If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search &amp; bid for etender UP.

Uttar Pradesh Housing And Development Board - UPAVP Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date15 Jul 2024
Closing Date7 Aug 2024
Tender Amount₹ 11,00,00,000 
Notes
Download

Costs

Summary

Electrical Safety Related External Electrification Work At Lala Lajpat Rai And Affiliated

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
b. 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection.

-

-

-

... More
c .1 set 11KV Insulator complete with spindles & hardware complete as required.

-

-

-

... More
d .1 No. 11KV 400A TP Gang operated Air break switches complete with 25mm dia GI pipe operating machanism, handle & locking arrangement.

-

-

-

... More
e. 1 set of 3 nos.11KV single pole drop out fuse complete with barrel fuses, and mounting arrangement.

-

-

-

... More
f. 1 set (3 nos.) 11KV lightning arrestor and connecting to all phases.

-

-

-

... More
g. 1 No. 150 mm dia GI pipe class 'B' (for XLPE cable protection) as required.

-

-

-

... More
h. 2 Set 50mm dia 3m long GI pipe earting with 25 x 6 mm GI earth strip complete as required (for GO & DO & LA)

-

-

-

... More
i 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices.

1

-

156750

... More
11 KV DOUBLE POLE STRUCTURE

-

-

-

... More
a. 2 Nos. 11 mtr. long MS STEEL poles complete with, pole excavation, MS STEEL foundation, and back filling complete MS steel channel/angle iron etc.

-

-

-

... More
b. 1 Set of cross arms, branching, clamps and painting complete with GI nut, bolts & washers as required (for GO & DO), LA connection.

-

-

-

... More
c .3 set 11KV Insulator complete with spindles & hardware complete as required.

-

-

-

... More
e. 1 No. 150 mm dia GI pipe class 'B' (for XLPE cable protection) as required.

-

-

-

... More
f. 2 Set 50mm dia 3m long GI pipe earting with 25 x 3 mm GI earth strip complete as required

-

-

-

... More
g. 1 nos. 11KV HT danger boards and 2 set of anticlimbing devices.

10

-

99750

... More
Supply, installing, testing and commissioning of INDOOR TYPE 11KV, HT VCB Panel Board' having Vacuum Circuit Breakers with Motorized cum manual spring charging mechanism rated for 11KV, 800Amp, 18.4kA/3 Sec, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type design confirming to IS 13118, IEC 62271-100, Internal Arc tested as per IEC 62271 - 200, Mechanical Endurance of M2 class ensuring 10000 operating sequences and E2 class Electrical Endurance. The VCB Panel Board comprising Aluminum Bus-Bar of 8OOAmp, Earthing Truck of suitable making capacity along with safety interlocking for complete board 'and control voltage of 24V DC with SCADA compatibility .The VCB Panel board supplied with mandatory spares such as 4 Nos. Trip Coil, 4 Nos. Closing Coil, 3 Nos. Spring Charging Motors, 2 Nos. Space Heaters, 2 Nos. Rack-in & Rack-out handle. The Board shall consist following panels :

-

-

-

... More
11 KV INCOMER VCB PANEL :

-

-

-

... More
11 KV, 800Amp, 18.4KA/3 Se, Floor rolling type, Horizontal Isolation & Horizontal Draw-out type as per IS 13118, IEC 62271-100. Vacuum Circuit breaker should have 3 Nos. encapsulated Vacuum Bottels of same manufacturer as of Circuit Breaker. Motorized spring charging mechanism (230V AC) with integral spring charging handle for manual spring charging associated shunt type trip & close coils (24 V DC)

-

-

-

... More
Current Transformer

-

-

-

... More
1 set of 3 Nos. Single Phase, 11 KV, 800/400/1+1+PS Class, core 1 : Class 5P10, 15VA, Core 2 : Class 0.5, 15VA and Core 3: PS Class for Transformer Differential Protection (PS Class: VK 200V, Imag 30mA @ Vk/2)

-

-

-

... More
Potential Transformer

-

-

-

... More
1 set .of ,3 Nos. Draw-out Type Feeder Connected PTs having ratio 11KV/rt3/110V/rt3, Class 0.5/3P, 100VA along with associated HRC Fuses for Primary side protection.

-

-

-

... More
Accessories : TNC Switeh, Panel Space Heater, Push Button Trip Circuit Healthy- Check, Panel illumination lamp with switch, 3 Pin Plug with Socket of 15Amp., Local &. Remote Switch, Emergency Trip Button, AC &. DC control illumination lamp with switch 3 Pin plug with socket of 15 Amp., Local & remote Switch, Emergency Trip Button, AC & DC Control circuit through MCB, Auxiliary Contacts (6 NO + 6 NC), Anti Pumping Device.

-

-

-

... More
Indications: LED Type Indications for R - Y - B Phase, Breaker On/OFF, Spring Charged, Trip Circuit Healthy, Breaker Trip, Breaker Test / Service position, AC & DC Healthy.

-

-

-

... More
Metering Instruments : 1 No. Tri-vector Meter (Ace. CI. 0.5) of L&T/Secure make, 1 No. Digital Voltmeter (Acc. CI. 0.5) of Rishabh, AE &. Elmeasure make, 1 No. Digital Ammeter (Acc. CI. 0.5) of Rishabh, AE & Elmeasure make.

-

-

-

... More
Protection & Auxiliary Relay :

-

-

-

... More
1 No. Numerical 3 Over Current + 1 Earth Fault (50/51/50N/51N) Relay providing over Current (Low Set: 5% - 200% / High Set: 50% - 1600% in step of 1%), Earth Fault (Low Set: 5% - 200% / High Set: 50% - 1600% in steps of 1%). Relay wil/be communicable on IEC 603 Protocol.

