Uttar Pradesh Rajkiya Nirman Nigam Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Uttar Pradesh Rajkiya Nirman Nigam - UPRNN Tender
Electrical Works
Eprocure
Opening Date6 Nov 2024
Closing Date14 Nov 2024
Tender AmountRefer Documents
Costs
EMD
Refer DocumentsDocument Cost
₹ 2,360Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_UPRNN_971237_1Tender No
1995/EUD/Tender/GIMS/RNN/2024 Dated 06-11-2024Tender Authority
Uttar Pradesh Rajkiya Nirman Nigam ViewPurchaser Address
-Website
http://etender.up.nic.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Outgoing-
-
-
-
63 A,FP MCB - 4 No. outgoings,
-
-
-
250A MCCB 4P- 5 No. outgoings,
-
-
-
AMPMETER, VOLTMETER, 250A CT, 800A CT, EXTENDED ROM (ROTARY HANDLE), SPREADER TERMINALS, INDICATORS
1
-
-
Supply and laying of aluminium conductor PVC insulated rmoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. lamps etc. of suitable size or as directed by the Engineer- ncharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by lamps etc.
-
-
-
240 sqmm X 3.5 C
100
-
-
120 sqmm X 3.5 C
100
-
-
Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other jointing materials for following size of PVC insulated and PVC sheathed I XLPE aluminium conductor cable of 1.1 KV grade as required
-
-
-
120 sq. mm 3-1/2 core
6
-
-
240 sq. mm 3-1/2 core
10
-
-
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17 .5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
-
-
-
225 mm width X 50 mm depth X 1.6 mm thickness
120
-
-
Supplying and laying of following size DWC HDPE pipe ISi marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required.
-
-
-
160 mm dia (OD-160 mm & ID-135 mm nominal)
100
-
-
MAIN LT PANEL servicing
-
-
-
Servicing/Repairing of main LT panel by tightening of bus bar nut bolts, blowering entire panel for removing dust and changing of damaged handle, meter and indicators. (Note- If any ACB/MCCB/MCB found damaged/ defective it will be charges extra)
1
-
-
HT Breaker Servicing
-
-
-
33 Kv Breaker servicing general cleaning checking and testing of protection system such as meggering of CT, PT and BUS BAR, high Potential test of end joints, general cleaning, dusting out tightening of connections, cleaning of parts,tightening of AUX connection. Earthing joints, Operation check,Mechanism of breakers, Decarburization of contacts, Lubrication of moving parts
5
-
-
400Amp L&T Make Busduct repairing of approx 12 mtr
1
-
-
400 amp installation 0f 15 mtr appox (it may be exceed)
1
-
-
400 amp Dismantaling 0f 15 mtr appox (it may be exceed)
1
-
-