1W+1S).

-

-

-

... More
One(1) No. 32 amps, TPN MPCB's To 10 HP VFD complete as required as an outgoing feeders to 1 No. Secondary Chilled water pump (SCHWP) motors (7.5W) each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch, and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motors. VFD shall be in the scope of HVAC Vendor / Contractor. (1S For ZONE - A).

-

-

-

... More
One(1) No. 32 amps, TPN MPCB's To 7.5 HP VFD complete as required as an outgoing feeders to 1 No. Secondary Chilled water pump (SCHWP) motors (5.6W) each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch, and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motors. VFD shall be in the scope of HVAC Vendor / Contractor. (1S For ZONE - B).

-

-

-

... More
Two(2) Nos. 32 amps TPN MPCB's , 10 HP, as an outgoing feeders to 1 No. Condensor water pump (CDWP) motors (7.5W) with Star-Delta starter, contactor, relay, timer, single phase preventor, complete as required for each. Each of these compartment shall contain direct operated digital multifuction meter of 0-32 amps range with selector switch and an indicating lamp with 2 amp MCB for ‘ON/OFF’ status of pump motor.(1W+1S).

-

-

-

... More
One(1) No. 40 amps TPN MPCB's , 15 HP, as an outgoing feeders to 1 No. Cooling Tower (CT) motors (12.5W approximate) .There shall be space in the panel to accommodate the VFD in compartment for future provision. (1W).

-

-

-

... More
SPARES

-

-

-

... More
One(1) Nos. 63 amps TPN MPCB's for space to accommodate 15 HP Star Delta starters.

-

-

-

... More
Two(2) Nos. 32 amps TPN MPCB's for space to accommodate DOL starters.

-

-

-

... More
One(1) Nos. 25 amps TPN MPCB's for space to accommodate DOL starters.

-

-

-

... More
Motor control centre as described above (Kindly Refer SLD before manufacturing the Panels)

1

-

-

... More
Notes:

-

-

-

... More
1) All incoming & outgoing shall be BMS Compatability.

-

-

-

... More
1) MCCB's shall be motor duty and suitable for 50 KA (ICS) fault current.

-

-

-

... More
2) Both incomers shall be electrically interlocked.

-

-

-

... More
3) Necessary cable alleys, space for spare switches, internal wiring, control wiring/cabling and copper earthing of all equipment shall also be included. All MCB's/MCCB's shall be motor duty rating.

-

-

-

... More
4) All MCCB's shall be with Neutral Link.

-

-

-

... More
5) The final selection of relay, contactor and timer shall be done as per Type-2 Coordination chart.

-

-

-

... More
6) There shall be sufficient space to accommodate the VFD in line with breaker wherever it is required within the panel.

-

-

-

... More
W --- Working

-

-

-

... More
W --- Stand By

-

-

-

... More
Total Carried to Summary

-

-

-

... More
PIPING - CHILLED WATER & CONDENSER WATER

-

-

-

... More
INSULATED CHILLED WATER PIPING (Nitrile rubber insulation)

-

-

-

... More
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.

-

-

-

... More
150 mm dia

85

-

-

... More
100 mm dia

235

-

-

... More
80 mm dia

90

-

-

... More
INSULATED VALVES

-

-

-

... More
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications.

-

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation as specified

-

-

-

... More
150 mm dia

3

-

-

... More
100 mm dia

6

-

-

... More
80 mm dia

6

-

-

... More
65 mm dia

8

-

-

... More
50 mm dia

18

-

-

... More
40 mm dia

4

-

-

... More
32 mm dia

8

-

-

... More
25 mm dia

28

-

-

... More
NON - RETURN VALVE/CHECK VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified.

-

-

-

... More
Pressure rating - PN-16

-

-

-

... More
125 mm dia

-

-

-

... More
100 mm dia

7

-

-

... More
Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified.

-

-

-

... More
125 mm dia

3

-

-

... More
100 mm dia

7

-

-

... More
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required

28

-

-

... More
Providing & fixing in position the mercury in glass industrial type thermometers.

12

-

-

... More
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified.

-

-

-

... More
125 mm dia

2

-

-

... More
100 mm dia

2

-

-

... More
80 mm dia

1

-

-

... More
50 mm dia

2

-

-

... More
CONDENSER WATER PIPE

-

-

-

... More
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.

-

-

-

... More
Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.

-

-

-

... More
150 mm dia

120

-

-

... More
125 mm dia

40

-

-

... More
40 mm dia

40

-

-

... More
VALVES WITHOUT INSULATION

-

-

-

... More
Supplying, fixing, testing and commissioning of following valves, gauges and strainers for condenser water circulation as per specifications.

-

-

-

... More
BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.

-

-

-

... More
150 mm dia

3

-

-

... More
40 mm dia

4

-

-

... More
25 mm dia

10

-

-

... More
NON - RETURN VALVE/CHECK VALVE with dual plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating as specified.