-

-

-

... More
1 No. Numerical Under Voltage + Over Voltage (27/59) Relay providing Over Voltage Protection (105% - 170% in steps of 1%), Under Voltage Protection (15% :. 90% in steps of 1 %), No Voltage Protection (3% ~ 20% in steps of 1V). Relay will be communicable on IEC 603 Protocol.

-

-

-

... More
1 No. Trip Circuit Supervision Relay

-

-

-

... More
1 No. High Speed Master Trip Relay

-

-

-

... More
Additional Accessories and Features :

-

-

-

... More
Electrical Interlocking between Incomers & Bus-Coupler to prevent mixing of suppliers.

-

-

-

... More
Standard features should include provision for connecting atleast one run of outgoing cables, Test Terminal Block for protection circuit. Panel fabrication shall preferably be made from sheet steel, safety shutters, continuous rated close & Trip coils. Type tested for Internal Arc for 18.4KA Vacuum Bottels, VCB &. Panel should be of same make. Control Circuit shall operate on 24V, DC except Spring Charging Motor &. Space eater which. shall operate on 24V DC except Spring Charging Motor & Space Heater which shall operate on 230V AC.

2

-

698250

... More
11 KV OUT GOING VCB PANEL :

-

-

-

... More
Same description as INCOMER PANEL above except following changes

-

-

-

... More
Potential Transformer, Voltmeter, R - Y - 'B Phase Indication, Under Voltage + relay are not required in Outgoing Panels

-

-

-

... More
Current Transformer :

-

-

-

... More
1 Set 3 Nos. Single Phase, 11 KV, 200/100/1+1, Core 1 : Class 5P10 15 VA, Core-2 : Class 0.5., 15VA

5

-

684000

... More
11 KV BUS-COUPLER VCB PANEL :

-

-

-

... More
Same description as INCOMER PANEL above except following changes:

-

-

-

... More
Current Transformer, Potential Transformer, Tri-vector Meter, Ammeter, Voltmeter, R - Y - B Phase Indication, Protection & Auxiliary Relays 11KV 630 VCB Panel.

1

-

676400

... More
Supply of 11KV grade 3core Brand Stranded Compact Circular Aluminium Conductor, Conductor Screen With Extruded Semi Conducting Compound, XLPE Insulated, Insulation Screening with extruded Semi Conducting Compound in combination with Copper Tape, cores laid up, innersheath of PVC tape, galvanised flat steel strip armoured and overall PVC Sheathed Cable conforming to IS 7098 / (PART-II) 1985 with latest amendments.

-

-

-

... More
240sq.mm 3 core

660

-

2213

... More
300sq.mm 3 core

3790

-

2619

... More
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.

-

-

-

... More
Above 120 sq. mm and upto 400 sq. mm

905

-

441

... More
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.

-

-

-

... More
Above 120 sq. mm and upto 400 sq. mm

905

-

316

... More
Laying of one number XLPE power cable of 11/33 kV grade of following size direct in ground by mechanical mean alongwith laying of pipe as required.

-

-

-

... More
Above 120 sq. mm and upto 400 sq. mm

2640

-

637

... More
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required .

-

-

-

... More
240sq.mm 3 core

10

-

12401

... More
300sq.mm 3 core

48

-

12401

... More
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :

-

-

-

... More
240sq.mm 3 core/300sq.mm 3 core

8

-

17396

... More
300sq.mm 3 core

33

-

17396

... More
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :

-

-

-

... More
240sq.mm 3 core/300sq.mm 3 core

1

-

31971

... More
300sq.mm 3 core

2

-

31971

... More
Supply of Heavy density poly ethylene pipes ISI marked anti radiant grade OD-160mm dia PN-6 grade having minimum wall thickness 9.5mm as per IS Code 4984 with socket coupler with trenchless excavation system. Complete in all respects.

2640

-

618

... More
Unitised Sub Station (11KV / 415 V) 800 KVA With 1 I/C & 2 O/G (With Natural cooling)

-

-

-

... More
Supply & Installation Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Cu. Busbar and connections from transformer to LT ACB will be by busbar connections.

-

-

-

... More
Unitised Sub Station will have the following equipment

-

-

-

... More
H.T SWITCHGEAR

-

-

-

... More
Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection.

-

-

-

... More
RMU NON Extensible (2 isolators, 1 VCB with CU Busbar

-

-

-

... More
Function type- 3 position disconnector and earthing switch equipped with separate drive unit.

-

-

-

... More
1. Operation of LBS manual

-

-

-

... More
2. Cable switch rating 11KV,630A, 25KA for 1 sec

-

-

-

... More
3. Cable bushing rating 630A.

-

-

-

... More
4. Cable cover- As per our standard.

-

-

-

... More
5. Fixed type capacitive voltage indication provided.

-

-

-

... More
6. ON/OFF/Earth indication on the front mimic of the panel.

-

-

-

... More
7. Bottom cable termination-suitable upto 1 No. 3C X 300sq.mm

-

-

-

... More
8. Cable entry bottom, front.

-

-

-

... More
9. Fault passage indicator (FPI)-E/F

-

-

-

... More
FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. Breaker equipped with over current time release for transformer protection.

-

-

-

... More
1. VCB 11KV, 630A, 25kA/1sec.

-

-

-

... More
2. Operation of breaker-Manual

-

-

-

... More
3. Self powered electronic numerical protection relay providing over current and earth fault protection.

-

-

-

... More
4. Tape wound protection current transformer

-

-

-

... More
5. Capacitive voltage indication fixed type.

-

-

-

... More
6. ON, OFF, EARTH indication on the frount mimic of the panel

-

-

-

... More
7. Cable box for termination of cable.

-

-

-

... More
8. Cable cover stand.

-

-

-

... More
9. Emergency trip push button.

-

-

-

... More
10. Shunt trip coil.

-

-

-

... More
11. Operation counter.

