UP Jal Nigam Tender

If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search &amp; bid for etender UP.

UP Jal Nigam - UPJN Tender

Works
Civil And Architectural Services
Eprocure
Opening Date25 Nov 2024
Closing Soon5 Dec 2024
Tender Amount₹ 11,98,65,347 
Notes
Download

Costs

Summary

Erich Nagar Panchayat Water Supply Scheme

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
Erich Nagar Panchayat Reorganisation Water supply scheme
Financial Document
Tender document of Erich Nagar Panchayat Reorganization water supply Scheme
Report Missing Document

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Rehabilitation of the building including plastering, grouting, distempering, restoration of cement flooring, door and windows and as required Tubesettlers of 2.90 MLD Capacity Rehabilitation of tubesettlers in 2.90 MLD capacity , weirs, Pipeing system and all others features as required Sand filters for 2.90 MLD Rehabilitation of filter bedsMedia replacement Rehabilitation of the building including plastering, grouting, distempering, restoration of cement flooring, door and windows and as required Repairs to concrete, grounting, whitewashing, replacement of doors, windows and ventilators, and as required Providing pressure grouting at a pressure of 0.56 Kg/sqcm in required row/Zigzag fashion as specified at 1.5M interval as per site condition to stop leakages through water retaining structures to the entire satisfaction of the Engineer-in-charge including material compound, hardening materials, compressor equipment including scaffolding smooth finishing, etc.complete Drilling 25 mm die holes in concrete structure with providing and fixing 0.1 m long G.I pipe line for pressure grouting including all material, labour cost and machinery charges,etc. Providing and Laying water proofing treatment on the all internal surface area of the water container of OHT excluding top dome. confirming to IS 6494 – 1988 at all level as directed by engineer-in-charge Apex painting on out side surface area of WTP with asian / berger / other reputated brand material including all material, labour, T&P etc. complete.Supply of all material, labour, T&P etc.required for fixing of ladder inside the water container of Back wash OHT of 65mm dia GI pipe (medium quality steel tubes as per IS 1239) with FRP coating from opening of top roof to inside the tank and top of bottom dome. Supply and fixing of CI man hole cover with locking device at opening on the top dome to go inside the tank Providing and fixing water level indicator upto 4 M height including M.S. enamelled gauge plate 300 mm wide and 3 mm thick, copper float, providing and fixing required accessories such as pointer, pulleys, nylon thread including cost of all material, labour, etc. complete.Supply of all material, labour, T&P etc. required for repairing of damaged railing including fixing of 25 mm dia G.I. Pipe (medium quality steel tubes as per IS 1239) railing consisting of 3n rows of with posts (1.0 m) of MS angle around stair case (both sides), balcony & periphery, Construction of floor with 50mm thick 1:1.5:3 p.c.c. Floor with cement, coarse sand and 20mm gauge stone ballast with base concrete (75mm thick) 1:4:8 cement, local sand & stone ballast 40mm gauge.) Replacement of backwash OHT damaged CI D/F vertical pipes PIPE as required.as per direction of engineer incharge.

2.9

527725

1530402.5

... More
FOR CLEAR RESERVIOR TANK REPAIRING OF ONE NO. EXISTING CWR CUM PUMP HOUSE (CAPACITY 100 Kl) (ZONE-I)

-

-

-

... More
Supply and fixing on lightening Conductor on Tank with proper arrangement and alignment including all labour and T&P etc. complete.The lightening conductor consisting of an elevation rod, down conductor and earth plate shall confrom with the standars as required by theElectircal Inspector of U.P from time to time , Any amendment addition etc. suggested or required by the Electircal Inspector shall beScarriuppelyd aonutd. fixing of water level indicator with suitable arrangement as per latest I.S. code with all labour T&P etc. complete.Repais f material etc required for completion of work. Tank wall, water tighteing work including all labour, material etc required for completion of work.Repairs of cracks on concret surface of tank including all labour, material extraholding etc required for completion of work.Repairs & Replacement of pipes and valves & Specials including all labour, material etc required for completion of work.Dismentling & reconstruction (including raising of flore of tank including all labour, material etc required for completion of work.Replacment of both M.S. Ladder (inner & outer) & MS cover on topI class brick work in 1 : 6 cement and coarse sand mortar in foundation and plinth including supply of all materials, labour T and P etc. required for proper completion of the work.12 mm thick plaster with cement & coarse sand mortar in 1:1:6 over brick work minimum thickness not to be less than 12 mm finished with3 mm floting coating of neat cement including supply of all materials, labour T&P etc. required for proper completion of the workRepair for electric fittingSupply and fix angle iron door chaukhat of size 50mm x 50mm x 6 mm including supply of all materials, labour T&P etc. required for proper completion of the work.1. Door frame (2 Nos2. Window frame (4 Nos.)Supply and fixing of 1mm thick sheet iron panelled door/ window shutters including supply and fixing and adjustment of Cleats, stops, hings, locks, bolts, handles. Spring and other fittings.( Excluding suplly Apex UltimaSupply and fixing of 100 mm dia CI pipe rain water down pipe with Supply and fixing 3 mm thick plain glass in windows including supply of all materials labour, T&P etc required for proper completion of work./Acrylic Exterior/ interior paint of approved brand & manufacturer & of required shade on under coated wall surface to give an uniform surface over one primer coat of white cement of approved brand after thoroughly brushing and rubbing the surface free from mortar droppings & other foreign matters including prepairing even surface with plaster of paris including supply of all material labour T&P etc required for proper completion of work.as per direction of engineer incharge.

1

654379

654379

... More
SIZE (3.60 X 3.00 X 3.00 M) CUM CHLORNATING ROOM (2.80 x 1.50 x 3.00 M)

-

-

-

... More
Provide all materials, labour, T&P complete Pump Housesize (3.60 x 3.00 x 3.00 m) cum chlornating room (2.80 x1.50 x 3.00 m) as per type design as per direction of engineer incharge.

1

559388

559388.5

... More
Bye Pass chamber

1

24947

24947

... More
R.C.C. CLEAR WATER RESERVIOR CUM PUMP HOUSE

-

-

-

... More
Supply of all the materials, labour T&P and construction of a R.C.C. CWR of various sizes including free board, as per approved design and drawing ,including fixing of inlet and outlet pipes of suitable sizes, fixing of M.S. ladder inside and outside the tank, M.H. covers with locking arrangement and ventilators at top and suction lavel indicator, etc as per IS specification, including necessary excavation to achieve proper level of bed as per drawing and design and refilling of earth around CWR as per direction of Engineer-Incharge and also development and site clearence as per requirement and supply of all material, labour T&P etc. & construct clear water pump house of size suitable to install of Engineer Incharge including cost of pumping plant specials etc , labour construct drainage arrangement for emptying the CWR for cleaning, repairs and maintenance etc all complete.as per direction of engineer incharge.

-

-

-

... More
100 KL

1

1727100

1727100

... More
Pump House

2

584335

1168671

... More
REPAIRING OF ONE NO. EXISTING OVERHEAD TANK (400 Kl/15M) (ZONE-I)

-

-

-

... More
Supply and fixing on lightening Conductor on O.H.T. with proper arrangement and alignment including all labour and T&P etc. complete.The lightening conductor consisting of an elevation rod, down conductor and earth plate shall confrom with the standars as required by the Electircal Inspector of U.P from time to time , Any amendment , addition etc. suggestedor required by the Electircal Inspector shall be carried out.Water lavel Indicator Supply and fixing of water level indicator with suitable arrangement as per latest I.S. code with all labour T&P etc. complete.All exposed surface of structure to be given three coats of approved exteriorcement paint Berger/ narolac / Asian ( Such as apex) to give a smooth and evencolour. the pipe system of above aprorn level along with the clamps to be painted with three coats approved synthetic paints. including supply of all labour material T&P necessory Scafolding etc. complete.Repairs of O.H.T. wall, water tighteing work including all labour, material etc required for completion of work.Repairs of cracks on concret surface of OHT ( Brase, Column, Bottom dom, top Dom etc complete) by guniting method including all labour, material extraholding etc required for completion of work.Repairs & Replacement of OHT pipes & Specials including all labour, material etc required for completion of work.Repairs & Replacement of Valves & carting including all labour, material etc required for completion of work.Dismentling & reconstruction (including raising of flore of OHT including all labour, material etc required for completion of work.Replacment of both M.S. Ladder (inner & outer) & MS cover on top dome including all labour, material etc required for completion of work.Provision of medium class G.I. pipe in free roof on stair case, balconey and top dome including all labour, material etc required for completion of work.Provision of safty gate on stair case.Net on top dome went including all labour, material etc required for completion of work. as per direction of engineer incharge.

1

942902

942902.84

... More
RCC OHT

-

-

-

... More
Supply of all the materials, labour T&P and construction of a R.C.C. Over head tank above ground level with main components, including cost of soil testing and based on IS-3370 or liquid storage concrete in over head tank and foundation concrete as per specification in I.S. 2911 300 KL with 20 m Staging All components of OHT will be casted in M-30 concrete with cement, coarse sand and approved stone grit as per I.S. 11682 and I.S. 456 Minimum depth of foundation below original ground level will be 2.5 The assumed bearing capacity of soil has been taken as 8 M.T. sqm 1 m wide RCC stair case from ground level to balcony.M.S. ladder made of 50 x 50 x 6 mm angle section and 20 mm plainM.S. bars (specification of M.S. should be as per IS 800-2007) withhand rails of 20 mm medium class G.I. pipes on both sides in three rows from balcony to be top dome resting on an RCC plateform (75 x 75 cm and 10 cm thick) projecting from top ring beam and one alluminimum ladder inside thw tank body (from manhole in top dome to bootom dome).Proper R.C.C. railing and 20 mm dia medium class G.I. pipe (in 3 rows) on both sides of stair case, around the balcony at each landing from landing with top ring beam up to manhole on the top dome and at the periphery. The G.I. pipes will be supported on R.C.C. posts of 100 mm dia or on the posts made of 50 x 50 x 6 mm M.S. angle\ section, spaced at intervals not more than 1.5 m.Proper ventilator at top dome in circular shape of 1.2 m dia along with an R.C.C. cover of minimum 1.50 m dia and 7.5 cm thickness, pillar of ventilator should be minimum 50 cm dia. The space between top dome and R.C.C. cover should be covered with mosquito net of standard quality along with expended mantled jail. Supply of fixing, jointing of following size of D.I. D/F pipes with D.I. D/F specials conforming to IS 8329/2000 as vertical pipes for proper completion of work including other appurtenant work Inlet pipe 150 mm,Overflow pipe 150 mm, Outlet pipe 200 mm, Washout pipe 100 mm, Construction of Masonary type sluice valve chamber for above sluice valve as per departmental type design and drawing including supply and fixing of 150 mm x 150 mm size C.I. surface box including locking arrangement. Testing & Commission etc. all complete work. as per direction of engineer incharge.