-

-

-

... More
125 mm dia

3

-

-

... More
Supplying, fixing, testing and commissioning of following sizes Motorized Butter fly Valve with CI Body, SS Disc,O - ring and minimum PN-16 pressure rating , conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20mA electric signal and providing similar transduced feedback output to control system as required.

-

-

-

... More
150 mm dia

2

-

-

... More
125 mm dia

16

-

-

... More
100 mm dia

20

-

-

... More
65 mm dia

4

-

-

... More
Providing and fixing in position the following automatic back wash type Pot strainers :

-

-

-

... More
150 mm dia pipes-chilled water

1

-

-

... More
150 mm dia pipes-condenser water

1

-

-

... More
Supply, installation, testing and commissioning of Flexible connections of suitable pressure rating to be installed at pumps, chillers, suction, discharge and at pipes crossing building expansion joints.

-

-

-

... More
125 mm dia pipes

12

-

-

... More
100 mm dia

20

-

-

... More
Supplying, installation, testing and commissioning of 19 mm Auto air vents

8

-

-

... More
Providing and fixing in position the Drain- Cock with ball valve 25 mm dia

10

-

-

... More
Total Carried to Summary

-

-

-

... More
THERMAL INSULATION

-

-

-

... More
Supply, installation and testing of insulation IN TRENCH/BURIED chilled water pipes and fittings etc. as per the approved shop drawings & specifications, the 'R' value should be minimum R-0.35:

-

-

-

... More
100 mm dia pipes

125

-

-

... More
80 mm dia pipes

100

-

-

... More
50 mm dia pipes

19.73

-

-

... More
Cooking Area

-

-

-

... More
3 BURNER RAGE WITH PIPE UNDER SELF GRID SIZE 350X350

1

-

-

... More
Gas Range (2 HP + 1 LP) with full length simmer plate (LP)

-

-

-

... More
Top and Front in SS, Sides & Rear MS painted Bottom four side Bracings in 25mm dia 16G tubes.

-

-

-

... More
1. 3 sides paneling in SS 20 SWG (300 mm)

-

-

-

... More
2. Back Splash 150 mm

-

-

-

... More
3. Bottom shelf in SS round & sq. tubes(16 swg)

-

-

-

... More
4. Bottom shelf in SS sheet (18 SWG) Size in mm. 1550 x700x850+150 -Gas

-

-

-

... More
WORK TABLE WITH 1 U/S

1

-

-

... More
TOP SS 304 16 G, MS FRAME INSIDE 32X32X5 with MIDLLE CHANNEL SUPORT

-

-

-

... More
LEG 40X40 MM square 18 g SS304 PIPE ,fitted with heavy duty nylon bullet feet .Size in mm. 600X700X850+150

-

-

-

... More
BULK COOKER CAPCITY - 100 Lt.

1

-

-

... More
Bulk Cooker, Gas fired, triple walled Insulated, with rear flue riser, LPG controls, tilting gear, SS frame

-

-

-

... More
Pan Size - 610 x 400 mm deep

-

-

-

... More
Heat Output - 70,000 BTU/ hr. Size in mm.O/S - 1100 x 710 x 1220 mm-Gas

-

-

-

... More
CHAPATI PLATE WITH PUFFER

1

-

-

... More
16mm thk. Steel top,machined with all-side four channel,drip tray,etc. Front in SS, Sides paneling MS painted, bottom cross bracings. Perforated Puffer Grates 225 x 225 mm. 4 Nos. Canteen Type LP burners for Puffer

-

-

-

... More
1. 3 sides paneling in SS 20 SWG (300 mm)

-

-

-

... More
2. Bottom shelf in SS tubeler pipe 20 mm ,16G

-

-

-

... More
Heat Output (40,000 x 4 + 21000 x 2) 2,02,000 BTU/ hr.Size in mm.450X900X900+100

-

-

-

... More
CHAPATI COLLECTION TROLLEY 2 UNDER SELF

1

-

-

... More
TOP & Middle self Made of 16 g 304 with 75 mm up ward band ,

-

-

-

... More
Bottom fench ms plate over the sheet mount ss pipe 40X40 mm ss pipe 16 g

-

-

-

... More
wheel 6" 360deg moveble .Size in mm.450X900X900+100

-

-

-

... More
SS WORK TABLE WITH 1 UNDER SELF

2

-

-

... More
TOP SS 304 16 G, MS FRAME INSIDE 32X32X5 with MIDLLE CHANNEL SUPORT

-

-

-

... More
LEG 40X40 MM square 18 g SS304 PIPE ,fitted with hevey duety nylon bullet feet .Size in mm.1200X900X900+100

-

-

-

... More
STOCK POT GAS RANGE

2

-

-

... More
with CI grates of size 400 x 400 mm Top and front in SS

-

-

-

... More
O/S - 600 x 600 x 600 mm

-

-

-

... More
Heat Output 70,000 BTU/ hr.Size in mm.600X000X000- Gas

-

-

-

... More
S.S. EHAUST HOOD WITH SS FILTER

1

-

-

... More
SS, wall type, 20 SWG with insulation and with P/C sheet

-

-

-

... More
TOP 16 G reinforced inside 40 mm , middle bottom self 18 g ss304

-

-

-

... More
framce work ms 32X32X5 mm with duly painted and sound deadend inside . Over head self made of 20g ss304 ,to self fitted with 1.5 kw heated with temp. Contoler pannel Size in mm.340X240X150+150- Elect