-

-

-

... More
12. Ammeter.

-

-

-

... More
RMU accessories-

-

-

-

... More
Manual Operating handle-1nos.

-

-

-

... More
Standard manometer for SF6 GAS pressure indication.

-

-

-

... More
Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm

-

-

-

... More
Transformer (Manufactured as per IS 1180 Level-II)

-

-

-

... More
Type- ONAN, Hermatically sealed corrugated tack.

-

-

-

... More
1. Ratio- 11KV/433V

-

-

-

... More
2. Capacity 800KVA

-

-

-

... More
3. Vector group DYn11

-

-

-

... More
4. Off load tappings +5% to -10% in steps of 2.5%

-

-

-

... More
5. Winding- Double wound copper

-

-

-

... More
6. Class of insulation-A

-

-

-

... More
7. Ambient temp. 40 degree C

-

-

-

... More
8. Temp. rise in oil over ambient- 40 deg. C

-

-

-

... More
9. Temp. rise in winding over ambient- 45 deg. C

-

-

-

... More
Transformer Accessories

-

-

-

... More
Oil Temperature indicator

-

-

-

... More
LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar

-

-

-

... More
1. Voltage rating 433V

-

-

-

... More
2. Current rating- 1500 Amp.

-

-

-

... More
L.T Panel

-

-

-

... More
Incoming # 1

-

-

-

... More
1600Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-1600/5A, CL1.0, 10VA

-

-

-

... More
Incoming # 2 For Inbuilt 380KVAR APFC Panel

-

-

-

... More
800Amp. 50KA, TP ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-800/5A, CL1.0, 10VA

-

-

-

... More
ENCLOSURE for PSS

-

-

-

... More
Rated temperature enclosure class should be K10

-

-

-

... More
Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick

-

-

-

... More
Earthing- Internal earthing connection by using 50X6 Aluminium strips.

-

-

-

... More
Unitised Sub Station (11KV / 415 V) 800 KVA With 1 I/C & 3 O/G (With Natural cooling)

3

-

4864000

... More
Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbar and connections from transformer to LT ACB will be by busbar connections.

-

-

-

... More
Unitised Sub Station will have the following equipment

-

-

-

... More
H.T SWITCHGEAR

-

-

-

... More
Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of 3 nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection.

-

-

-

... More
RMU NON Extensible (3 isolators, 1 VCB with CU Busbar

-

-

-

... More
Function type- 3 position disconnector and earthing switch equipped with separate drive unit.

-

-

-

... More
1. Operation of LBS manual

-

-

-

... More
2. Cable switch rating 11KV,630A, 25KA for 1 sec

-

-

-

... More
3. Cable bushing rating 630A.

-

-

-

... More
4. Cable cover- As per our standard.

-

-

-

... More
5. Fixed type capacitive voltage indication provided.

-

-

-

... More
6. ON/OFF/Earth indication on the front mimic of the panel.

-

-

-

... More
7. Bottom cable termination-suitable upto 1 No. 3C X 300sq.mm

-

-

-

... More
8. Cable entry bottom, front.

-

-

-

... More
9. Fault passage indicator (FPI)-E/F

-

-

-

... More
FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. Breaker equipped with over current time release for transformer protection.

-

-

-

... More
1. VCB 11KV, 630A, 25kA/1sec.

-

-

-

... More
2. Operation of breaker-Manual

-

-

-

... More
3. Self powered electronic numerical protection relay providing over current and earth fault protection.

-

-

-

... More
4. Tape wound protection current transformer

-

-

-

... More
5. Capacitive voltage indication fixed type.

-

-

-

... More
6. ON, OFF, EARTH indication on the frount mimic of the panel

-

-

-

... More
7. Cable box for termination of cable.

-

-

-

... More
8. Cable cover stand.

-

-

-

... More
9. Emergency trip push button.

-

-

-

... More
10. Shunt trip coil.

-

-

-

... More
11. Operation counter.

-

-

-

... More
12. Ammeter.

-

-

-

... More
RMU accessories-

-

-

-

... More
Manual Operating handle-1nos.

-

-

-

... More
Standard manometer for SF6 GAS pressure indication.

-

-

-

... More
Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm

-

-

-

... More
Transformer (Manufactured as per IS 1180 Level-II)

-

-

-

... More
Type- ONAN, Hermatically sealed corrugated tack.

-

-

-

... More
1. Ratio- 11KV/433V

-

-

-

... More
2. Capacity 800KVA

-

-

-

... More
3. Vector group DYn11

-

-

-

... More
4. Off load tappings +5% to -10% in steps of 2.5%

-

-

-

... More
5. Winding- Double wound copper

-

-

-

... More
6. Class of insulation-A

-

-

-

... More
7. Ambient temp. 40 degree C

-

-

-

... More
8. Temp. rise in oil over ambient- 40 deg. C

-

-

-

... More
9. Temp. rise in winding over ambient- 45 deg. C

-

-

-

... More
Transformer Accessories

-

-

-

... More
Oil Temperature indicator

-

-

-

... More
LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar

-

-

-

... More
1. Voltage rating 433V

-

-

-

... More
2. Current rating- 1500 Amp.

-

-

-

... More
L.T Panel

-

-

-

... More
Incoming # 1

-

-

-

... More
1600Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexure

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-1600/5A, CL1.0, 10VA

-

-

-

... More
Incoming # 2 For Inbuilt 380KVAR APFC Panel

-

-

-

... More
800Amp. 50KA, TP ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-800/5A, CL1.0, 10VA

-

-

-

... More
ENCLOSURE for PSS

-

-

-

... More
Rated temperature enclosure class should be K10

-

-

-

... More
Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick

-

-

-

... More
Earthing- Internal earthing connection by using 50X6 Aluminium strips.