1

5900925

5900925

... More
Testing of bearing capacity of soil from a reorganized Govt. Engineering college or as directed by department.

1

95950

95950

... More
RISING MAIN AND BYE PASS ARRANGEMENT (ZONE-I and II)

-

-

-

... More
Supply of the following sizes of D.I. pipes Class K-9 conforming to latest I.S. 8329/2000 complete in all respect F.O.R. destination including all taxes and insurance including speials.

-

-

-

... More
250 mm dia D.I. Class K-9 Total rising main including bye pass

210

3969

833582.4

... More
200 mm dia D.I. Class K-9 Total rising main including bye pass

30

2957

88711.5

... More
150 mm dia D.I. Class K-9 From CWR2 to OHT including bye pass

740

1996

1477714.14

... More
80 mm dia D.I. Class K-9 From Tube well to OHT including bye pass

410

1152

472545.91

... More
350 mm dia D.I. Class K-7 Increase pipe from River to Intake Well

1100

5128

5640921

... More
Carting from the store (up to 8 Km.) The following sizes of D.I. double pipe K-7 / K-9 and specials to the site of work lowering them in to trenches and laying true to alignment and gradient including jointing, testing of pipeline and including supply of jointing material such as nut & bolts, rubber insertion, white lead etc. com- plate but excluding cost of trenching and cutting of pipes etc. For making of lengths but including making joints.as per direction of engineer incharge.

-

-

-

... More
250 mm dia D.I. Class K-9

210

150

31668

... More
200 mm dia D.I. Class K-9

30

112

3360.9

... More
150 mm dia D.I. Class K-9

740

76

56688.44

... More
80 mm dia D.I. Class K-9

410

37

15318.83

... More
350 mm dia D.I. Class K-7

1100

183

201927

... More
Excavation in ordinary soil (lime, clay or sand Including lift up to 1.5m and lead up To 50m and refilling, watering, Ramming of excavated earth in to trenches and disposal of surplus earth up to 10 KM from the center of the foundation trenches. as per direction of engineer incharge.

2604.27

256

668984.88

... More
Supply of the following sizes of C.I. Double flanged sluice valves as per I.S. 780/1960 for testing 10kg/Sqcm F.O.R Destination including all taxes and Insurance.as per direction of engineer incharge.

-

-

-

... More
250 mm dia

2

100440

200880.92

... More
200 mm dia

2

74610

149221.44

... More
150 mm dia

2

33743

67487.39

... More
80 mm dia

1

16372

16372.91

... More
350 mm dia

1

215033

215033.55

... More
Carting of D/F Sluice valves of following sizes to the site of works lowering them into already prepared trenches and fixing them In position including supply of jointing materials such as bolt nut, rubber insertion white lead complete with excluding values and specials required but including the testing etc. complete excluding values and specials required but including the testing etc. complete.as per direction of engineer incharge.

-

-

-

... More
250 mm dia

2

3794

7589.72

... More
200 mm dia

2

2429

4859.02

... More
150 mm dia

2

2240

4481.06

... More
80 mm dia

1

1074

1074.33

... More
350 mm dia

1

5392

5392.67

... More
Supply of all materials, labour, T&P and construction of following chambers as per type design including supply and materials, labour and T&P, testing etc. complete.as per direction of engineer incharge.

-

-

-

... More
Masonry Type

7

16407

114852.15

... More
Surface Box Type

1

1731

1731.9

... More
Provision of Thrust block

-

-

-

... More
250 mm dia

2

10664

21329.68

... More
200 mm dia

1

10664

10664.84

... More
150 mm dia

2

10664

21329.69

... More
80 mm dia

1

5651

5651.46

... More
350 mm dia

1

10664

10664.84

... More
Dismantling and reinstatement of lying of pipe line including sorting out of serviceable materials and disposal of unserviceable materials.following type of road surfaces. as per direction of engineer incharge.

-

-

-

... More
C.C. Road

340

1608

546848.18

... More
DISTRIBUTION SYSTEM (ZONE-I and II )

-

-

-

... More
Excavation in ordinary soil (lime, clay or sand Including lift up to 1.5m and lead up To 50m and refilling, watering, Ramming of excavated earth in to trenches and disposal of surplus earth up to 10 KM from the center of the foundation trenches. as per direction of engineer incharge.

16110.34

256

4138424.14

... More
Supply of the following HDPE Pipes as per B.I.S. code no. 4984/2016 or its latest amendment including cost of 1 HDPE coupler per pipe length and all bend , reducer, tee and all type of spacial which are required in Electro fusion joint fitting inclusive of all taxes and duties, 3rd party inspection charges, packing and forwarding charges, transit insurance charges, road transportation charges etc. F.O.R. destination etc. complete HDPE Pipe PN-10 (O. D.) PE-100 as per direction of engineer incharge.

-

-

-

... More
90 mm dia

15998

275

4405529.24

... More
110 mm dia

1049

392

411669.56

... More
140 mm dia

715

633

452788.05

... More
160 mm dia

1232

825

1016609.44

... More
Supply of following sizes D.I. K-7 pipes, as per I.S.- 8329/2000 or its Latest ammenmend suitable for pipe with rubber gasket, coupling, coupler, including supply of specials DI DF/DI DS like Tees, Vertical / Horizontal Bend, Gap Pieces required for case of sectional testing etc and making S/S joints all materials T&P etc. all complete. as per I.S. F.O.R. destination including all local cartage etc complete.as per direction of engineer incharge.

-

-

-

... More
200 mm dia DI Pipe K-7

852

2244

1912688.88

... More
250 mm dia DI Pipe K-7

709

2949

2091535.82

... More
250 mm dia DI Pipe K-7 for connecting overflow to main supply

50

2949

147499

... More
Carting of following pipes, specials and fittings from site store to site of work, lowering them into trenches, laying true to alignment and gradient, laying and jointing with electro fusion fitting of pipe line including cutting of pipe for making up lengths as required for proper completion of work.HDPE Pipe PN-10 (O. D.) PE-100 as per direction of engineer incharge.

-

-

-

... More
90 mm dia

15998

112

1792895.86

... More
110 mm dia

1049

140

146954.41

... More
140 mm dia

715

240

172193.45

... More
160 mm dia

1232

288

355813.92

... More
Carting from store (upto 8 Km) the following sizes of D.1. Pipes (class K-9) and AC pipes (class-15) and specials to the site of work, lowering them in to trenches and taying true to alignment and gradient including testing of pipeline D.I. (K-9) pipes as per direction of engineer incharge.

-

-

-

... More
200 mm dia DI Pipe K-7

852

93

79329.72

... More
250 mm dia DI Pipe K-7

709

125

89057.49

... More
250 mm dia fDI Pipe K-7 or connecting overflow to main supply

50

125

6280.5

... More
Supply of following type of valves as per specifications F.O.R. desination rates per meter (exclusive of GST) in Rs. every where in UP upto stores of consignees inclusive of third party inspection charges, packing and forwarding charges, transit insurance charges, road transportation charges, unloading & stacking the same etc. complete.Double flanged Ductile Iron Sluice valves as per IS 14840 : 2000 as per direction of engineer incharge.

-

-

-

... More
C.I. Double flanged Sluice Valves

-

-

-

... More
80 mm

6

16372

98237.46

... More
100 mm

2

22882

45764.32

... More
125 mm

1

28224

28224.65

... More
150 mm

2

33743

67487.4

... More
200 mm

3

59688

179065.74

... More
Scour Valves

-

-

-

... More
80 mm dia

1

16372

16372.91

... More
Air Valves

-

-

-

... More
25 mm

2

7851

15703.88

... More
Fire Hydrants

-

-

-

... More
80 mm

1

18806

18806.2

... More
Carting, lowering, laying, aligning, fixing in position and installation of following valves in pipe line including all material, labour, testing and commissioning as per direction of Engineer-in- charge. Double flanged Ductile Iron Sluice valves as per IS 14840 : 2000 as per direction of engineer incharge.

-

-

-

... More
C.I. Double flanged Sluice Valves

-

-

-

... More
80 mm

6

1788

10728.12

... More
100 mm

2

2150

4300.78

... More
125 mm

1

2444

2444.97

... More
150 mm

2

3226

6452.22

... More
200 mm

3

4356

13070.13

... More
Scour Valves

-

-

-

... More
80 mm dia

1

1788

1788.02

... More
Air Valves

-

-

-

... More
25 mm

2

702

1404.46

... More
Fire Hydrants

-

-

-

... More
80 mm

1

1456

1456.11

... More
Supply of all materials, labour T&P etc. required and construction of following chambers as per type design including supply and materials labour, T&P etc. complete. construction of following chambers as per type design including supply and materials labour, T&P etc. complete. as per direction of engineer incharge.

-

-

-

... More
Surface Box Type

6

1731

10391.4

... More
Masonry Type

10

16407

164074.5

... More
Air Valves

4

6380

25522.72

... More
Fire Hydrants

2

15495

30991.86

... More
Thrust Block

10

10664

106648.4

... More
Dismantling of following type of surface including sorting out and staking of serviceable unserviceable materials up to a distance of 50 m. as per direction of engineer incharge.

-

-

-

... More
B.O.E. ROAD 60% old bricks

237.36

79

18919.97

... More
Bituminous Road

2275.96

168

382725.43

... More
CC Road

2836.05

317

901325.05

... More
Inter locking Road

7277.2

143

1046752.45

... More
Reinstatment of following type of surface including sorting out and staking of serviceable materials and disposal of unserviceable materials up to a distance of 50 m. as per direction of engineer incharge.

-

-

-

... More
B.O.E. ROAD 60% old bricks

237.36

304

72212.03

... More
Bituminous Road

2275.96

1914

4356642.63

... More
CC Road

2836.05

1290

3660092.69

... More
Inter locking Road

7277.2

951

6925201.84

... More
Crossing of Culvert for laying pipe line including supply and materials labour, T&P etc. complete.as per direction of engineer incharge.