-

-

-

... More
4 Slot toaster

1

-

-

... More
Capacity 6 Slices, Instant toasting using Quartz heaters with timer

-

-

-

... More
Complete Stainless Steel, Even Heat

-

-

-

... More
O/S -455 x 255 x 260 mm high

-

-

-

... More
Chamber Size 320 x 235 x 208

-

-

-

... More
Electric Load - 3 KW, 220 V/ 50 HZ/ 1 Ph.

-

-

-

... More
Stainless Steel toast tray and heater protection shields Size in mm.Dia 400X550 Elect

-

-

-

... More
Water boiler Capacity 25 Liter

1

-

-

... More
Water Boiler, SS, Electric, Double Walled

-

-

-

... More
with SS Electric Heaters

-

-

-

... More
Capacity 25 Litres

-

-

-

... More
Electric Load - 3 KW, 1 Ph., 220 V

-

-

-

... More
O/S - 383 dia + 100 x 510 mm high

-

-

-

... More
Inner Pan - 300 Dia x 380 mm deep Size in mm.Dia 400X550

-

-

-

... More
MILK BOILER Capacity 25 Liter

1

-

-

... More
Milk Warmer, SS, Electric, Tripple Walled

-

-

-

... More
Capacity 25 Litres, 3 KW, 1 Ph.

-

-

-

... More
O/S - 410 mm dia + 100 x 580 mm

-

-

-

... More
Inner pan - 300 dia x 383 mm high Elect

-

-

-

... More
Juicer Mixer Grinder, Moter 900 Watts, Sujata dynamic

1

-

-

... More
Standred as per OEM Size in mm.375X410X4840+1300 Elect

-

-

-

... More
ATTA NEADING MACHINE capacity 30 kg

1

-

-

... More
Atta Kneader, Heavy Duty

-

-

-

... More
Capacity 50 Kg. Flour with 3 HP / 3 ph. Motor with SS Bowl and Arm

-

-

-

... More
WET GRINDER /MASLA GRINDER 10 Lt Capacity

1

-

-

... More
Stainless steel cover for motor and gear assembly, Drum cover in FRP,

-

-

-

... More
Capacity 5 litres, 1HP Crompton motor, 220 v, 50 cycles A/c

-

-

-

... More
O/S - 450 x 660 x 1100 mm

-

-

-

... More
POTATO PILLER MACHINE

1

-

-

... More
Potato Peeler, 10, SS, Electric

-

-

-

... More
Capacity 10 Kg./ charge, Belt Drive (1 HP, 1 Ph.) (100 Kg. / hr.), O/S - 400 mm dia + 180 x 945 mm high

-

-

-

... More
SS WASTE BIN TROLLY

2

-

-

... More
Made of 18 g ss 304 fited on 3"heavy duty castor

-

-

-

... More
Store Area

-

-

-

... More
4 DOOR VERTICAL CHILLER

1

-

-

... More
Temperature -2 to +8 deg C, Inner SS

-

-

-

... More
Doors and sides paneling in SS

-

-

-

... More
Two full Solid Doors

-

-

-

... More
Panel incorported Digital Temperature Controller, Electronic

-

-

-

... More
Auto Defrost, Forced Draft Cooling, 6 plastic coated shelves Size in mm.1350X700X2100 Elect

-

-

-

... More
PUF INJECTED Insulation - 60 mm

-

-

-

... More
Drip Tray, Power 440 Watts

-

-

-

... More
heavy duty 3" castor wheel

-

-

-

... More
4" rexnold fan ,4 nos ,with Techmsuh make comprssor /DANFOSS

-

-

-

... More
INGREDIENT/ PULSES / AATA /MAIDA SS BIN

4

-

-

... More
20 G SS sheet 304 Top lid in 2 pice mount over the " castor Wheel Size in mm.400X500X800

-

-

-

... More
THREE SINK UNITE (SINK SIZE 500X500X300)

1

-

-

... More
TOP AND SINK MADE OF 16 G SS 304 ,3 Side cross 25 mm dia tuble pipe . Fitted on square 40 mm ss304 leg frame work inside ss 32X32X3 mm , all sink corner with redius 75 mm , SS drain sokec welded 1-1/2 BSP Size in mm.1800X700X850+150

-

-

-

... More
CLEAN DISH LANDING TABLE -

1

-

-

... More
TOP 16 G SS 304 with ss frame work 32X32X3 , 3 side cross bracing with tubler pipe 25 mm , Leg sqare pipe 40 mm Size in mm.1050X750X850+150

-

-

-

... More
SERVICE HOT BAIN MARIE

1

-

-

... More
Top 16 g ss 304 all 3 side panneling 1 mm thick ss304 sheetwith fron tray slide 300 mm