-

-

-

... More
Unitised Sub Station (11KV / 415 V) 400 KVA With 1 I/C & 2 O/G (With Natural cooling)

1

-

4864000

... More
Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbar and connections from transformer to LT ACB will be by busbar connections.

-

-

-

... More
Unitised Sub Station will have the following equipment

-

-

-

... More
H.T SWITCHGEAR

-

-

-

... More
Three way, 11KV 630Amp. 25KA for 1 sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection.

-

-

-

... More
RMU NON Extensible (2 isolators, 1 VCB with Cu. Busbar

-

-

-

... More
Function type- 3 position disconnector and earthing switch equipped with separate drive unit.

-

-

-

... More
1. Operation of LBS manual

-

-

-

... More
2. Cable switch rating 11KV,630A, 25kA/1sec.

-

-

-

... More
3. Cable bushing rating 630A.

-

-

-

... More
4. Cable cover- As per our standard.

-

-

-

... More
5. Fixed type capacitive voltage indication provided.

-

-

-

... More
6. ON/OFF/Earth indication on the front mimic of the panel.

-

-

-

... More
7. Bottom cable termination-suitable upto 1 no. 3C X 300sq.mm

-

-

-

... More
8. Cable entry bottom, front.

-

-

-

... More
9. Fault passage indicator (FPI)-E/F

-

-

-

... More
FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. T2 equipped with over current time release for transformer protection.

-

-

-

... More
1. VCB 11KV, 630A, 25kA/1sec.

-

-

-

... More
2. Operation of breaker-Manual

-

-

-

... More
3. Self powered electronic numerical protection relay providing over current and earth fault protection.

-

-

-

... More
4. Tape wound protection current transformer

-

-

-

... More
5. Capacitive voltage indication fixed type.

-

-

-

... More
6. ON, OFF, EARTH indication on the frount mimic of the panel

-

-

-

... More
7. Cable box for termination of cable.

-

-

-

... More
8. Cable cover stand.

-

-

-

... More
9. Emergency trip push button.

-

-

-

... More
10. Shunt trip coil.

-

-

-

... More
11. Operation counter.

-

-

-

... More
12. Ammeter.

-

-

-

... More
RMU accessories-

-

-

-

... More
Manual Operating handle-1nos.

-

-

-

... More
Standard manometer for SF6 GAS pressure indication.

-

-

-

... More
Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm

-

-

-

... More
Transformer (Manufactured as per IS 1180 Level-II)

-

-

-

... More
Type- ONAN, Hermatically sealed corrugated tack.

-

-

-

... More
1. Ratio- 11KV/433V

-

-

-

... More
2. Capacity 400KVA

-

-

-

... More
3. Vector group DYn11

-

-

-

... More
4. off load tappings +5% to -10% in steps of 2.5%

-

-

-

... More
5. Winding- Double wound copper

-

-

-

... More
6. Class of insulation-A

-

-

-

... More
7. Ambient temp. 40 degree C

-

-

-

... More
8. Temp. rise in oil over ambient- 40 deg. C

-

-

-

... More
9. Temp. rise in winding over ambient- 45 deg. C

-

-

-

... More
Transformer Accessories

-

-

-

... More
Oil Temperature indicator

-

-

-

... More
LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar

-

-

-

... More
1. Voltage rating 433V

-

-

-

... More
2. Current rating- 1000 Amp.

-

-

-

... More
L.T Panel

-

-

-

... More
Incoming

-

-

-

... More
800Amp. 50KA, 4P EDO ACB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-1000/5A, CL1.0, 10VA

-

-

-

... More
Incoming # 2 For Inbuilt 200KVAR APFC Panel

-

-

-

... More
400Amp. 50KA, TP MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-400/5A, CL1.0, 10VA

-

-

-

... More
Earthing- Internal earthing connection by using 50X6 Aluminium strips.

-

-

-

... More
Unitised Sub Station (11KV / 415 V) 250 KVA With 1 I/C & 3 O/G (With Natural cooling)

3

-

4085000

... More
Outdoor type package substation with facility for internal lighting, earthing, padlocks etc. Connection between RMU & transformer will be by 1 no. 3Cx95 sq.mm. XLPE cable/Busbar and connections from transformer to LT ACB will be by busbar connections.

-

-

-

... More
Unitised Sub Station will have the following equipment

-

-

-

... More
H.T SWITCHGEAR

-

-

-

... More
Three way, 11KV 630Amp. 25KA for 1sec. SF6 insulated Non-Extensible compact switchgear consisting of two nos. of fixed load break switch and one no. fixed vacuum circuit breaker in SF6 insulated stainless steel enclosure with self powered series trip microprocessor base numerical over current & earth fault relay (IDMTL+inst.) for protection.

-

-

-

... More
RMU NON Extensible (3 isolators, 1 VCB with AL Busbar

-

-

-

... More
Function type- 3 position disconnector and earthing switch equipped with separate drive unit.

-

-

-

... More
1. Operation of LBS manual

-

-

-

... More
2. Cable switch rating 11KV,630A, 25kA/1sec.

-

-

-

... More
3. Cable bushing rating 630A.

-

-

-

... More
4. Cable cover- As per our standard.

-

-

-

... More
5. Fixed type capacitive voltage indication provided.

-

-

-

... More
6. ON/OFF/Earth indication on the front mimic of the panel.

-

-

-

... More
7. Bottom cable termination-suitable upto 1 no. 3C X 300sq.mm

-

-

-

... More
8. Cable entry bottom, front.

-

-

-

... More
9. Fault passage indicator (FPI)-E/F

-

-

-

... More
FUNCTION Type- 3 position disconnector and earth switch equipped with seperate drive unit. T2 equipped with over current time release for transformer protection.

-

-

-

... More
1. VCB 11KV, 630A, 25kA/1sec.

-

-

-

... More
2. Operation of breaker-Manual

-

-

-

... More
3. Self powered electronic numerical protection relay providing over current and earth fault protection.