49

14128

692303.36

... More
Crossing of Road for laying pipe line including supply and materials labour, T&P etc. complete.as per direction of engineer incharge.

-

-

-

... More
3.5 M wide Road

41

18230

747450.5

... More
7.0 M wide Road

6

44664

267988.38

... More
Road barricading of traffic, night signals, fixing caution boards etc for the laying of pipe line. as per direction of engineer incharge.

692

222

153707.04

... More
Charges payable to PWD for permission of crossing Roads.

2

43177

86355

... More
Making interconnection in 90 to 500 mm dia AC/PVC HDPE / DI pipes including supply, carting of specials, lowering them into tranches, cutting, fixing them in proper alignment and jointing including balling out of water, necessary excavation for connection and barricading including all labour, T&P etc. required for proper completion of the work. as per direction of engineer incharge.

-

-

-

... More
160 mm to 140 mm

5

8568

42841.7

... More
160 mm to 90 mm

4

8386

33544.12

... More
140 mm to 90 mm

7

7565

52959.62

... More
110 mm to 90 mm

5

4193

20965.1

... More
90 mm to 90 mm

24

4101

98444.64

... More
HOUSE CONNECTION ON EXISTING PIPE LINE (ZONE-I)

-

-

-

... More
Making House Connection with distribution main including dismantling of road, supply, carting of specials, Lowering them into trances, fixing them in proper alignment and jointing including bailing out to water, necessary excavation for connection including all labour, T&P etc. required for proper completion of the work.as per direction of engineer incharge.

-

-

-

... More
In B.O.E. Roads

-

-

-

... More
For 90 mm to 110 mm dia

7

3543

24806.95

... More
For 140 mm to 160 mm dia

1

3717

3717.03

... More
In Bituminous Roads

-

-

-

... More
For 90 mm to 110 mm dia

55

6091

335030.85

... More
For 140 mm to 160 mm dia

30

6264

187939.8

... More
For 200 mm to 250 mm dia

15

6446

96704.4

... More
In C. C. Roads

-

-

-

... More
For 90 mm to 110 mm dia

85

5380

457342.5

... More
For 140 mm to 160 mm dia

45

5553

249915.6

... More
For 200 mm to 250 mm dia

20

5735

114719.8

... More
In C. C. Interlocking tiles Roads

-

-

-

... More
For 90 mm to 110 mm dia

50

4611

230556.5

... More
For 140 mm to 160 mm dia

40

4784

191372.8

... More
For 200 mm to 250 mm dia

20

4966

99332.6

... More
In Earthen Roads

-

-

-

... More
For 90 mm to 110 mm dia

20

2967

59358.6

... More
For 140 mm to 160 mm dia

5

3141

15705.6

... More
For 200 mm to 250 mm dia

5

3323

16617.1

... More
HOUSE CONNECTION ON NEW/EXTENSION PIPE LINE (ZONE-I)

-

-

-

... More
Making House Connection with distribution main including dismantling of road, supply, carting of specials, Lowering them into trances, fixing them in proper alignment and jointing including bailing out to water, necessary excavation for connection including all labour, T&P etc. required for proper completion of the work.as per direction of engineer incharge.

-

-

-

... More
In B.O.E. Roads

-

-

-

... More
For 90 mm to 110 mm dia

18

3083

55507.86

... More
For 140 mm to 160 mm dia

1

3256

3256.96

... More
For 200 mm to 250 mm dia

1

3439

3439.27

... More
In Bituminous Road

-

-

-

... More
For 90 mm to 110 mm dia

249

4612

1148472.66

... More
For 140 mm to 160 mm dia

76

4785

363700.28

... More
For 200 mm to 250 mm dia

36

4967

178842.24

... More
In C. C. Roads

-

-

-

... More
For 90 mm to 110 mm dia

454

4185

1900335.04

... More
For 140 mm to 160 mm dia

79

4358

344357.05

... More
For 200 mm to 250 mm dia

50

4541

227062.5

... More
In C. C. Interlocking tiles Roads

-

-

-

... More
For 90 mm to 110 mm dia

273

3724

1016690.22

... More
For 140 mm to 160 mm dia

63

3897

245531.79

... More
For 200 mm to 250 mm dia

38

4079

155026.32

... More
In Earthen Roads

-

-

-

... More
For 90 mm to 110 mm dia

117

2738

320371.74

... More
For 140 mm to 160 mm dia

13

2911

37848.33

... More
For 200 mm to 250 mm dia

13

3093

40218.36

... More
REPAIRING OF BOUNDARY WALL

-

-

-

... More
Existing Boundry wall area Zone 1 First class brick work in 1:4 cement and local sand mortar in super structure and plinth including supply of all materials, labour T&P etc required for proper completion of work.12 mm thick plaster with cement and local sand mortar in proportion of 1:6 over brick work, minimum thickness not be less than 10 mm including supply of all materials labour, T&P etc required for proper completion of work. Provision of barbed iron wire fencing to posts in four rows.Provision M.S. iron angle (50x50x6mm) for the barbed wire fixing and meter C/C.Cement concrete with 20 mm gauge approved stone ballast coarse sand and cement in proporation 4:2:1 including supply of all materials, labour, T&P etc required for fixing M.S. Iron angle proper completion of work.White washing in three coat including supply of all materials, labour, T&P etc. complete required for proper completion of the workProviding plaster of Paris wall putty of 2mm thickness over plastered surface to prepare the surface even and smooth complete.Apex Ultima /Acrylic Exterior/ interior paint of approved brand & manufacturer & of required shade on under coated wall surface to give an uniform surface over one primer coat of white cement of approved brand after thoroughly brushing and rubbing the surface free from mortar droppings & other foreign matters including prepairing even surface with plaster of paris including supply of all material labour T&P etc required for proper completion as per direction of engineer incharge.

204

2686

548066.4

... More
BOUNDARY WALL, GATE SITE DEVELOPMENT & APPROACH ROAD (ZONE-II)

-

-

-

... More
Construction of compound wall comprising of RCC Columns @ 3.0 m c/c distance with beam at plinth and top, brick work in 1:4 of as per type design including supply of all material, labour, T& P etc complete ( 2m height above plinth level 230 mm thick brick wall ) as per direction of engineer incharge.

135.2

7004

946988.12

... More
Provide all materials, labour T&P etc. required for proper completion of work and construct pillars as per type design and fixing of gate 3.6 m wide gate and 1.2 m wicket gate.

1

46535

46535.75

... More
Provide all materials, labour T&P etc. required for proper completion of work and construct Interlocking approach road.

153

1563

239267.67

... More
Construction of Drain as per type design in all materials, labour T&P etc. required for proper completion of work inside campous for proper drainage. Size (300 mm x 300 mm). as per direction of engineer incharge.

80

2014

161196

... More
Provision of Lighting in campous as per direction of Engineer-in-charge including all materials , labour T&P etc complete.

1

43177

43177.5

... More
Provide all labour,T&P chlorination complete and construction of chlorination room. Zone 1 and 2 as per direction of engineer incharge.as per type design.

2

191900

383800

... More
Provide all materials, labour T&P etc. required for proper completion of work including leveling, dressing excavation and filling of earth where necessary for develop of water works site including carriage of earth For Main Compound as per direction of engineer incharge.

1306.25

314

411097.78

... More
REPAIR OF ONE NO. EXISTING STAFF QUARTER (ZONE-I)

-

-

-

... More
Ist Class brick work in 1:4 cement and local sand mortar in superstructure including supply of all material, labour, T&P etc required for proper completion of the work. (Thickness of wall to one brick thick).12 mm thick plaster with cement & coarse sand mortar in 1:1:5 over brick work minimum thickness not to be less than 12 mm finished with 3 mm floting coating of neat cement including supply of all materials, labour T&P etc. required for proper completion of the work.Scraping old color washing and preparing the surface by removing loos material etc. including all labour and T&P etc complete. 40 mm thick over base concrete consisting of cement, local sand and 40 mm gauge first class brick ballast in the proportion of 1:4:8. For construction of apron 0.6 m wide. White washing in three coat including supply of all materials, labour, T&P etc. complete required for proper completion of the work Providing plaster of Paris wall putty of 2mm thickness over plastered surface to prepare the surface even and smooth complete.Apex Ultima /Acrylic Exterior/ interior paint of approved brand & manufacturer & of required shade on under coated wall surface to give an uniform surface over one primer coat of white cement of approved brand after thoroughly brushing and rubbing the surface free from mortar droppings & other foreign matters including prepairing even surface with plaster of paris including supply of all material labour T&P etc required for proper completion of work. Supply and fixing of flush doors including supply of all materials, paints, labour T&P etc. required for proper completion of the work.Repair for electric fitting Repair for sanitation work.as per direction of engineer incharge.

1

225482

225482.5

... More
STAFF QUARTER FOR PUMP OPERATOR (ZONE-II)

-

-

-

... More
Provide all materials, labour, T&P Complete and construction of a set of Single room Set Staff quarter for pump operator as per type design ( 30 SQM ) as per direction of engineer incharge.

1

1175387

1175387.5

... More
MASTER CONTROL STATION

-

-

-

... More
Provide all materials, labour, T&P Complete and construction of a room for Master Control Station size. as per direction of engineer incharge. ( 40 SQM ) as per direction of engineer incharge.

1

1127412

1127412.5

... More
E AND M WORKS

-

-

-

... More
RENNOVATION OF PUMPING MACHINARY AND ACCESSORIES FOR EXISTING INTAKE WELL

-

-

-

... More
SITC of Vertical type self-oil lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 14 mtr/suitable length column assembly, with vertical hollow shaft. Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-

-

-

-

... More
2500LPM, 30.0 HP, 31m Head

2

820770

1641541.39

... More
SITC of 150mm Main piping complete with suitable size and quantity required for delivery side, bye pass arrangement and 150mm common Header upto 1 m. outside the pump house along with 150 x 150 x 150 mm A/F Tee, 150 mm bend, 150 mm blind flange, D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe and dismantling joints etc. complete in all respect as per site conditions suitable for above pumping plants.

1

143925

143925

... More
SITC of Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes

-

-

-

... More
Valve actuator of size 150mm for pumps

2

119937

239875

... More
Valve actuator of size 150mm for common header

1

119937

119937.5

... More
SITC of Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .

-

-

-

... More
150 mm Dia for pumps

2

38397

76794.54

... More
150 mm Dia for common header

1

38397

38397.27

... More
SITC of CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.

-

-

-

... More
Electromagnetic flow meter of size 150mm for common header

1

143925

143925

... More
SITC OF ELECTRICAL ITEMS:-

-

-

-

... More
Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 25 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity 99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)

60

1810

108634.62

... More
SITC OF MOTOR CONTROL CENTER (MCC) PANEL :- Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting of INCOMMING SECTION 400A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION 160 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 3 No, Spreader Links & Extended ROH for MCCB - 3 Nos., 63A TPN MCCB 35KA - 2 Nos. Terminal 63A

1

531342

531342.32

... More
SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 30 HP / 22 KW

2

81557

163115

... More
SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 19KVAR

1

82415

82415.29

... More
SITC of Servo Controlled Automatic Voltage stabilizer suitable for out put voltage of 415 Volt +/-1%, 3 Ph, 50 Hz, with copper wound transformer (air/oil cooled) . The stabilizer shall function satisfactorily even if incoming supply is unbalanced between phases within range of 10%. The stabilizer should be constructed in cubical box, with bi- directional wheels for easy handling, necessary monitors and user's controls on front panel such as indication, alarm, volt meter and selector switch for measuring input and out put voltage, Auto/Manual selector switch, Raise/Low push buttons etc. Suitable capacity termination strips and bus bars for incoming and out going cable should be provided. All three phases shall be independently monitored and corrected (Operating voltage 240V - 500V), 415 volt, 3Phase, 50Hz -- 50 KVA with changeover switch.

1

191900

191900

... More
SITC of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)

-

-

-

... More
160 Amp Rating

1

67165

67165

... More
SITC of CE/UL Certified level transmitter for Intake well :- Supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Range- 0 to …30... mtrs Accuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68

-

-

-

... More
CE/UL Certified level transmitter for Intake well

1

115140

115140

... More
SITC of CE/UL Certified Pressure transmitter for pumps and common header :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68

-

-

-

... More
CE/UL Certified Pressure transmitter for pumps

2

47975

95950

... More
CE/UL Certified Pressure transmitter for Common Header

1

47975

47975

... More
SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)

1

143925

143925

... More
Supply and fixing of Rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness

5

2820

14104.65

... More
Supply and fixing of Cable trench Chequerred plate

500

172

86355

... More
SITC of Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.

4

6080

24321.41

... More
SITC of Internal and external electrification of pumping station:-

-

-

-

... More
Indoor Lighting

-

-

-

... More
Surface Mounting

-

-

-

... More
Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD 10 % , p. f.≥ 0.95,CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard

-

-

-

... More
Suspended Mounting / Surface Mounting

-

-

-

... More
36W LED light fixture 2'×2' with acrylic / prismatic front cover.

4

2502

10009.5

... More
Fans

-

-

-

... More
Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.

-

-

-

... More
1200 mm Sweep BEE 3 Star rated (service value =5.0 to 5.5 )

2

1551

3103.02

... More
Fixing of fresh air fan/exhaust fan up to size of 300 mm on ply/ poly board of 6.0 mm in existing window frame including cost of ply, cutting of hole in ply. Nut bolts etc. as required.

2

132

264.82

... More
Installation, testing and Commissioning of ceiling fan (any size) including wiring the down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required.

-

-

-

... More
with regulator

2

50

101.71

... More
Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.

-

-

-

... More
450mm sweep (900/1400 RPM)

2

4103

8207.56

... More
Outdoor Lighting

-

-

-

... More
Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system.

-

-

-

... More
Compact Solar LED Street Light- 60W(MONO) 18V / 12.8V 27Ah /40W

2

44014

88028.37

... More
Complete wiring of Pump house with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.

1

49126

49126.4

... More
Automation For Intake Well

-

-

-

... More
CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.

1

550000

550000

... More
GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.

1

30000

30000

... More
CE/UL Certified Intelligent energy meters

1

25000

25000

... More
CE/UL Certified Surge protector for control panel

1

15000

15000

... More
CE/UL Certified 3 KVA UPS with batteries as per technical bid documents

1

150000

150000

... More
CE/UL Certified 7" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.

1

30000

30000

... More
Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments

1

150000

150000

... More
Cable

-

-

-

... More
(i) Complete cabling upto 3 Pumps

1

80000

80000

... More
Security Survelliance IP Camera with recorder (optional)

2

20000

40000

... More
Installation, commissioning & testing

1

20000

20000

... More
RENNOVATION OF PUMPING MACHINARY AND ACCESSORIES FOR EXISTING CWR TO OHT ZONE-1( 400KL )

-

-

-

... More
SITC of Energy Efficient Totally Enclosed Fan Cooled (TEFC) Squirrel Cage Induction Motor (IE2) ( Enclosure conforming to protection IP55) Horizontal Foot Mounted Induction Motor, continuously rated suitable for operation on 415+/-10% ,50Hz+/-5% , A.C. supply with class F insulation for 50 Deg. C ambient temperature and altitude less than 1000 M above MSL and conforming to IEC:60034-1 & IS 12615:2018. with pump with following specifications.

-

-

-

... More
1400LPM, 20.0 HP, 39m Head

2

260136

520273.52

... More
SITC of 150mm Main piping complete with suitable size and quantity required for delivery side and 150mm common Header upto 1 m. outside the pump house along with 150 x 150 x 150 mm A/F Tee, 150 mm duckfoot bend, Enlargers, 150 mm blind flange, D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe and dismantling joints etc. complete in all respect as per site conditions suitable for above pumping plants.

1

143925

143925

... More
SITC of Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes

-

-

-

... More
Valve actuator of size 150mm for pumps

4

119937

479750

... More
Valve actuator of size 150mm for common header

1

119937

119937.5

... More
Valve actuator of size 250mm at CWR Inlet

1

182305

182305

... More
SITC of Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .

-

-

-

... More
150 mm Dia for pumps

2

38397

76794.54

... More
150 mm Dia for common header

1

38397

38397.27

... More
SITC of CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.

-

-

-

... More
Electromagnetic flow meter of size 150mm for common header

1

143925

143925

... More
Electromagnetic flow meter of size 250mm at CWR Inlet

1

215887

215887.5

... More
SITC OF ELECTRICAL ITEMS:-

-

-

-

... More
Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 16 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity 99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)

60

1206

72365.52

... More
SITC OF MOTOR CONTROL CENTER (MCC) PANEL :- Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting of INCOMING SECTION 125A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION 63 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 3 No, Spreader Links & Extended ROH for MCCB - 3 Nos., 63A TPN MCCB 35KA - 2 Nos. Terminal 63A

1

402500

402500.66

... More
SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 20HP / 15 KW - 2 Nos.

2

67165

134330

... More
SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 14KVAR

1

49449

49449.75

... More
SITC of Servo Controlled Automatic Voltage stabilizer suitable for out put voltage of 415 Volt +/-1%, 3 Ph, 50 Hz, with copper wound transformer (air/oil cooled) . The stabilizer shall function satisfactorily even if incoming supply is unbalanced between phases within range of 10%. The stabilizer should be constructed in cubical box, with bi- directional wheels for easy handling, necessary monitors and user's controls on front panel such as indication, alarm, volt meter and selector switch for measuring input and out put voltage, Auto/Manual selector switch, Raise/Low push buttons etc. Suitable capacity termination strips and bus bars for incoming and out going cable should be provided. All three phases shall be independently monitored and corrected (Operating voltage 240V - 500V), 415 volt, 3Phase, 50Hz -- 40 KVA with changeover switch.

1

168872

168872

... More
SITC of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)

-

-

-

... More
125 Amp Rating

1

47975

47975

... More
SITC of CE/UL Certified level transmitter for Intake well :- Supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Range- 0 to …30... mtrs Accuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68

-

-

-

... More
CE/UL Certified level transmitter for CWR

1

115140

115140

... More
SITC of SITC of CE/UL Certified Pressure transmitter for pumps and common header :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68

-

-

-

... More
CE/UL Certified Pressure transmitter for pumps

2

47975

95950

... More
CE/UL Certified Pressure transmitter for Common Header.

1

47975

47975

... More
SITC of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( Competible to SCADA )

1

71962

71962.5

... More
SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)

1

143925

143925

... More
Supply and fixing of Rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness

5

2820

14104.65

... More
Supply and fixing of Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.

4

6080

24321.41

... More
SITC of Internal & External electrification of CWR

-

-

-

... More
Indoor Lighting

-

-

-

... More
Surface Mounting

-

-

-

... More
Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD 10 % , p. f.≥ 0.95,CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard

-

-

-

... More
Suspended Mounting / Surface Mounting

-

-

-

... More
36W LED light fixture 2'×2' with acrylic / prismatic front cover.

6

2502

15014.26

... More
Fans

-

-

-

... More
Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.

-

-

-

... More
1200 mm Sweep BEE 3 Star rated (service value =5.0 to 5.5 )

2

1551

3103.02

... More
Fixing of fresh air fan/exhaust fan up to size of 300 mm on ply/ poly board of 6.0 mm in existing window frame including cost of ply, cutting of hole in ply. Nut bolts etc. as required.

2

132

264.82

... More
Installation, testing and Commissioning of ceiling fan (any size) including wiring the down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required.

-

-

-

... More
with regulator

2

50

101.71

... More
Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.

-

-

-

... More
450mm sweep (900/1400 RPM)

2

4103

8207.56

... More
Outdoor Lighting

-

-

-

... More
Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system.

-

-

-

... More
Compact Solar LED Street Light- 60W(MONO) 18V / 12.8V 27Ah /40W

6

44014

264085.1

... More
Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.

1

36940

36940.75

... More
AUTOMATION FOR CWR-1

-

-

-

... More
CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.

1

550000

550000

... More
GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.

1

30000

30000

... More
CE/UL Certified Intelligent energy meters

1

25000

25000

... More
CE/UL Certified Surge protector for control panel

1

15000

15000

... More
CE/UL Certified 3 KVA UPS with batteries as per technical bid documents

1

150000

150000

... More
CE/UL Certified 7" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.