-

-

-

... More
Tnak made of ss304 250 mm deep , with water outel 1/2 bsp and 1.5 kw 2 nos heater

-

-

-

... More
Bottom self made of 1 mm sheet side electrical pannel with tepreture controler ISI approve

-

-

-

... More
ARRANGMENT OF 5 nos. 1/1 gn pan 4 hot and 1 ambient

-

-

-

... More
water tank insulated with 2" meneral wool Size in mm.180X675X850+400 Elect

-

-

-

... More
_

-

-

-

... More
HOT Food Patient Trolley

2

-

-

... More
ALL SIDE BOSY CONSTRUC FULL 1 MM thick ss304 shhet Top made of 16 gwith MS frame work inside Inner body made of 20 g ss sheet fill with all side insulation front door with tray slide inside top arrangemnt of round 300 mm container flushed inside tank . heatr aaragemnt and tep. controler to maintained th tep.

-

-

-

... More
both side with hand rail to push and pull , 4 nos heagy duty ^' nylon wheel used .Size in mm.460X600X1550 Elect

-

-

-

... More
FLY KILLER MKT

4

-

-

... More
Air Curtain 1200mm Length

1

-

-

... More
MGPS

-

-

-

... More
Supply,Instllation testing and commissiong ofMedical Grade Copper Pipe as per technical specification BS: 13348 KITE MARK. Solid drawn, seamless, deoxidized, non arsenical, half hard, tempered and degreased materials conforming to BS: EN 13348 KITE MARK Medical Grade Pipe

-

-

-

... More
76mmODX1.2mm thick

100

-

-

... More
54mmODX1.2mm thick

40

-

-

... More
42mm ODX1.2mm thick

70

-

-

... More
28mmODX 1mm thick

300

-

-

... More
22mmODX 1mm thick

1600

-

-

... More
15mm ODX 1mm thick

1450

-

-

... More
12mm ODX 1mm thick

550

-

-

... More
Supply,Instllation testing and commissiong of Medical Gas Terminal Units (Gas Outlet Points) Oxygen, N2O, MA4 Air, SA7 Air, CO2, AGSS and Vacuum : It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

-

-

-

... More
for Oxygen

190

-

-

... More
for Nitrous Oxide

7

-

-

... More
for Compressed Air ( 4 Bar )

47

-

-

... More
For Compressed Air (7 Bar)

4

-

-

... More
For Vacuum

190

-

-

... More
Supply,Instllation testing and commissiong of Probe for Medical Gas Terminal Units (Gas Outlet Points) Oxygen, N2O, MA4 Air, SA7 Air, CO2, AGSS and Vacuum : It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

-

-

-

... More
for Oxygen

190

-

-

... More
for Nitrous Oxide

7

-

-

... More
for Compressed Air ( 4 Bar )_

47

-

-

... More
Fro Compressed Air (7 Bar)

4

-

-

... More
For Vacuum

190

-

-

... More
Supply, Installation, testing and commissioning of Touch type LCD alarm. It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

-

-

-

... More
Master Alarm Panel

1

-

-

... More
Areas Alarms Panel:

-

-

-

... More
2 Gas Service

14

-

-

... More
3 Gas Service

5

-

-

... More
4 Gas Service

4

-

-

... More
5 Gas Services

2

-

-

... More
Supply, Installation, testing and commissioning of Imported Single Service Area valve Unit with NIST connection. It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

-

-

-

... More
2 Gas Service

14

-

-

... More
3 Gas Service

5

-

-

... More
4 Gas Service

4

-

-

... More
5 Gas Services

2

-

-

... More
Supply, Installation testing and commissioning of Fully Automatic Oxygen Control System ( Improted for Oxygen) It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulator panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs . All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders.

1

-

-

... More
Supply, Installation testing and commissioning of Oxygen Main Manifold 10+10 size with header bars, tail pipes and non return valves. (Improted for Oxygen) It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

1

-

-

... More
Supply, Installation testing and commissioning of Oxygen Emergency Manifold 6+6 size with header bars, tail pipes and non return valves and Fully Automatic Oxygen Control Panel. (Improted for Oxygen) It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulator panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs . All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders.

1

-

-

... More
Supply installation, testing and commissioning of Oxygen Flow flow meter 0-15lpm and Poly sulphone humidifier bottle (Imported).It shall fully comply and meets with active medical device of class IIa and in compliance with the EN ISO 15002: 2008 standard. It should be duly CE marked and comply with 93/42/EEC Medical Devices: General. It shall be CE marked with the notified body number specified. It shall be provided with a copy of the certificate of origin.

20

-

-

... More
Supply installation, testing and commissioning of Low Flow Oxygen Flow flow meter 0-1.5lpm and Polysulphone humidifier bottle (Imported).It shall fully comply and meets with active medical device of class IIa and in compliance with the EN ISO 15002: 2008 standard. It should be duly CE marked and comply with 93/42/EEC Medical Devices: General. It shall be CE marked with the notified body number specified. It shall be provided with a copy of the certificate of origin.