-

-

-

... More
4. Tape wound protection current transformer

-

-

-

... More
5. Capacitive voltage indication fixed type.

-

-

-

... More
6. ON, OFF, EARTH indication on the frount mimic of the panel

-

-

-

... More
7. Cable box for termination of cable.

-

-

-

... More
8. Cable cover stand.

-

-

-

... More
9. Emergency trip push button.

-

-

-

... More
10. Shunt trip coil.

-

-

-

... More
11. Operation counter.

-

-

-

... More
12. Ammeter.

-

-

-

... More
RMU accessories-

-

-

-

... More
Manual Operating handle-1nos.

-

-

-

... More
Standard manometer for SF6 GAS pressure indication.

-

-

-

... More
Right angled cable boots suitable for 1 RMU X 3C X 300sq.mm

-

-

-

... More
Transformer (Manufactured as per IS 1180 Level-II)

-

-

-

... More
Type- ONAN, Hermatically sealed corrugated tack.

-

-

-

... More
1. Ratio- 11KV/433V

-

-

-

... More
2. Capacity 250KVA

-

-

-

... More
3. Vector group DYn11

-

-

-

... More
4. off load tappings +5% to -10% in steps of 2.5%

-

-

-

... More
5. Winding- Double wound copper

-

-

-

... More
6. Class of insulation-A

-

-

-

... More
7. Ambient temp. 40 degree C

-

-

-

... More
8. Temp. rise in oil over ambient- 40 deg. C

-

-

-

... More
9. Temp. rise in winding over ambient- 45 deg. C

-

-

-

... More
Transformer Accessories

-

-

-

... More
Oil Temperature indicator

-

-

-

... More
LT Busbar- Main bus bar are aluminium however copper flexible arer provided between Transformer and LT incommer connection alongwith main busbar

-

-

-

... More
1. Voltage rating 433V

-

-

-

... More
2. Current rating- 500 Amp.

-

-

-

... More
L.T Panel

-

-

-

... More
Incoming

-

-

-

... More
500Amp. 50KA, 4P MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-630/5A, CL1.0, 10VA

-

-

-

... More
Incoming # 2 For Inbuilt 125KVAR APFC Panel

-

-

-

... More
250Amp. 50KA, TP MCCB O/L, S/C, E/F protection LSIG, LCD Display having specs as per attached annexture for inbuilt 380KVAR APFC Panel

-

-

-

... More
ON, OFF TRIP lamp.

-

-

-

... More
R/Y/B indicating lamp.

-

-

-

... More
Multifunction meter

-

-

-

... More
CT-250/5A, CL1.0, 10VA

-

-

-

... More
ENCLOSURE for PSS

-

-

-

... More
Rated temperature enclosure class should be K10

-

-

-

... More
Outdoor type 2mm thick galvenised enclosure shall have IP54 degree of protection for HT & LT switchgear compartment & IP34 degree of protection for transformer compartment. The enclosure exterior shall be powder coated with PP based paint. HT & LT compartment will be provided with the door and pad locking arrengement. Transformer compartment will be provided with cover. The compartment illumination lamp with door operated switch shall be provided for lifting arrengement shall be provided with PSS. Base frame of PSS shall be 4mm thick.

-

-

-

... More
Earthing- Internal earthing connection by using 50X6 Aluminium strips.

1

-

3733500

... More
Construction of fencing & shed work

-

-

-

... More
Supply & Construction of fencing & shed work arround the CSS & Panel including excavation refilling, painting etc. as required as per details given below:-

-

-

-

... More
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge.

-

-

-

... More
Ordinary rock

-

-

-

... More
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :

-

-

-

... More
1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)

-

-

-

... More
Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in:

-

-

-

... More
Cement mortar 1:6 (1 cement : 6 coarse sand)

-

-

-

... More
Structural steel work in single section, fixed with or without connecting plate,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.

-

-

-

... More
CEMENT PLASTER (IN FINE SAND)

-

-

-

... More
12 mm cement plaster of mix :

-

-

-

... More
1:6 (1 cement: 6 fine sand)

-

-

-

... More
R.C.C. Standards post/ struts/rails/ pales of mix 1:1.5:3 (1 cement : 1.5 coarsesand : 3 graded stone aggregate 12.5 mm nominal size) with wooden plugs or 6mm bar nibs wherever required as per direction of Engineer-incharge (cost of earth works in excavation, concrete works in foundation to be paid separately).

-

-

-

... More
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge.

-

-

-

... More
Made of G.I. wire of dia 4 mm

-

-

-

... More
Providing corrugated G.S. sheet roofing including vertical / curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of approved paint on overlapping of sheets complete (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.

-

-

-

... More
1.00 mm thick with zinc coating not less than 275 gm/m²

7

-

282475

... More
SUB STATION SAFETY EQUIPMENT :

-

-

-

... More
Supplying and fixing 1800 mm x 900 mm wide checkered rubber matting conforming to IS 5424-1969 complete as required.

-

-

-

... More
Suitable for 11KV

10

-

2423

... More
Supplying & fixing standard shock treatment charts in English & Hindi duly framed and covered with glass.

8

-

290

... More
Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.

19

-

232

... More
Supply and erection of ISI marked portable fire extinguishers, wall mounted type, wall brackets complete in all respects, including fixing on walls as per the direction of engineer-in-charge. (CO2 gas type 6.5 kg. Capacity)

16

-

18905

... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

20

-

5703

... More
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

14

-

10561

... More
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)

520

-

110

... More
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)

420

-

742

... More
HOSPITAL BUILDING MAIN L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall have AMF facility to achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec)

-

-

-

... More
Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec). MCCB, with microprocessor release with protection function LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics)

-

-

-

... More
INCOMING

-

-

-

... More
4 Nos. 800 Amp FP EDO ACB 50KA ,

-

-

-

... More
BUSCOUPLER

-

-

-

... More
1 Nos. 800Amp ACB 50KA ,

-

-

-

... More
AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

-

-

-

... More
Load Management through PLC

-

-

-

... More
Contactor for Load Management System

-

-

-

... More
Auto changeover.