1

30000

30000

... More
Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments

1

150000

150000

... More
Turbidity Analyzer at CWR

1

135000

135000

... More
PH Analyzer

1

135000

135000

... More
Chlorine Analyzer

1

270000

270000

... More
Cable

-

-

-

... More
(i) Complete cabling upto 3 Pumps

1

80000

80000

... More
Security Survelliance IP Camera with recorder (optional)

2

20000

40000

... More
Installation, commissioning & testing

1

20000

20000

... More
AUTOMATION OF EXISTING OHT ( 400 KL ) AGAINST ZONE-1 WITH 02 NO. DMA ZONES

-

-

-

... More
Supply of Motor operated actuator without sluice valve at OHT outlet :- Supply of DI/DF Electrically integrated actuater without sluice valve (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes

-

-

-

... More
250 mm dia

1

115000

115000

... More
Supply of flow control valve with electric actuator for flow controling,pressure monitoring and web based with cable PLC etc Complete at DMA inlet.

-

-

-

... More
200 mm

1

307904

307904

... More
250 mm

1

416010

416010

... More
Supply of CE/UL Certified level transmitter for OHT :- Supply of Radar type level transmitter with CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Range- 0 to …30... mtrs Accuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68

1

120000

120000

... More
Supply of CE/UL Certified Electromagnetic flow meter at DMA inlet :- Supply of CE/UL Full Bore Electromagnetic Flow Meter of approved make for remote places of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable and also interfacing with PLC panel.

-

-

-

... More
200 mm dia

1

190000

190000

... More
250 mm dia

1

225000

225000

... More
Supply of CE/UL Certified Pressure transmitter at DMA inlet :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68

2

50000

100000

... More
Supply of Dosing System at DMA inlet :-Supply of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( SCADA Compatible )

2

75000

150000

... More
Supply of Residual chlorine analyser / meter at DMA inlet :-Supply of RCA must have automatic sensor cleaning facility at pure water sump and Interfacing with PLC panel. Residual Chlorine meter shall comprises of 3 components i.e. sensors, flow through assembly and transmitter with indicator and gives 2 outputs one to Local display & other to PLC including Mounting arrangement. Overall Range : 0 - 8 mg/l (ppm) Accuracy : 2% of full scale Supply Voltage : 230 V ac+B7 Output : 4-20 mA Membrane free sensor of 2 gold plated electrodes for long term stability and reference electrode (ag/Agcl) must be provided to avoid maintenance. IP 65 Nema 4 housing protection class required.

2

270000

540000

... More
Installation, cabling of OHT including all power and control cable of all equipments,testing and commissioning complete in all respect.

2

100000

200000

... More
160 KVA SUB STATION AT ( CWR-1+WTP )

-

-

-

... More
Supplying of indoor type floor mounted metal clad, 11 KV VCB panel with 1No. VCBs, totally enclosed & fully interlocked, horizontal drawout, horizontal/ vertical isolation type breaker as per IS 13118, as amended up to date and additional specifications, having capacities as mentioned below, single break, trip free mechanism, manually charged and auto/manually closing breaker suitable for use on 11 KV, 3 Phase, 50 Hz A.C. supply with short circuit fault level of 100 KVa, complete with self contained, fully interlocked, rack in and rack out mechanism, air insulated but encapsulated copper bus bars of 1600Amps capacity, breaker featured with mechanical ON/OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4 NO+4NC and equipped with following switchgears and accessories i/c connections suitable for 11 KV cable (cable entry from *bottom/ top/side) end termination with heat shrinkable jointing material etc. as required. (Note- Cost of end termination not included in this item) (a) Incoming – ½* No 800Amp. VCB (b) 1* No. – 11 KV / 110 Volts PT Class 0.5 accuracy and 100 VA burder with 1 No. Voltmeter (0-15KV), analog/digital* type, selector switch for voltmeter and protection fuses/MCB for HT metering upto 12 KV on incomer. (c) 1* No. – (0-100 A) dual scale Ammeter, analog/digital* type, selector switches for ammeters. (d) 1* No. – Microprocessor based numerical relay with O/L, E/F and S/C protection. (e) 1* No. – Set of dual core dual ratio 3 CTs 300/150/5/5 A of 15 VA burden and accuracy Class – 0.5 for metering and class 5P10 for protection. (a) Outgoing – 2Nos. 800Amp. VCB (b) 2Nos. – (0-100 A) Ammeters, dual scale analog/digital* type & selector switches for Ammeters. (c) 2 Nos. – Microprocessor based numerical relays with O/L, E/F & S/C protections. (d) 2 Nos. – Set of dual core dual ratio 3 CTs 100/ 50/5/5 A of 15 VA burden and accuracy Class-1.0 for metering and class 5P10 for protection. 1. Supply of power pack 24 volts complete with battery and charging device.

1

2110900

2110900

... More
Supply of 50 Sq.mm size XLPE cable from 11 K.V.UPPCL metering panel to 11 KV incoming H.T. switch gear panel and panel to transformer.

100

630

63039.2

... More
Supplying of 160 KVA, 11/0.415 KV, 3 Phase, 50 Hz, Dyn 11, indoor ONAN type, copper wound transformer with OFF load tap changing arrangement on HV side in steps of +/- 2.5% & -7.5%, having cable end boxes on HV side suitable for 3x150sqmm XLPE cable of 33 KV grade and bus trunking arrangement on LV side complete with all accessories i/c first filling of filtered dehydrated oil and confirming to IS 1180 & as per specification attached complete in all respects as required at site.

2

492363

984727.17

... More
Supplying of cubicall type LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2 mm thick for frame work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 630Amp capacity extensible type TPN aluminium alloy bus bars of hight conductivity, DMC / SMC bus bars of high conductivity, DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec., bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 50sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half, i/c providing following switch gears :- (I) Incoming : 2 Nos 400 Amps horizontal drawout type air circui+B12t breaker of fault breaking capacity 50 KA (Ics=Icu upto 433 V manually operated, fitted with interlocked door, automatic safety shutters, mechanical ON/ OFF and service/test/isolated position indicators and frame earthing contact, conforming to IS 1397- 2 : 1993 as amended up-to-date complete with following accessories for each MCCB. (a) Independent manual spring closing mechanism- 1 No.B10 (b) Microprocessor release (EMI & EMC certified) for over current, earth fault & short circuit protection- 1 set. (c) Analog 96 mm square flush pattern / Digital* type Voltmeter (0-500 V), with selector switch & back up HRC fuses/ MCBs-1 set. (d) Analog 96 mm. square flush pattern/ Digital* type Ammeter (0-630Amp), with selector switch and one set of 3 nos. CT’s of ratio10/5A Class I accuracy and 15 VA burden- 1set. (e) 3 Nos. Phase indication LED lamps with 2 Amp back up HRC fuse, breaker ‘ON’ indicating light with 2 A HRC fuse, test terminal block set, fuses, circuits as per standard practice, auxiliary contacts for positive interlocking of the breakers as required. (f) Shunt trip coil 220 V A.C. (II) Bus Couplers : 1Nos. 320Amps drawout type, air circuit breakers of fault breaking capacity 50 KA (Ics=Icu upto 433 V) manually operated, with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact conforming to IS 13947- 2 : 1993 as amended upto date complete with following accessories for each MCCB: (a) Independent manual spring closing mechanism- 1 No. (b) Breaker ‘ON’ indicating light with back up 2 A HRC fuse test terminal block, fuses, circuits contactors for positive electrical interlocking of breakers, etc. as required- 1 set. (III) Bus Bars : TPN aluminium bus bars of minimum of 630Amps capacity with heat shrinkable coloured sleeves and i/c DMC/SMC bus bar cross section, size supports & their spacing etc. for withstanding fault level of 31 MVA for 1 Sec.

1

531342

531342.32

... More
(IV) Interlocking : Electrical through advance contacts in ACB’s (incomers & bus couplers) and mech- anical (castel key) interlocking should beprovided to ensure that only one supply is available at a time on each section of bus and to eliminate any possiblility of accidentally approaching two supplies at one bus section. (V) Outgoing : (a) 1 Nos. 400Amp 4 Pole MCCB (Ics = kA upto 433 V)/SFU with HRC fuse (BC : 80 kA) (b) CT’s of ratio 10/5Amps 4Nos.4Set (1 set of 2 Nos.) (c) Analog 96 mmsq/Digital* type ammeter (0-100Amp) with selector switch set.

-

-

-

... More
Supply and laying of 650/1100 volt grade 185sq mm 3½ core PVC Armoured Aluminium cable from transformer to L.T panel and from outgoing panel to distribution panel (1x3½x185 sq mm)

400

1981

792547.2

... More
Making Earth pit for earthing complete in all respect. Earthing system shall executed as per IS:3043 and I.E. rules.

8

9211

73689.6

... More
Installation and commissioning of 11 KV/0.4 KV substations including HT Panels and L.T. main control panel including all labor T&P complete in all respect.

1

191900

191900

... More
Supply and making of indoor cable end termination joint kit of size 70 sq mm 3 core for 11 KV H.T. XLPE cable

6

8122

48733.01

... More
Supply and making of outdoor cable end termination joint kit of size 240 sq mm 3 core for 11 KV H.T. XLPE cable

6

16470

98824.66

... More
Provision for routine testing of equipments such as transformer, HT Panels and main LT Panel at manufacturer’s works.

1

95950

95950

... More
NOC from Electrical safety department for all field installations such as pumping plants, substation etc.

1

95950

95950

... More
CONSTRUCTION OF NEW TUBEWELL TO FEED OHT ( ZONE-2 )

-

-

-

... More
Resistivity and hydrological Survey

1

14392

14392.5

... More
Transportation from store :

-

-

-

... More
Transportation, Erection, Dismantiling of DC/RC/DTH Rig machine

1

31356

31356.46

... More
Transportation, Erection, Dismantiling of 150 PSI Compressor

1

22298

22298.78

... More
Transportation, Erection, Dismantiling of 1 Cusec / 3 Cusec OP Unit and Yield test

1

43062

43062.36

... More
Drilling of Tube well bore :

-

-

-

... More
Drilling and reaming of 450mm dia bore from GL to 35 m BGL by DC method

35

1679

58769.38

... More
Drilling and reaming of 200/165mm dia bore from 36 m BGL To 75 m below by DTH method.

40

1199

47975

... More
Tube Well Assembly :

-

-

-

... More
M.S. Tubewell Assembly with all required parts like plain pipe, slotted pipe, rings, well cap, well plug, clamp, reducer, central guide, support structure etc. as required as per typed design complete in all respect.

-

-

-

... More
200mm dia M.S.E.R.W. housing plain/slotted pipe of wall thickness 7.1 mm. :- 35 Mtr.