161

-

-

... More
Supply, Installation testing and commissioning of Fully Automatic N2O Control Panel with heater (Improted) It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulator panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs . All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders.

1

-

-

... More
Supply, Installation testing and commissioning of N2O Main Manifold 10+10 size with header bars, tail pipes and non return valves. (Improted for N2O) It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

1

-

-

... More
supply, Installation testing and commissioning of N2O Emergency Manifold 4+4 size with header bars, tail pipes and non return valves and Fully Automatic N2O Control Panel with heater. It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulator panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs . All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders.

1

-

-

... More
Supply, Installation testing and commissioning of Fully Automatic CO2 Control Panel with heater (Improted) It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulator panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs . All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders.

1

-

-

... More
Supply, Installation testing and commissioning of CO2 Main Manifold 10+10 size with header bars, tail pipes and non return valves. (Improted for CO2). It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

1

-

-

... More
supply, Installation testing and commissioning of CO2 Emergency Manifold 4+4 size with header bars, tail pipes and non return valves and Fully Automatic CO2 Control Panel with heater. It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty. It should have Digital 3.5’ colorful display. It should have Integrated & protected test point. Central regulator panel with cylinder headers each side. It should have headers which shall be complete with gas specific cylinder tailpipes. Pre-wired for alarm connection to BMS outputs . All components degreased for oxygen use .Average gas consumption indication (for not liquefied gases). Remaining gas volume indication (for not liquefied gases). It should have general maintenance indicator. It should have Pressure transmitters monitor both banks of cylinders.

1

-

-

... More
supply, installation, testing and commissioning of Medical Air Plant 3 Phase 50 Hz (Package Unit) : Total 7000lpm as working and 7000lpm as stand by or reserve. It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. Company should provide free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality andf genuinuty. It shall be provided with a copy of the certificate of origin from chamber of commerce. Pentaplex medical air plant.) Medical Air Plant of 13bar for both 4bar MA4 Air supply and SA7 Air supply. 13 Bar from air compressor and 10bar from dryer. Each 7000lpm Pentaplex Medical Air Plant 3 Phase 50 Hz (Package Unit) consist of Pentaplex (5 x 22kw SCREW compressors), with duplex drier and filtration, 3 x 22kw screw compressors working as duty, 1 x 22Kw screw compressor as standby & 1 x 22Kw screw compressor as reserve as per HTM standards. It should be supplied with 2 x 3000 liters capacity vertical air receiver. It should have 72 dBA sound pressure level and 54mm OD pipe work. It should have updated software, It should complies with EN62304 class A, EFL, ARAVF. It should have 10m CAN cable. It should have main switch, amp meter, FTGOL switch, AC outlet temperature sensor & LAN/Local switch. Each base frame mounted screw compressor will provide 2400 lpm air flow. EMC certificate copy must be submitted. Compressors shall be directly driven by EFC IP55 energy saving CEMEP Class EFF1 high efficiency electric motor. It should have VSD drive comprises of two AC/DC converters connected back-to-back: Grid-side converter (rectifier) & Machine-side converter (inverter – PWM). A DC-bus acts as an energy buffer between both converters.

1

-

-

... More
Supply installation testing and commissining of Medical Vacuum Plant 3 Phase 50 Hz (Package Unit) :Total 7200lpm as working and 7200lpm as stand by or as reserve. It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. (*Quaduplex medical vacuum plant.) Two identical vacuum pumps should be duty as working and two identical as standby. Comprising of quaduplex oil ubricated rotary vane vacuum pumps (4 x 15kw 3600lpm each), 2 x 15Kw 3600lpm each working as duty and 2 x 15Kw 3600lpm each as stand by as per HTM standards. 3 x 3000 liters (9000ltrs total) capacity vertical vacuum receiver tanks. 77 dBA sound pressure level. 76mm OD pipe work and 42mm is exhaust pipe. The Medical Vacuum Plant shall be fully tested. A test certificate shall be provided showing the results of the tests, including the free-air flow rate obtained at an inlet vacuum of 450 mmHg. Type testing of plant flows or testing in component form is not acceptable.

1

-

-

... More
Imported AGSS Plant 3 Phase 50 Hz (Package Unit) : Total 5600 lpm as working and 5600 lpm as stand by.It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. Company should provide free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality andf genuinuty. It shall be provided with a copy of the certificate of origin from chamber of commerce. (*2 set of 2800lpm each duplex agss plant.). Duplex AGSS Plant consist of Twin stand alone AGSS pumps of 3 phase each 2800l/min capacity with built in flow indication and pressure regulation valve. Mounted on single frame with control panel and separate warning label. One pump will be standby with the other in operation. It should have 2 x 3KW Nominal Motar per blower, 1 x DOl starter, 54mm service connection and should have approx. weight 120Kg. Anaesthetic Gas Scavenging (AGS) Plants are intended to provide a continuous low level vacuum supply to pipeline systems in healthcare facilities for the removal of waste anaesthetic gases captured from patient breathing circuits.