-

-

-

... More
Buscoupler switching.

-

-

-

... More
Electrial & Mechnical Interlocking.

-

-

-

... More
BUSBARS

-

-

-

... More
2 Nos. 1000 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
6Nos. 200 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
3Nos. 500 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1Nos. 400 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2Nos. 315 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2 Nos. 250 Amp FP MCCB 50 kA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2 Nos. 160 Amp FP MCCB 50 kA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1 Nos. 125 Amp FP MCCB 50 kA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
4 Nos. 100 Amp FP MCCB 50 kA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
4 sets of multifunction meter with parameter current, voltage, KWH, KVAH, Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port.

-

-

-

... More
4 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
4 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
4 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 50KA.

-

-

-

... More
RELAYS

1

-

3269577

... More
MEDICINE WARD & BURN WARD SIDE L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall have AMF facility to achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec)

-

-

-

... More
Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec). MCCB, with microprocessor release with protection function LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics)

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 315 Amp FP MCCB 25 kA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 400 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
1 Nos. 160 Amp FP MCCB 25 kA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
5 Nos. 125 Amp FP MCCB 25 kA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. With RS 485

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 25KA.

-

-

-

... More
RELAYS

2

-

324900

... More
ICU & EMERGENCY BLOCK MAIN L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall have AMF facility to achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec)

-

-

-

... More
Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec). MCCB, with microprocessor release with protection function LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics)

-

-

-

... More
INCOMING

-

-

-

... More
4 Nos. 800 Amp FP EDO ACB 50KA ,

-

-

-

... More
BUSCOUPLER

-

-

-

... More
1 Nos. 800Amp ACB 50KA ,

-

-

-

... More
AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

-

-

-

... More
Load Management through PLC

-

-

-

... More
Contactor for Load Management System

-

-

-

... More
Auto changeover.

-

-

-

... More
Buscoupler switching.

-

-

-

... More
Electrial & Mechnical Interlocking.

-

-

-

... More
BUSBARS

-

-

-

... More
2 Nos. 1000 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
2Nos. 800 Amp FP EDO ACB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2Nos. 500 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2Nos. 400 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2Nos. 250 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2Nos. 200 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2Nos. 63 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
4 sets of multifunction meter with parameter current, voltage, KWH, KVAH, Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port.

-

-

-

... More
4 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
4 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
4 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 50KA.

-

-

-

... More
RELAYS

1

-

2895942

... More
OPD BLOCK MAIN L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
The Main LT Panel shall use all draw out type breakers suitable for 415 V AC, 3 phase, 50 Hz, 3 phase 4 wire supply system. The panel shall have AMF facility to achieve electrical interlocking, synchronizing, buscoupler switching, auto operation of incommer and bus coupler, auto start of D.G. Sets, auto D.G. running by pre set timing, auto changeover etc and having following incomming and outgoing Air Circuit Breakers,microprocessor release for overload, short circuit, instantaneous & earthfault protection with Current & Voltage metering & LCD display & should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec)

-

-

-

... More
Air Circuit Breaker with microprocessor release ge metering & LCD display , with ready to clsoe indicator, should have capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet and as per the detail specification of ACB (Icu=Ics=Icw=50 kA (1 sec). MCCB, with microprocessor release with protection function LCD display for fault trip history, haivng current limiting feature, double break mechanism & capability to communicate ON /OFF/ Trip Status on Modbus/Ethernet. (50 kA Ics)

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 1600 Amp FP EDO ACB 50KA ,

-

-

-

... More
2 Nos. 800 Amp FP EDO ACB 50KA ,

-

-

-

... More
AUTO OPERATION OF INCOMER / BUSCOUPLER ACB's.

-

-

-

... More
Load Management through PLC

-

-

-

... More
Contactor for Load Management System

-

-

-

... More
Auto changeover.

-

-

-

... More
Buscoupler switching.

-

-

-

... More
Electrial & Mechnical Interlocking.

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 2000 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
1Nos. 1000 Amp FP EDO ACB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1Nos. 800 Amp FP EDO ACB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
4Nos. 500 Amp FP MCCB 50 kA, , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
3 sets of multifunction meter with parameter current, voltage, KWH, KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port.

-

-

-

... More
3 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
3 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
3 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 50KA.

-

-

-

... More
RELAYS

1

-

2050480

... More
NURSES HOSTEL & RESIDENCES OUTDOOR TYPE PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 500 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 630 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
1 Nos. 200 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1 Nos. 125 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
3 Nos. 100 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2 Nos. 63 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of multifunction meter with parameter current, voltage, KWH, KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 25KA.

-

-

-

... More
RELAYS

1

-

460726

... More
NURSES HOSTEL MAIN L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 200 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 250 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
5 Nos. 100 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1 Nos. 63 Amp TP MCCB 50 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-200Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 25KA.

-

-

-

... More
RELAYS

1

-

266238

... More
12 FLAT NURSES BLOCK METER PANEL 1/2

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 100 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 125 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
14 Nos. 40 Amp DP MCB

-

-

-

... More
12Nos. 40Amp. KWh 1 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-100Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

2

-

152523

... More
13 FLAT NURSES BLOCK METER PANEL 3/4

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 100 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 125 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
15 Nos. 40 Amp DP MCB

-

-

-

... More
13Nos. 40Amp. KWh 1 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-100Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

2

-

164255

... More
MARRIED DOCTOR NRH HOSTEL & WARD BLOCK

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 1250 Amp FP EDO ACB 50 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 1600 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
3 Nos. 400 Amp FP MCCB 50 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2 Nos. 250 Amp FP MCCB 50 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1 Nos. 200 Amp FP MCCB 50 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
2 Nos. 125 Amp TP MCCB 50 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 50KA.