35

2648

92687.7

... More
Lowering of Tube well Assembly

-

-

-

... More
Lowering of 200mm. Dia M.S. housing pipe from GL to 35 mtr. BGL

35

239

8395.63

... More
Supply of 1.6 to 4.8mm size pea gravel and shrouding of tube well

7

6236

43657.25

... More
Development of Tube well

-

-

-

... More
By Air Compressor

-

-

-

... More
Development of Tube well by 150 PSI capacity air compressor

20

2331

46631.7

... More
By Over Pumping Unit

-

-

-

... More
Development of Tube well by OP Unit

40

748

29936.4

... More
Chemical & Bacteriological test of water

1

1439

1439.25

... More
PUMPING MACHINARY OF TUBEWELL (ZONE-2)

-

-

-

... More
SITC of Pumping Plant including panel, cable, complete in all respect with all required material T&P labour etc. (200LPM , 95 m Head , 2900 RPM, 10 H.P)

1

124926

124926.9

... More
SITC of Main piping & Valves with 24 mtr. Column pipe, Painting, Tools with wiring of pump house (internal & external) complete in all respect with required material, T&P labour, chain pully and gauges. - 63 mm dia

1

133754

133754.3

... More
TOOLS (REPUTED MAKE ) IN A TOOL KIT 1. Pipe wrenches - 2 No. 2. D/E Spanner 22/6 mm - 6 Pcs 3. Adjustable wrench 300 mm - 1 No. 4. Screw driver 5. 250 mm - 1 No. 6. 200 mm - 1 No. 7. 150 mm - 1 No. 8. Combination pliers 200 mm - 1 No. 9. Nose pliers 150 mm - 1 No. 10. hammer with handle 1 kg. - 1 No. 11. Line tester (Taparia make) - 1 No.

-

-

-

... More
Soft Starter with RS 485 Port- 400 V Class, 7.5 KW, Rating

1

57570

57570

... More
Supply and fixing of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( SCADA Competible )

1

71962

71962.5

... More
Motor Operated Actuator with Sluice Valve - 63 mm size

2

62367

124735

... More
CE/UL Certified Electromagnetic Flowmeter-63 mm size

1

67165

67165

... More
Servo voltage stabilizer oil cooled having capacity 20 KVA fully copper winding three phase A.C supply 50 Hz. Input voltage 240-450 output voltage 415 volt +/- 1% with earthling wire and power cable

1

115140

115140

... More
Auto Phase reversal unit with inbuilt time delay & enclousare ( confirm to IEC:60947-1 & IEC:-60947-b-1)

-

-

-

... More
100 Amp Rating

1

43177

43177.5

... More
Electrical & Instrumentation Works for Zone-2

-

-

-

... More
ELECTRCAL SYSTEM

-

-

-

... More
INTERNAL & EXTERNAL ELECTRIFICATION WORK FOR TUBEWELL ( ZONE-2 )

-

-

-

... More
Indoor Lighting

-

-

-

... More
Surface Mounting

-

-

-

... More
Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD 10 % , p. f.≥ 0.95,CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard

-

-

-

... More
Suspended Mounting / Surface Mounting

-

-

-

... More
36W LED light fixture 2'×2' with acrylic / prismatic front cover.

4

2502

10009.5

... More
Outdoor Lighting

-

-

-

... More
Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system.

-

-

-

... More
Compact Solar LED Street Light- 60W(MONO) 18V / 12.8V 27Ah /40W

2

44014

88028.37

... More
Complete wiring of Pump house,with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.

1

14392

14392.5

... More
Complete earthing / lightning protection system including earth electrode, earth strip, wires, junction box for test links, treated and non-treated earth pits, etc. with necessary accessories

1

19190

19190

... More
AUTOMATION OF PROPOSED OHT ( 200 KL ) WITH 02 NO. DMA Zone-2

-

-

-

... More
Supply of Motor operated actuator without sluice valve at OHT outlet :- Supply of DI/DF Electrically integrated actuater without sluice valve (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes

-

-

-

... More
200 mm dia

1

50000

50000

... More
300 mm dia

1

65000

65000

... More
Supply of flow control valve with electric actuator for flow controling,pressure monitoring and web based with cable PLC etc Complete at DMA inlet.

-

-

-

... More
200 mm

1

307904

307904

... More
300 mm

1

493094

493094

... More
Supply of CE/UL Certified level transmitter for OHT :- Supply of Radar type level transmitter with CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Range- 0 to …30... mtrs Accuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68

1

120000

120000

... More
Supply of CE/UL Certified Electromagnetic flow meter at DMA inlet :- Supply of CE/UL Full Bore Electromagnetic Flow Meter of approved make for remote places of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable and also interfacing with PLC panel.

-

-

-

... More
200 mm dia

1

190000

190000

... More
300 mm dia

1

260000

260000

... More
Supply of CE/UL Certified Pressure transmitter at DMA inlet :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68

2

50000

100000

... More
Supply of Dosing System at DMA inlet :-Supply of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank.( SCADA Compatible )

2

75000

150000

... More
Supply of Residual chlorine analyser / meter at DMA inlet :-Supply of RCA must have automatic sensor cleaning facility at pure water sump and Interfacing with PLC panel. Residual Chlorine meter shall comprises of 3 components i.e. sensors, flow through assembly and transmitter with indicator and gives 2 outputs one to Local display & other to PLC including Mounting arrangement. Overall Range : 0 - 8 mg/l (ppm) Accuracy : 2% of full scale Supply Voltage : 230 V ac+B7 Output : 4-20 mA Membrane free sensor of 2 gold plated electrodes for long term stability and reference electrode (ag/Agcl) must be provided to avoid maintenance. IP 65 Nema 4 housing protection class required.

2

270000

540000

... More
Installation, cabling of OHT including all power and control cable of all equipments,testing and commissioning complete in all respect.

2

100000

200000

... More
Master Control Station ( MCS ) at Existing WTP

-

-

-

... More
CE & BIS approved manufacturer's industrial grade LCD monitor with latest configuration as per specification of size 65"

1

240000

240000

... More
Desktop/PC for STP as per spec. mentioned

2

90000

180000

... More
CE/UL approved manufacturer's 5 KVA UPS with batteries as spec. mentioned for STP and Computer as per requirement

1

300000

300000

... More
CE & UL approved manufacturer's control room PLC with CPU & power supply at MCS in IP65 enclosure as per spec. mentioned

1

550000

550000

... More
CE/UL certified field gateway agent for transfering data from MCS to control room

1

150000

150000

... More
GSM based wireless / broadband/Equipment communication system for PLC capable to transfer and gather data from remote sites to control stations, including all accessories complete

1

40000

40000

... More
CE/UL approved manufacturer's Firewall for network protection

1

180000

180000

... More
Lightning surge protector for ethernet communication protection

1

15000

15000

... More
CE/UL approved manufacturer's industrial grade ethernet switch

2

15000

30000

... More
Mobile App facility system architecture complete.

1

250000

250000

... More
Canon/HP 1018/equivalent Laser printer

1

30000

30000

... More
Security Survelliance IP camera

1

20000

20000

... More
Installation, testing and commissioning with required furniture,Air Conditioner etc

1

50000

50000

... More
SCADA SYSTEM FOR 1 TUBEWELL

-

-

-

... More
CE & UL Certified PLC/ RTU in IP 54 enclosure suitable to communicate with GSM based modem unit with CPU & Power supply with analog & digital parameter & features as specified, for each tubewell/ OHT & stand alone OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations.

1

275000

275000

... More
G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/ PLC Capable to transfer and gather data from remote sites to control stations all accessories included with signal enhancer anteena made for pumping plant internet charges.

1

30000

30000

... More
CE & UL certified Inteligent Smart Energy Meter

1

25000

25000

... More
CE & UL certified Hydrostatic type sub soil water level transmitter for tubewell.

1

120000

120000

... More
CE & UL certified pressure transmitter

1

50000

50000

... More
CE & UL certified Surge protector for above control panel

1

15000

15000

... More
CE/UL Certified 1 KVA UPS with batteries as per technical bid documents

1

50000

50000

... More
CE & UL certified 7" HMI touch screen suitable to communication with PLC/RTU local display and control of process parameter.

1

30000

30000

... More
Complete cabling of tubewell including all power and control cables of all equipment at pump house and OHT both.

1

60000

60000

... More
Control panel with IP-54 protection industrial grade for all equipment separate for control (24V and power equipments)

1

120000

120000

... More
Installation, commissioning & testing for tubewells

1

10000

10000

... More
PUMPING MACHINARY AND ACCESSORIES FOR CWR TO OHT ZONE-2 ( 200 KL )

-

-

-

... More
SITC of Vertical type self-water lubricated statically, dynamically, hydraulically balanced turbine pump capable of discharging at the following duty condition as given below due to all causes with surface discharge head confirming to IS:1710 and as amended as on date with accessories as per IS 5120/1977(Reconfirmed 2011) and as amended thereafter to suit the site condition.The Pump Bowl assembly and casing shall be CI IS 210 FG: 260 with suitable coating inside casing of 500 DFT, suitable for protection against corroision,erosion and prevent oxidation.Impeller and Wearing / Neckring shall be Duplex stainless steel CD4MCu (Chromium-24.5% minimum,Carbon 0.04% ) as per ASTM A890 GrlA or DIN 1.4474-EN 10088, Hardness 220-260 BHN,pump shaft-Stainless steel AISI 410, pumps and line shaft sleeve - stainless steel with ceremic coating 700 BHN,Strainer-SS 304,coupling between pump ang motor - Flexible pin bush type and bearings shall be Anti friction L-10 with 60000 Hrs life at 1450 rpm. 6 mtr/suitable length column assembly, with vertical hollow shaft. Squirrel cage induction motor(IS:126152011/IEC 60034-1) suitable for the above pump continuous rated TEFC IP-55 with Class 'F' insulation for operation in AC, three Phase/50 HZ (±5%), 415V (±10%), running with a speed of pump. Capacity as follows :-

-

-

-

... More
800LPM, 15.0 HP, 35m Head

2

536762

1073525.06

... More
SITC of 100mm Main piping complete with suitable size and quantity required for delivery side and 100mm common Header upto 1 m. outside the pump house along with 100 x 100 x 100 mm A/F Tee, 100 mm CI D/F 90 bend, Enlargers, 100 mm blind flange, D/F Pipes suitable size all necessary nuts, bolts, rubber packing, M.S Support for pipe and dismantling joints etc. complete in all respect as per site conditions suitable for above pumping plants.

