Airports Authority Of India Tender
View complete overview of Uttarakhand AAI Tender
Airports Authority Of India - AAI Tender
Electrical and Electronics
Eprocure
Opening Date15 Mar 2022
Closing Date11 Apr 2022
Tender Amount₹ 8,08,100 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 16,521Document Cost
₹ 1,180Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_AAI_110061_1Bid Award Id
ViewTender No
AAI/PNT/ELECT/CARPARKINGTender Authority
Airports Authority Of India ViewPurchaser Address
-Website
http://https://www.aai.aero
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Installation of the following GI street light poles with 04 nos foundation bolts of M20X600mm long J type EN 8 grade with 1:2:4 Cement concrete(0.55x 0.55x 1.05) to the required depth as per special conditions(1:cement :2coarse sand:4graded stone aggregate 20mm nominal size)and necessary base concrete of 1:5:10 for 100mm thickness below the pole (1cement :5 fine sand : 10graded stone aggregate 40mm nominal size) suitable finishing on surface above the ground level etc complete as required.
a) 6 Mtr
16
-
-
Supplying and embedding following dia (ISI Marked) HDPE pipe in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required a)63 mm dia
50
-
-
Installation ,testing and commissioning of 45 W/54W LED fitting on existing street light pole with 2 x 1.5 sqmm FRLS PVC insulated copper conductor round cable from cable looping box to fitting Complete as required as per EIC.
A) ITC of 45 W LED fittings
32
-
-
SH : 2 Supply and LAYING of Cable and End TERMINATION
-
-
-
Supply of XLPE/PVC insulated, PVC sheathed aluminium conductor armoured power cable of 1.1KV grade confirming to IS 7098 (Part I) 1978 with upto date amendments etc as required for the following sizes.(Make : As per approved list.)
a) 4 x 6 sqmm
1000
-
-
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
a) 4 x 6 sqmm
33
-
-
Supplying and laying of following size HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground ( 75 cm below ground level including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
(a)63 mm dia
900
-
-
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/Metal/HDPE pipe as required.
(a)Upto 35 sq. mm.
950
-
-
SH : 3 EARTHING
-
-
-
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having licking arrangment and watering pipe etc. (with charcoal/coke and salt) as required.
4
-
-
Providing and laying earth conncection from earth electrode with 6 SWG dia G.I. wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
50
-
-
Providing and fixing 6 SWG dia G.I. Wire on surface or in recess for loop earthing as required
950
-
-
SH:4 Wiring of Toilet Block
-
-
-
Supply,Installation, testing and commissioning of pre-wired, fluorescent fitting/compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/war, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
12
-
-
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in existing surface / recessed PVC conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
(a)Group B
20
-
-
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in existing surface/ recessed PVC conduit as required
(a)2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
20
-
-
Wiring for light/ power plug with 2X2.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit alongwith 1 No 2.5 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
20
-
-
Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.
-
-
-
5/6 Amps Switch
2
-
-
15/16 Amps Switch
2
-
-
3 pin 5/6 Amps Socket outlet
2
-
-
3 pin 15/16 Amps Socket outlet
2
-
-
Supply & Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
6
-
-
Supplying and fixing 3 pin,5 amp celling rose on the existing junction box/wooden block including connection etc as required.
18
-
-
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
(a)8 way(2+6), Double Door
1
-
-
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10kA,"C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commisioning etc. as required.
-
-
-
Single Pole
6
-
-
Single Pole and neutral
1
-
-
Evaluation Notes How It Works ?