Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited Tender
View complete overview of Uttarakhand BRIDCUL Tender
Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited - BRIDCUL Tender
Eprocure
Opening Date7 Feb 2024
Closing Date26 Feb 2024
Tender Amount₹ 74,31,000
Costs
EMD
₹ 1,48,620Document Cost
₹ 5,900Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_BRID3_69155_1Bid Award Id
ViewTender No
199/BRIDCUL/873/24 Dated 03/02/2024Tender Authority
Bridge Ropeway Tunnel And Other Infrastructure Development Corporation Of Uttarakhand Limited ViewPurchaser Address
-Website
http://uktenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
VRF Indoor Unit
-
-
-
Providing & Fixing of Four Way Cassette Unit with Cordless/Corded remote (5 Star Rated)
-
-
-
1.03 TR Cassette Type
1
-
-
1.29 TR Cassette Type
2
-
-
1.56 TR Cassette Type
2
-
-
2.02 TR Cassette Type
10
-
-
2.56 TR Cassette Type
6
-
-
2.85 TR Cassette Type
4
-
-
3.2 TR Cassette Type
7
-
-
4.0 TR Cassette Type
10
-
-
Supply of approved make of ventilation fan sections of double SKIN CONSTRUCTION ,belt driven centrifugal fan ,mounted on floating foundation of spring mounted vibration isolators , and canvass connection , squirrel cage induction motor , mounted within the housing , and all other details as called for in the drawings , specifications. Fan section shall be suitable for floor / ceiling mounted application as detailed in the drawings ).The fan motor shall be suitable for operation on Single speed , 415+/-10% Volts, 50Hz,AC power supply. Sound level shall not be more than 60 DBA at 3.0 m from fan The quoted price should be inclusive of DOL starter panel with necessary cabling and earthling.
CFM Area to be feed
-
-
-
4000 G.F Examination Store
1
-
-
2500 FF Corridor
1
-
-
Supply, of double skin Air Fan section without filter section for exhaust complete with DIDW fan backward curved centrifugal fan with three phase motor. The quoted price should be inclusive of DOL starter panel with necessary cabling and earthling.
CFM Area to be feed
-
-
-
3500 G.F Examination Store
1
-
-
2000 FF Corridor
1
-
-
Copper Distribution Joint Kit
-
-
-
Copper joint kit for indoor
39
-
-
Copper joint kit for outdoor
3
-
-
Corded remote RO
42
-
-
Centralize Remote Controller
1
-
-
Installation of Variable Refrigerant Flow System
-
-
-
Installation of Modular type outdoor units equipped with highly efficient scroll compressors. Each outdoor unit should have minimum 1 no. variable compressor up to 18 HP, 2 nos. variable compressors upto 32 HP capacity, 3nos. variable compressors up to 54 HP capacity with special heat exchanger, 27 Steps speed control DC motor condenser fan , auto check function for connection error, auto address setting and in built Double Stage Oil Seperation to ensure minimum oil entrachment and proper lubrication.The condensing units should be capable for outside ambient 48 Deg. C.
-
-
-
Installation, testing and commissioning Outdoor Unit
-
-
-
HEAT PUMP
144
-
-
M S Stand for Outdoor Unit mounting
6
-
-
Commissioning of VRF systems including topping R410A gas per site requirements
144
-
-
Refrigerant Piping, Drain Piping & Cabling
Supply installation testing and commissioning of Interconnecting refrigerant pipe work with (19mm/13 mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per VOLTAS STD. & specifications, all piping inside the room shall be properly supported with MS hanger.
-
-
-
38.1 mm O.D. (with 19 mm insulation )
52
-
-
34.1 mm O.D. (with 19 mm insulation )
33
-
-
31.7 mm O.D.(with 19 mm insulation )
16
-
-
28.6 mm O.D.(with 19 mm insulation )
26
-
-
25.4 mm O.D..(with 19 mm insulation )
10
-
-
22.2 mm O.D..(with 19 mm insulation )
42
-
-
19.1 mm O.D. (with13mm insulation )
38
-
-
15.9 mm O.D.(with 13mm insulation )
19
-
-
12.7 mm O.D.(with 13mm insulation )
24
-
-
9.5 mm O.D.(with 13mm insulation )
35
-
-
6.4 mm O.D. (with 13mm insulation )
25
-
-
Cable Tray
Providing and fixing of GI cable tray with properly support complete with GI threaded .
-
-
-
Cable Tray for copper piping (300 mm ) without cover
200
-
-
Providing and fixing rigid PVC piping complete with fittings, supports as per VOLTAS STD.& specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation.
-
-
-
32 mm dia
170
-
-
supply & fixing of control cum transmission wiring of Copper conductor cable alongwith conduite for looping between indoor & outdoor VRF system & to main Control remote controller system
-
-
-
2 C X .75 Sq. mm
384
-
-
Ducting
Providing and fixing of Sheet metal ducting complete with supports dampers etc. as per specificat-ions & drawings.
G.I. Sheet Metal Ducting (Rectangular) site Fabricated
-
-
-
0.63 mm (24 Ga)
232
-
-
Grilles/Diffusers Supply, Installation and Testing of return air grilles/ diffusers as per specifications and drawings.
Aluminium return air diffusers without damper
9
-
-
Providing and fixing fire retardant nonporous double layer flexible connection between each unit and duct.
4
-
-
Installation ,Testing and commissioning of approved make of ventilation fan sections of double SKIN CONSTRUCTION ,belt driven centrifugal fan ,mounted on floating foundation of spring mounted vibration isolators , and canvass connection , squirrel cage induction motor , mounted within the housing , and all other details as called for in the drawings , specifications. Fan section shall be suitable for floor / ceiling mounted application as detailed in the drawings ).The fan motor shall be suitable for operation on Single speed , 415+/-10% Volts, 50Hz,AC power supply. Sound level shall not be more than 60 DBA at 3.0 m from fan The quoted price should be inclusive of DOL starter panel with necessary cabling and earthling.
CFM Area to be feed
-
-
-
4000 G.F Examination Store
1
-
-
2500 FF Corridor
1
-
-
Installation ,Testing and commissioning, of double skin Air Fan section without filter section for exhaust complete with DIDW fan backward curved centrifugal fan with three phase motor. The quoted price should be inclusive of DOL starter panel with necessary cabling and earthling.
CFM Area to be feed
-
-
-
3500 G.F Examination Store
1
-
-
2000 FF Corridor
1
-
-