1

95950

95950

... More
SITC of Motor operated actuator with sluice valve :- Supply of DI/DF sluice valve with Electrically integrated actuater (Totally enclosed, weather-proof and dust proof construction with IP-67, protection class suitable for installation in any position without lubrication, leakage or other operational difficulty with special grease filled gear box and suitable for manual operation for emergency which will automatically dis-engage on restoration of power to motor and with 10 watt single phase space heater and continuous local mechanical position indicator and individually replaceable counter gear assembly and with two torque and four limit switches with S.S. flap and operated with gear driven cams and of rating 250 Volt, 5 Amp, AC/DC, torque switch dial and with TEFC squirrel cage induction) operated suitable to SCADA operation sluice valve having body door cover of graded in cast iron to IS:210 Gr.Fg.260 body and door rings of SS ASTM A743 Gr.CF8 and bearing block of leaded tin bronze to IS:318 Gr.LTB2 hinge pin of stainless steel AISI:431.Valves generally conform to IS:5312.Flanges to be drilled as per IS:1538 Part-IV &VI. Valves are suitable for hydrostatic test pressure of 10Kg./Cm2 for seat and 15Kg./Cm2 for body(PN-1.0) of following sizes

-

-

-

... More
Valve actuator of size 100mm for pumps

2

119937

239875

... More
Valve actuator of size 100mm for common header

1

119937

119937.5

... More
Valve actuator of size 150mm at CWR Inlet

1

119937

119937.5

... More
SITC of Non return valve :- Supply of DI/DF Single Door/ Multi Door Non return/reflux valve conforming to IS:5312/2003(part I & II) PN-1.0 to be fixed after pumps for 90% fast closing & 10% slow closing .

-

-

-

... More
100 mm Dia for pumps

2

25410

50820.88

... More
100 mm Dia for common header

1

25410

25410.44

... More
SITC of CE/UL Certified Electromagnetic flow meter :- Supply of CE/UL Full BorecElectromagnetic Flow Meter of approved make of following dia and specifications complete: Media : Water (Raw/ Chlorinated) , Pressure : up to 1.0 MPa, Process temp: - 50 deg C, Flow/Meter Tube : SS 304, Electrode : SS AISI 316L / Hastelloy C276/ Tantalum, Lining Material : Hard Rubber/ Neoprene / Poly-urethane (PU) , Flange : SS / CS, Flange Standard & Rating : ANSI 150, Coil housing : SS AISI 304/ Carbon Steel/ Die Càst Aluminium, with anticorrosive paint & provide completely sealed (leak proof) construction as per requirement ‘of IEC 60529, Accuracy : + 0.5 % M.V. velocity 0.3 to 10 m/s, Transmitter/ signa convertor Enclosure : Die Cast Aluminium, Power Supply : 80-240 V AC - 5OHz, Output 1 : 4-20 mA, Output 2: Pulse, Communication Output : RS 485/ Heart, Display Type : LCD/ LED Display, Cable Entry : M20 X 1.5, Provision of RAM/PROM to store calibration and configuration parameters and totalizer value during power failure, Protection category- IP 68 for sensor (flow tube) and IP 67 for transmitter/ convertor, including Surge Arrester, cable.

-

-

-

... More
Electromagnetic flow meter of size 100mm for common header

1

95950

95950

... More
Electromagnetic flow meter of size 150mm at CWR Inlet

1

143925

143925

... More
SITC OF ELECTRICAL ITEMS:-

-

-

-

... More
Supply & laying of 1.1KV grade XLPE insulated unarmured multi strand copper conductor cable of 3C x 10 sq.mm from control Panel to respective Motors with lugs etc. (copper conductor should be electrlytic grade copper, purity 99.97% ISI marked asper IS:1554 P-I / IS :7098 P I)

50

799

39963.2

... More
SITC OF MOTOR CONTROL CENTER (MCC) PANEL :- Single front, Indoor & floor mounted,cubical type Panel factory fabricated (2 mm thick for sructure, 1.6mm thick for door,covers shrouds and Gland Plate-3 mm thick) CRCA sheet duly power coated dust and vermin proof IP-54 /IS:2147, considered Earth Bus-Bar-GI Strip compitable to SCADA operation with RS485 Port consisting of INCOMING SECTION 100A, 50KA, TPN, MCCB microprocessor baseed (O/C,S/C) release - 1 No , Spreader Links & Extended ROH for - 1 No, 3 Phase Digital Multifunction Meter - 1 No, Digital Voltmeter 0-500V - 1 No, Digital Ammeter 0-400A - 1 Nos, CT For meter Resin Cast CL-1400A/5A,15VA - 3 Nos, Phase indication light LED type 220V AC - 1 Set, Control MCB SP 6A ,10KA ABB - 3 Nos, CT Shorting Terminal - 4 Nos, Neutral Link - 1 No. OUTGOING SECTION 50 A, 50KA, TPN, MCCB microprocessor based (O/C,S/C) RELEASE - 3 No, Spreader Links & Extended ROH for MCCB - 3 Nos., 63A TPN MCCB 35KA - 2 Nos. Terminal 63A

1

402500

402500.66

... More
SITC of Air Cooled Digital soft starter suitable for the LT motor offered for operation in AC three Phase 50Hz (+/- 5%), 415V(+/-10%) including line contactors suitable for next standard higher KW rating, Over & Under load protection, short circuit & single phasing protection with frequency meter, Ammeter, Voltmeter, indicating lamp 6Nos, LED ON/OFF type and Start /Stop push button and Instrument Fuses, suitable to SCADA operation with RS485 Port rating capacity 15 HP / 11 KW

2

67165

134330

... More
SITC of microprocessor based three phase sensing power factor correction relay panel , IEC / EN 61000-6- (2&4) having 3 CT sensing, sensitivity up to 50 milli amp secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, communication interface with RS 485, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR rating capacity of 13KVAR

1

49449

49449.75

... More
SITC of Servo Controlled Automatic Voltage stabilizer suitable for out put voltage of 415 Volt +/-1%, 3 Ph, 50 Hz, with copper wound transformer (air/oil cooled) . The stabilizer shall function satisfactorily even if incoming supply is unbalanced between phases within range of 10%. The stabilizer should be constructed in cubical box, with bi- directional wheels for easy handling, necessary monitors and user's controls on front panel such as indication, alarm, volt meter and selector switch for measuring input and out put voltage, Auto/Manual selector switch, Raise/Low push buttons etc. Suitable capacity termination strips and bus bars for incoming and out going cable should be provided. All three phases shall be independently monitored and corrected (Operating voltage 240V - 500V), 415 volt, 3Phase, 50Hz -- 40 KVA with changeover switch.

1

168872

168872

... More
SITC of Auto Phase reversal unit with inbuilt time delay & enclosure ( confirm to IEC:60947-1 & IEC:60947-b-1)

-

-

-

... More
100 Amp Rating

1

43177

43177.5

... More
SITC of CE/UL Certified level transmitter for Intake well :- Supply of CE/UL cirtified of Radar level transmitter CE marked with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output-4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Range- 0 to …30... mtrs Accuracy - +/- 0.25% of Full Scale or better Enclosure- IP 68

-

-

-

... More
CE/UL Certified level transmitter for CWR

1

115140

115140

... More
SITC of CE/UL Certified Pressure transmitter for pumps and common header :- Supply of CE/UL Certified pressure transmitter CE markd with following technical parameters and Interfacing with PLC panel including mounting arrangement. Output 4-20 mA / HART Power supply - 24V DC ext. Display - 4" LED Accuracy - +/- 0.1 % of full scale or better Enclosure- IP 68

-

-

-

... More
CE/UL Certified Pressure transmitter for pumps

2

47975

95950

... More
CE/UL Certified Pressure transmitter for Common Header.

1

47975

47975

... More
SITC of Electro Mechanical type Chemical dosing system 0 to 6 LPH capacity on working pressure 4kg/cm2 to feed Sodium hypo chloride complete set with 100 Litre solution tank. ( Competible to SCADA )

1

71962

71962.5

... More
SITC of Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required according to latest IS:3043 Supplying and laying 50 mm X 6 mm G.I. strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)

1

143925

143925

... More
SITC of 3Ton capacity hand operated over head Travelling (HOT) crane suitable for a span upto 6 Mtrs, and travel length upto 10 Mtrs. with clear lift upto 6 M including gear type chain pulley block and geared Travelling trolley complete with all accessories including girder

1

359374

359374.97

... More
SITC Rubber mats for electrical purpose as per IS:5424-1969, plain/chequered (1mX2m) - 10mm thickness

5

2820

14104.65

... More
Supply & fixing of Cable trench Chequerred plate

500

172

86355

... More
Supply and fixing of Fire fighting equipments 4.5 Kg such as four nos. fire extinguishers ABC type, one set sand bucket with stand and grouting at site and one set Al strong plate and board.

4

6080

24321.41

... More
SITC of Internal & External electrification of CWR :-

-

-

-

... More
Indoor Lighting

-

-

-

... More
Surface Mounting

-

-

-

... More
Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non - yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection BIS certified isolated driver having efficiency 85%, with Short & Open circuit protection and in compliance to IEC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt, THD 10 % , p. f.≥ 0.95,CRI 80 , life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000° / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard

-

-

-

... More
Suspended Mounting / Surface Mounting

-

-

-

... More
36W LED light fixture 2'×2' with acrylic / prismatic front cover.

6

2502

15014.26

... More
Fans

-

-

-

... More
Providing & Fixing of ISO Certified company made BEE Star rated copper wounded double ball bearing capacitor start, aluminium body & Metallic blade ceiling fan as per PWD specification for electrical Works, Conform to all the performance requirements laid down in IS:374-2019 including all amendments, as applicable; & Carry BIS licensing (i.e. ISI marking) or Quality Certification such as ISO - 9001 or above. with down rod up to 30 cm with secondary support safety cable ( steel wire ) , cotter pin with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc.) as required.

-

-

-

... More
1200 mm Sweep BEE 3 Star rated (service value =5.0 to 5.5 )

2

1551

3103.02

... More
Fixing of fresh air fan/exhaust fan up to size of 300 mm on ply/ poly board of 6.0 mm in existing window frame including cost of ply, cutting of hole in ply. Nut bolts etc. as required.