-

-

-

... More
RELAYS

1

-

564063

... More
MARRIED DOCTOR HOSTEL L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 400 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 500 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
5 Nos. 125 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1 Nos. 63 Amp TP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-400Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 25KA.

-

-

-

... More
RELAYS

1

-

311904

... More
12 FLAT DOCTORS BLOCK METER PANEL 1/2/3/4

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 125 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 150 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
14 Nos. 40 Amp FP MCB

-

-

-

... More
12Nos. 40Amp. KWh 3 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-150Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 3 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

4

-

152523

... More
NRH HOSTEL L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 400 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 500 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
3 Nos. 160 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1 Nos. 125 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
1 Nos. 63 Amp TP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-400Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 25KA.

-

-

-

... More
RELAYS

1

-

268765

... More
PRIVATE WARD MAIN L.T PANEL

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be Indoor, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 250 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 320 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
6 Nos. 125 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-250Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 25KA.

-

-

-

... More
RELAYS

1

-

293854

... More
4TH CLASS EMPLOYEE TYPE-1 RESIDENTIAL AREA MAIN L.T PANEL (OUTDOOR TYPE)

-

-

-

... More
SITC of LT switchgear panels suitable for 433 V, 3 phase, 4 wire, 50 Hz power distribution system. The panel shall be OUTDOOR, free standing, floor mounting, sheet metal clad, cubicle, dead front, dust and vermin proof type compartmentalised design fabricated out of 14 SWG CRCA sheet steel, complete with colour coded, heat shrinkable PVC insulated, aluminium bus bars and separate earth bus bar of adequate cross section through out the length of the panel. The incoming and outgoing feeders shall be accommodated in a fully segregated, modular multitier arrangement with adequate size and distinct cable alley, bus bar alley/chamber. The panel shall be complete with name plate, earthing, numbering, danger plate etc. as per specifications and drawings as required. The panel shall withstand the fault level of 35kA as per Single Line Diagram. The Panel shall also be capable to communicate status like ON/OFF/ Trip through Modbus/Ethernet for major component like ACB, MCCB, MCB & Multifunation meters.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 800 Amp FP EDO ACB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 1000 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
3 Nos. 125 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
8 Nos. 100 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
3 Nos. 63 Amp FP MCCB 25 KA , with On, Off Indication lamp and A/V/KW meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of multifunction meter with parameter current,voltage,KWH,KVAH,Power factor on incoming from transformers. Class Accuracy 0.5 with RS485 Port.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Short Circuit Breaking capacity should not less than 25KA.

-

-

-

... More
RELAYS

1

-

523992

... More
Type-II Block Main L.T Panel

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 125 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 150 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
2 Nos. 100 Amp DP MCB

-

-

-

... More
2 Nos. 63 Amp DP MCB

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-150Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

2

-

67688

... More
12 TYPE-II RESIDENCE OUTDOOR TYPE METER PANEL 1/2/3/4

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 100 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 150 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
15 Nos. 40 Amp DP MCB

-

-

-

... More
12Nos. 40Amp. KWh 1 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-150Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

4

-

146205

... More
17/15 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 100 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 150 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
18 Nos. 40 Amp DP MCB

-

-

-

... More
17Nos. 40Amp. KWh 1 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-150Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

3

-

153425

... More
13 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 100 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 125 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
14 Nos. 40 Amp DP MCB

-

-

-

... More
13Nos. 40Amp. KWh 1 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-100Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

2

-

137180

... More
RELAYS

-

-

-

... More
11 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 100 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 125 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
12 Nos. 40 Amp DP MCB

-

-

-

... More
11Nos. 40Amp. KWh 1 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-100Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

2

-

152523

... More
8 TYPE-1 RESIDENCE OUTDOOR TYPE METER PANEL 1/2

-

-

-

... More
Design, Manufacturing, Supply, Commissioning & Testing of Meter Panel. The panel will be totally enclosed type with, free standing, floor mounted, outdoor duty, dust & vermin proof, , front/back operated, electrical panel fabricated from 2 mm thick M.S. Sheet as per specifications & drawing laid in this document and will be complete with the main and auxiliary bus bars, multimeter, indication lamps, CT's, protection MCB, interconnection wiring, earth bus and will be powder coated finish with 50 micron thickness including providing of suitable size of compartment to mount 3 Phase or 1 Phase energy meter with hinge door provided with cutout to get meter reading.

-

-

-

... More
INCOMING

-

-

-

... More
1 Nos. 100 Amp FP MCCB 25 KA ,

-

-

-

... More
BUSBARS

-

-

-

... More
1 Nos. 125 Amp TPN busbars of aluminium alloy .

-

-

-

... More
OUTGOING

-

-

-

... More
9 Nos. 40 Amp DP MCB

-

-

-

... More
8Nos. 40Amp. KWh 1 Phase Energy meter

-

-

-

... More
INSTRUMENTS

-

-

-

... More
1 sets of 0-500V digital type Voltmeter with voltmeter selector switch.

-

-

-

... More
1 sets of 0-100Amp. digital type ammeter with ammeter selector switch.

-

-

-

... More
1 Sets of phase indicating lights (RYB) with protection fuses (one set for each incoming breaker).

-

-

-

... More
1 Sets breaker 'ON' & 'OFF' indicating lamp (one set for each incoming breaker).

-

-

-

... More
1 Sets auto trip indicating lamp .

-

-

-

... More
Note: All outgoings should have ammeter and RYB indications with backup MCB as indicated in single line diagrams.

-

-

-

... More
Cost of 1 Phase Energy meter is inclusive in above rates.