1

-

-

... More
Suply installation testing and commissiong of Low Flow suction unit (Imported). It shall fully comply and meets with active medical device of class IIa and in compliance with the EN ISO 10079-3: 2009 standard. It should be duly CE marked and comply with 93/42/EEC Medical Devices: General. It shall be CE marked with the notified body number specified. Vacuum Regulator : It should be continuous vacuum regulator, compact, strong and ergonomic device. It should have manual adjustment of the vacuum gauge from -45degree to +45degree for a better visibility. Vacuum gauge should be protected by a plastic housing. It should have on/off switch-button providing a quick restoration of the  pre-adjusted vacuum level. It should have central regulation knob with a free rotation at the end of the course (impossible blocking). It should have quick adjustment :2.5turns are enough  to reach the maximum vacuum level. It should have vacuum levels : 0-250 mbar/hPa.  The vacuum regulator should be 3-in-1 system. It should have a device with a metal outlet tubing nipple integrated in the body of the regulator for a better safety, emergency suctions can even be processed. It should be supplied with a 100ml safety jar equipped with a mechanical anti-over flow safety valve and single use antibacterial plastic filter upfront. The safety jar should be made of polycarbonate, autoclavable up to 134degree C and unbreakable. The safety jar should be fixed by an easy-click rotation. The safety jar should be able to rotate to avoid any pinch of the tubing. It should have a unit serial number laser engraved on the body of each vacuum regulator ensuring its identifications and traceability. It should be light weight 490g and dimensions (height230mm X Width 70mm X Depth 90mm).Polysulphone collection jar of 1000ml with lid : it should be unbreakable and autoclavable upto 134º C must be fitted with an extremely simple anti overflow safety device, thereby ensuring easy maintenance. Should be totally transparent, they ensure perfect sucked liquid visibility.

20

-

-

... More
Suply installation testing and commissiong of Ward suction unit (Imported). It shall fully comply and meets with active medical device of class IIa and in compliance with the EN ISO 10079-3: 2009 standard. It should be duly CE marked and comply with 93/42/EEC Medical Devices: General. It shall be CE marked with the notified body number specified. Vacuum Regulator : It should be continuous vacuum regulator, compact, strong and ergonomic device. It should have manual adjustment of the vacuum gauge from -45degree to +45degree for a better visibility. Vacuum gauge should be protected by a plastic housing. It should have on/off switch-button providing a quick restoration of the  pre-adjusted vacuum level. It should have central regulation knob with a free rotation at the end of the course (impossible blocking). It should have quick adjustment :2.5turns are enough  to reach the maximum vacuum level. It should have vacuum levels : 0-250 mbar/hPa.  The vacuum regulator should be 3-in-1 system. It should have a device with a metal outlet tubing nipple integrated in the body of the regulator for a better safety, emergency suctions can even be processed. It should be supplied with a 100ml safety jar equipped with a mechanical anti-over flow safety valve and single use antibacterial plastic filter upfront. The safety jar should be made of polycarbonate, autoclavable up to 134degree C and unbreakable. The safety jar should be fixed by an easy-click rotation. The safety jar should be able to rotate to avoid any pinch of the tubing. It should have a unit serial number laser engraved on the body of each vacuum regulator ensuring its identifications and traceability. It should be light weight 490g and dimensions (height230mm X Width 70mm X Depth 90mm).Polysulphone collection jar of 1000ml with lid : it should be unbreakable and autoclavable upto 134º C must be fitted with an extremely simple anti overflow safety device, thereby ensuring easy maintenance. Should be totally transparent, they ensure perfect sucked liquid visibility.

161

-

-

... More
Suply installation testing and commissiong of High Flow Theater Suction Unit (Imported). It shall fully comply and meets with active medical device of class IIa and in compliance with the EN ISO 10079-3: 2009 standard. It should be duly CE marked and comply with 93/42/EEC Medical Devices: General. It shall be CE marked with the notified body number specified. Vacuum Regulator : It should be continuous vacuum regulator, compact, strong and ergonomic device. It should have manual adjustment of the vacuum gauge from -45degree to +45degree for a better visibility. Vacuum gauge should be protected by a plastic housing. It should have on/off switch-button providing a quick restoration of the  pre-adjusted vacuum level. It should have central regulation knob with a free rotation at the end of the course (impossible blocking). It should have quick adjustment :2.5turns are enough  to reach the maximum vacuum level. It should have vacuum levels : 0-250 mbar/hPa.  The vacuum regulator should be 3-in-1 system. It should have a device with a metal outlet tubing nipple integrated in the body of the regulator for a better safety, emergency suctions can even be processed. It should be supplied with a 100ml safety jar equipped with a mechanical anti-over flow safety valve and single use antibacterial plastic filter upfront. The safety jar should be made of polycarbonate, autoclavable up to 134degree C and unbreakable. The safety jar should be fixed by an easy-click rotation. The safety jar should be able to rotate to avoid any pinch of the tubing. It should have a unit serial number laser engraved on the body of each vacuum regulator ensuring its identifications and traceability. It should be light weight 490g and dimensions (height230mm X Width 70mm X Depth 90mm). Twin Polysulphone collection jar of 4000ml with lid : it should be unbreakable and autoclavable upto 134º C must be fitted with an extremely simple anti overflow safety device, thereby ensuring easy maintenance. Should be totally transparent, they ensure perfect sucked liquid visibility.