-

-

-

... More
RELAYS

2

-

137180

... More
Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge ,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.

-

-

-

... More
6 sq. mm 2 core

3652

-

262

... More
10 sq. mm 2 core

6252

-

277

... More
25 sq. mm 3-1/2 core

3240

-

354

... More
35 sq. mm 3-1/2 core

3240

-

401

... More
50 sq. mm 3-1/2 core

2570

-

467

... More
70 sq. mm 3-1/2 core

1025

-

582

... More
95 sq. mm 3-1/2 core

480

-

665

... More
150 sq. mm 3-1/2 core

1585

-

909

... More
240 sq. mm 3-1/2 core

900

-

1083

... More
300 sq. mm 3-1/2 core

2860

-

1532

... More
400 sq. mm 3-1/2 core

604

-

1946

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.

-

-

-

... More
6 sq. mm 2 core

200

-

183

... More
10 sq. mm 2 core

196

-

184

... More
25 sq. mm 3-1/2 core

24

-

238

... More
35 sq. mm 3-1/2 core

24

-

281

... More
50 sq. mm 3-1/2 core

32

-

315

... More
70 sq. mm 3-1/2 core

28

-

357

... More
95 sq. mm 3-1/2 core

10

-

448

... More
150 sq. mm 3-1/2 core

26

-

532

... More
240 sq. mm 3-1/2 core

14

-

784

... More
300 sq. mm 3-1/2 core

58

-

912

... More
400 sq. mm 3-1/2 core

14

-

1188

... More
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.

-

-

-

... More
100 mm width X 50 mm depth X 1.6 mm thickness

400

-

414

... More
300 mm width X 50 mm depth X 1.6 mm thickness

2000

-

593

... More
450 mm width X 62.5 mm depth X 2 mm thickness

400

-

867

... More
600 mm width X 62.5 mm depth X 2 mm thickness

600

-

1042

... More
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 Way SPN DB

20

-

1964

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4WAY TPN DB

25

-

3122

... More
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4WAY VTPN DB

10

-

4313

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6WAY TPN DB

30

-

3796

... More
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8WAY VTPN DB

21

-

7758

... More
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8WAY TPN DB

15

-

4554

... More
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.

-

-

-

... More
Single pole

1360

-

196

... More
Double pole

40

-

501

... More
Triple pole

30

-

769

... More
Triple pole and neutral

25

-

938

... More
S&F of 40 Amp. TP MCB (10 KA) C Curve CAT-A

90

-

1625

... More
S&F of 63 Amp. TP MCB (10 KA) C Curve CAT-A

48

-

1644

... More
S&F of 6 Amp. to 40 Amp. 4 pole MCB (10 KA) C Curve CAT-A

30

-

2100

... More
S&F of 6 Amp. to 63 Amp. 4 pole MCB (10 KA) C Curve CAT-A

15

-

2100

... More
Dismantlinmg of Existing Panel & shifting of same at appropriate location as per Direction of Engineer In-charge

30

-

23014

... More
Repairing of Floor L.T panel including painting, fixing of rating plates, repairing of door lock etc. as required.

10

-

92506

... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.

38

-

5703

... More
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.

1900

-

186

... More
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)

500

-

110

... More
EXTERNAL LIGHT FEEDER PILLAR

-

-

-

... More
Supply installing testing & commissioning of outdoor type Distribution Panel compartmentalised design, dust tight & vermin proof made out of 14 gauge M.S. sheet, stove powder coated complete as required with following incomming & outgoing as per detail below.

-

-

-

... More
Incoming

-

-

-

... More
63 Amp. 25 KA FP MCCB 1 No.

-

-

-

... More
Suitable contractor and timer for down & dusk

-

-

-

... More
100 Amp. TPN Alu. Bus bar

-

-

-

... More
Outgoing

-

-

-

... More
25 Amp. 10KA FP MCB 5 No.

3

-

58663

... More
Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge ,complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc.

-

-

-

... More
6 sq. mm 4 core

5250

-

282

... More
10 sq. mm 4 core

3000

-

311

... More
16 sq. mm 4 core

240

-

326

... More
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.

-

-

-

... More
6 sq. mm 4 core

420

-

76

... More
4 X 10 sq. mm (25mm)

24

-

205

... More
4 X 16 sq. mm (28mm)

6

-

236

... More
Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge .

-

-

-

... More
6 sq. mm

1680

-

17

... More
Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness backlite sheet & 4 way connector with single arm bracket (1 Mtr length) on RCC foundation including the cost of foundation, foundation bolts, xcavation & back filling and Required T&P completee in all respect.

200

-

15675

... More
Supply & fixing of 7 mtr GI Octagonal Pole of approved make (top dia 70mm, Bottom dia 130mm and base plate 12mm thik) having 3mm thikness backlite sheet & 4 way connector with Double arm bracket (1 Mtr length) on RCC oundation including the cost of foundation, foundation bolts, xcavation & back filling and Required T&P completee in all respect.

10

-

16245

... More
Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable 1.5 Sqmm 3 core multistand copper unarmored cable suitable lenght and 1 no 10 Amp SPMCB for 52 watt to 72 Watt. Confirming to IP65 and above Protection complete in all respect. Cat.-AAA 6600-7920 system lumens High Power LED with lenses, 110lm/W, PF0.95, Potted driver set (Not Circuitory) Phase to Phase Protection at 440 V & 300V auto cut re-start feature. with 5 year warantee. as per as per direction of E/I.

220

-

5520

... More
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.

42

-

5232

... More
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of+B944 2.7 metre long etc. with charcoal/ coke and salt as required.

6

-

5703

... More
Supply and laying of 25 mm X 3mm G.I. strip from earth electrode irectly in the ground as required complete in all respect.

180

-

186

... More
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.

10000

-

53



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.