2

-

-

... More
Supply installation testing and commissioning of High pressure Hose antistatic duly colour coded for oxygen , Nitrous Oxide Compressed air and vacuum as per technical specification . (imported). Letter of authorization from original manufacturer with technical compliance must be submitted along with bid documents. HTM0201 standards complies certificate from original manufacturer must be submitted along with tender bid documents. European CE with 4 digit notified body number certificate must be submitted along with bid documents.Country of origin certificate from chamber of commerce must be submitted along with tender bid documents.

100

-

-

... More
Supply installation testing and commissioning of Imported Bed Head medical Supply Unit : It shall comply with all relevant Hospital Technical Memoranda (HTM), Hospital Building Notes (HBN) and British Standards (BS) as well as ISO11197:2009. It shall be CE marked with the notified body number specified. It shall be provided with a copy of the certificate of origin. Company should provide free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality andf genuinuty. The system shall be provided as factory assembled modules for single arm configurations. The ceiling column frame shall be constructed from extruded aluminum alloy 6063 T6. The end caps should replicate the profile of the vertical head. The aluminum extrusions used to contrast shall be of approximate wall thickness not less than 3.5 mm. The external surfaces should be antibacterial paint which ensures 100% shied against infectious agent. The lids shall be removable to allow access to the aluminum sections. Segregation shall be provided within the side sections to ensure that services are not accessible when removing the lids. The arm shall be supplied with ABS heads with LED backlighting signaling. It should have 180kgs weight bearing capacity of the arm. It should one vertical 1200mm single column to mount gas outlets and electrical. It can rotate from 0 to 330 degree. The control of brakes must be done using the holder release. It should be supplied as a fully wired and tested module. The devices are made in compliance with EC CERTIFICATE 1548/MDD Directive 93/42/EEC concerning medical devices Annex II with certification. The equipment should be considered class IIb. It should be IP 20 Classification according to the degree of protection against penetration of liquids and external agents. It should have protection provided on external power circuit which provides adequate protection with circuit breakers or fuses dimensioned accor¬ding to the power indicated on the label. This shall be supplied in compliance with the 93/42/CE regulation. Pendant shall fully meet the essential requirements for emissions and immunity as defined within BS EN 60601-1-1 and ISO standards. It should have 400-600mm up and down movement. It should have Electromagetic Brakes with LED barke lights. It should have vertical pole made of stainless steel with support of aluminum and IV stand with 4 Hooks. It should have one Shelf BIOCLEAN made of Solid Material for ceiling pendant with handle and 2xDIN rails (L530xW460mm) (capacity load 40Kg). It should have one drawer BIOCLEAN made of Solid Material for ceiling pendant with handle and 2xDIN rails (L530xW460mm) (capacity load 40Kg) It should be pre wired 10nos. electrical sockets of Indian origin multipin. It should be pre wired 10nos. ear5hing bonding sockets It should have 2nos. RJ 45 Data sockets of Indian origin multipin. Pre piped 6-8nos. HTM02-01 standards complies BS gas outlets points with NIST connection

28

-

-

... More
Supply installation testing and commissioning of medical line lokcable valve pre piped : It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class IIa or IIb Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. Line Isolation valves and should comprise full-bore ball valve complete with copper stub pipes for ease of installation. Valve - connected to the copper stub pipes by means of flat faced unions fitted with nitrile O-ring seals, allowing removal of the valve without the need to distort the pipe work. Stub pipes for valve up to 54 mm will be connected to the valve body using screwed connectors, while valve above this size will use flanged connectors. Valve - Brass body, end cap and stem, with a full – bore chrome plated brass ball. Valve - Operate from fully closed to fully open with a quarter turn of the handle. All line values - Supplied with a mechanism to enable the unit to be locked in the fully closed or fully open position. Supplied with copper stub pipes for ease of installation using inert gas jointing procedures. O-Ring Seals on the valve stub allow gas tight capping at a spur for further expression. Company should provide free sale certificate from medicine and healthcare products regulatory agency (on behalf of the scretray of state for health and social care) of the manufacturing product country for quality and of genuinuty.

-

-

-

... More
15mm OD

18

-

-

... More
22mm OD

12

-

-

... More
28mm OD

8

-

-

... More
42mmOD

4

-

-

... More
54mmOD

2

-

-

... More
PASSENGER 24 Persons (1632Kgs.) / 1.00 Mtr. Per Second, MICRO PROCESSOR BASED VVVF, 9 METER / PIT 1600mm / HEADROOM 4200 mm, 3 (GR+2 UPPER FLOORS),G,1,2, 3 (GR+2 UPPER FLOORS), 1 (ONE), IN FRONT ONLY, MACHINE ROOMLESS - GEARLESS, Lift Well Size 2650 X 2650 (MM Wide * MM Depth * MM Height * MM E-Value), Inside Size 1700 X 2100 X 2200 (MM Wide * MM Depth * MM Height * MM C-Value), Clear opening of Gates / Doors / Lintel 1000 X 2000 (MM Wide * MM Height) Lintel - 2200 mm, STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH , Car Ceiling-SLEEK SMALL CIRCULAR-JLFC 03 - SS HAIRLINE FINISH, Car Floor- -PVC,LED LIGHTS & CROSS FLOW - FAN,POWER OPERATED SIDE OPENING SLIDING DOOR - STAINLESS STEEL (1.5 mm) - Land Entrance Protection (G,1,2 )HAIRLINE FINISH, SIDE OPENING SLIDING DOOR - STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH,Landing Door Frame (G,1,2 )STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH,MICROPROCESSOR BASED DUPLEX SELECTIVE COLLECTIVE CONTROL WITH / WITHOUT ATTENDANT,AC 3 PHASE, 50 CYCLES, 415 VOLTS ±10%,ORANGE SQUARE DOT-MATRIX SCHROLLING DISPLAY-VERTICAL,ORANGE SQUARE DOT-MATRIX SCHROLLING DISPLAY-VERTICAL

1

-

-

... More
PASSENGER 13 Persons (884Kgs.) / 1.00 Mtr. Per Second Drive MICRO PROCESSOR BASED VVVF 9 METER / PIT 1600mm / HEADROOM 4200 mm,3 (GR+2 UPPER FLOORS)3, (GR+2 UPPER FLOORS),1 (ONE), IN FRONT ONLY,MACHINE ROOMLESS - GEARLESS,Size of Lift Well 2450 X 1850 (MM Wide * MM Depth * MM Height * MM E-Value), Lift Car Inside Size:-1500 X 1400 X 2200 (MM Wide * MM Depth * MM Height * MM C-Value)Clear opening of Gates / Doors / Lintel 1000 X 2000 (MM Wide * MM Height) Lintel - 2200 mm, STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH , Car Ceiling-SLEEK SMALL CIRCULAR-JLFC 03 - SS HAIRLINE FINISH, Car Floor- -PVC,LED LIGHTS & CROSS FLOW - FAN,POWER OPERATED SIDE OPENING SLIDING DOOR - STAINLESS STEEL (1.5 mm) - Land Entrance Protection (G,1,2 )HAIRLINE FINISH, SIDE OPENING SLIDING DOOR - STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH,Landing Door Frame (G,1,2 )STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH,MICROPROCESSOR BASED DUPLEX SELECTIVE COLLECTIVE CONTROL WITH / WITHOUT ATTENDANT,AC 3 PHASE, 50 CYCLES, 415 VOLTS ±10%,ORANGE SQUARE DOT-MATRIX SCHROLLING DISPLAY-VERTICAL,ORANGE SQUARE DOT-MATRIX SCHROLLING DISPLAY-VERTICAL

1

-

-

... More
PASSENGER, 16 Persons (1088Kgs.) / 1.00 Mtr. Per Second,MICRO PROCESSOR BASED VVVF,6 METER / PIT 1600mm / HEADROOM 4200 mm, 2 (GR+1 UPPER FLOOR, 2 (GR+1 UPPER FLOOR), 1 (ONE), IN FRONT ONLY, MACHINE ROOMLESS - GEARLESS,Size of Lift Well 2550 X 2100 (MM Wide * MM Depth * MM Height * MM E-Value), Lift Car Inside Size 1500 X 1650 X 2200 (MM Wide * MM Depth * MM Height * MM C-Value),Clear opening of Gates / Doors / Lintel / Ec:- 1000 X 2000 (MM Wide * MM Height) Lintel - 2200 mm,Type or Design of Lift Car STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH -Car Ceiling-SLEEK SMALL CIRCULAR-JLFC 03 - SS HAIRLINE FINISH, Car Floor- -PVC,LED LIGHTS & CROSS FLOW - FAN,POWER OPERATED SIDE OPENING SLIDING DOOR - STAINLESS STEEL (1.5 mm) - Land Entrance Protection (G,1,2 )HAIRLINE FINISH, SIDE OPENING SLIDING DOOR - STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH,Landing Door Frame (G,1,2 )STAINLESS STEEL (1.5 mm) - HAIRLINE FINISH,MICROPROCESSOR BASED DUPLEX SELECTIVE COLLECTIVE CONTROL WITH / WITHOUT ATTENDANT,AC 3 PHASE, 50 CYCLES, 415 VOLTS ±10%,ORANGE SQUARE DOT-MATRIX SCHROLLING DISPLAY-VERTICAL,ORANGE SQUARE DOT-MATRIX SCHROLLING DISPLAY-VERTICAL

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.