2

132

264.82

... More
Installation, testing and Commissioning of ceiling fan (any size) including wiring the down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required.

-

-

-

... More
with regulator

2

50

101.71

... More
Providing & Fixing of Heavy duty capacitor start, copper wind Double ball bearing 900/1400 RPM single phase Exhaust fan as per PWD specification for electrical Works, conforming to IS:2312 ISI marked in existing opening including making connections testing etc. as required.

-

-

-

... More
450mm sweep (900/1400 RPM)

2

4103

8207.56

... More
Outdoor Lighting

-

-

-

... More
Supply and fixing of all in one solar LED light fixturewith integrated high efficient Monocrystalline panel with Lithium (LiFePO4) Ferro Phosphate Battary wih BIS approved make. Luminaire should be secondary optic lences for better distribution with delivered efficacy of 100 lumen per watt. Bidder shall have in house R & D Laboratory which is recognised by Ministry of Science & Technology Department , Govt of India/NABL.Bidder shall in house pole and luminaire manufacturing facility.Luminaire can be supplied with hybrid switch along with indicator to understand the source of power ( either from solar or AC supply).All the above should be integrated and should 1 system.

-

-

-

... More
Compact Solar LED Street Light- 60W(MONO) 18V / 12.8V 27Ah /40W

5

44014

220070.92

... More
Complete wiring of Pump house, HT & LT room with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.

1

56610

56610.5

... More
AUTOMATION FOR CWR-2

-

-

-

... More
CE & UL Certified PLC/RTU with redudant CPU & Power supply in IP 54 enclosure suitable to Communicate with GSM based modem unit with redudant CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.

1

550000

550000

... More
GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.

1

30000

30000

... More
CE/UL Certified Intelligent energy meters

1

25000

25000

... More
CE/UL Certified Surge protector for control panel

1

15000

15000

... More
CE/UL Certified 3 KVA UPS with batteries as per technical bid documents

1

150000

150000

... More
CE/UL Certified 7" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.

1

30000

30000

... More
Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments

1

150000

150000

... More
Turbidity Analyzer at CWR

1

135000

135000

... More
PH Analyzer

1

135000

135000

... More
Chlorine Analyzer

1

270000

270000

... More
Cable

-

-

-

... More
(i) Complete cabling upto 3 Pumps

1

80000

80000

... More
Security Survelliance IP Camera with recorder (optional)

2

20000

40000

... More
Installation, commissioning & testing

1

20000

20000

... More
AUTOMATION FOR DMA AGAINST ZONE-1,2

-

-

-

... More
CE & UL Certified PLC/RTU in IP 54 enclosure suitable to Communicate with GSM based modem unit with CPU & Power Supply with analog & digital parameter & features as specified for each ZPS/OHT to store and transmit data on GSM backbone, RTU/PLC designed with logic to transfer data at multiple stations with control panel as specified in tender technical specification.

4

275000

1100000

... More
GSM / GPRS based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories including with signal enhancer antanna made for pumping plant internet charges as specified in tender technical specification.

4

30000

120000

... More
CE/UL Certified Intelligent energy meters

4

25000

100000

... More
CE/UL Certified Surge protector for control panel

4

15000

60000

... More
CE/UL Certified 1 KVA UPS with batteries as per technical bid documents

4

50000

200000

... More
CE/UL Certified 7" touch screen suitable for communication with PLC/RTU for local display & control of process parameters.

4

30000

120000

... More
Control Panel with IP-54 Protection, industrial grade for all equipment. Separate for control (24V) and power equipments

4

150000

600000

... More
Cable

-

-

-

... More
(i) Complete cabling

4

80000

320000

... More
Security Survelliance IP Camera with recorder (optional)

8

20000

160000

... More
Installation, commissioning & testing

4

20000

80000

... More
Rehabilitation of 2.90 MLD WTP

-

-

-

... More
Flash Mixer - Supply , Installation ,Testing and Commissioning of 1 No Agitator for Flash Mixer with gear box and motor, with all necessary arrangements including PAC dosing tank complete in all respect.

1

191900

191900

... More
Filter Back Wash System

-

-

-

... More
Air Blowers- Supply , Installation ,Testing and Commissioning of 720 Cum/Hr at 0.35 kg/cm² pressure coupled with suitable capacity 415V 3 phase 50 Hz induction motorwith base frame,suction air filter,silencer,pressure relief valve,delivery non return valve, starter, Control Panel, pressure sensor, Power Wiring and Main Piping Valve etc (1working+ 1 standby) including all necessary arrangements. (System should be SCADA compatible.)

2

518130

1036260

... More
Back Wash Pumps-Supply , Installation ,Testing and Commissioning of Back Wash water filling Pumps with Motor of 600 lpm, 20 mtr head capacity including soft starter, control panel, power wiring and main piping and valves complete in all respect. (1working+ 1 standby). System should be SCADA compatible.

2

239875

479750

... More
Supply , Installation ,Testing and Commissioning of dust and vermin proof LT panel consisting of one no. incoming of 200 Amp MCCB and 6 Nos. (5+1) outgoing MCCB Mirco processor based complete with power wiring, Ampire meter, Voltmeter & capacitor of suitable capacity for individual motors

1

531342

531342.32

... More
Supply and laying of 3.5 core 95 Sq.mm. Armoured Aluminum Conductor Cable from Starter to respective motors with lugs etc.

150

1068

160332.45

... More
Supply , Installation ,Testing and Commissioning of Vaccum feed Gas Chlorinator system with all accessories and making connection with existing pipeline required including supply & installation of ejector unit , vaccum chlorination unit,trunnion roller support, auxiliary container valve,flexible copper connector, manifold valve,tonner manifold pipes,chlorine pressure gauge, isolation valve, gas filter, pressure reducing valve, chlorine gas pipe with fittings, diffuser, lifting beam, load indicator, 25 NB PP diaphram valve,on injector inlet & outlet, 32 OD UPVC pipe for chlorine solution, 25NB GM gate valve on pump suction and delivery, 25 NB GM "Y" type strainer on pump suction,25NB GM check valve on pump delivery, pressure gauge with isolated valve on pump delivery and chlorine Booster pump with motor of required capacity for Post- Chlorination system of 1.0 Kg/Hr Gaseous Chlorination Plant (1working+ 1 standby) complete in all respect

2

266261

532522.5

... More
Supply , Installation ,Testing and Commissioning of 100 kg Chlorine Gas Tonner complete in all respect.

4

31663

126654

... More
SITC of Chlorine leak absorption system complete in all respect withfollowing items- 1-Chlorine neutralisation FRP tank with necess fittings. 2-FRP Tonner half hood. 3- Blower with motor 4-PP chemical pump for circulating caustic with piping and valves. 5- Caustic flakes 6- Iterconnecting piping 7- Appropriate capacity of starter for motors 8- civil materials for foundation 9- Leak detector with two sensors, hooter etc 10- Complete automation of chlorine absorption system

1

1252147

1252147.5

... More
Supply of saefty equipments related to chlorination system e.g. breathing apparatus, eye wash, shower etc complete in all respect

1

71962

71962.5

... More
INTERNAL AND EXTERNAL ELECTRIFICATION FOR EXISTING 2.90 MLD WTP

-

-

-

... More
Internal and External Electrification

-

-

-

... More
Outdoor Lighting

-

-

-

... More
Supply installation tesling & Commissioning of IS0 certifted company made high mast lighting system (as per PLG 07 of ILP UK technical report no 7 of ILE UK /IS:875 Part-1 - 2015//BSEN10025/and IS:2062 )consisting of totally hot dip galvanised by single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm (excluding luminares), mast head frame assembly with full cover, including 1 No. LED 15 Watts aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement ( winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, S.S. ropes (AISI 316, 7 / 19 costruction), EPR insulated PCP sheathed trailing cable, including outdoor type control panel for auto on / off, reverse / forward motor operation and CC foundation of M - 25 grade complete as required as per IS 456/IS 2911. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal (Octogonal) section, telescopic jointed and welding as per BS 5135 and also provide test certificate for wind tunnel test for High mast fixtures. complete in all respect.

-

-

-

... More
12.5 Mtr. HM (in 2 Section)

1

145338

145338.34

... More
Providing & Fixing of IK07 IP-66 protected high power LED flood light system with Pressure diecast aluminium housing LM6/ ADC12 material, toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED lamps . Integrated driver must be potted & has a unique BIS R number shall be high efficiency having efficiency more than 85 % and in compliance to BIS certified and T.C. certificate. The System level Luminaire efficacy =120 Im/ wt with High Power LEDs is to be used . LED driver Input Voltage AC 120 to 270 V AC with High voltage Cutoff @=300 V AC and Auto resetting Safety . Input Frequency 50Hz‡3%, Power Factor 0.95 ,driver Efficiency 85% . THD(I) 10% , driver current 1000mA shown in LM79 report. driver should be Phase to phase protection of 440 V for 4 Hrs. Electrical Connector Must be provided, Surge Protection Min =4KV internal and 10KV external, System life of 30000 Burning hours with 70% of Initial Lumens maintained, color Rendering Index 70 and CCT 5700K + 1355K, Driver current 1000mA shown in LM79 report. Manufactures Word Mark/Name Engraved/Embossing/Screen printing on die cast housing to allow traceability/authenticity. Fixture -shall be IS 10322 Complianced and also provide test Certificate/ report with liable warranty of product/accessories.

-

-

-

... More
High Power LED Flood Light 200W

8

21249

169992.7

... More
Indoor Lighting

-

-

-

... More
Providing & Fixing of IP40 LED Surface/ Recessed / suspended mounting Mid power SMD type LED Light fixture made from CRCA sheet steel housing, high purity / transmisivity UV stabilized Non -yellowish diffuser for uniform light distribution. High efficiency with 2.5 KV internal/external surge protection B|S certified isolated driver having efficiency 85% , with Short & Open circuit protection and in compliance to IC standards (Integral with light fixture). System lumen efficacy of ≥ 120 Im/Watt ,THD 10 % , p.f.0.95,CRI 80 . life time of minimum 50000 Burning Hours with , 70% of intial Lumen maintaned till life ends , CCT 3000°K / 4000°K / 5700°K / 16000°K / 6500°K (As per ANSI Bin) , maximum power consumption should not more than the specified rating and Fixture shall be of BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing and also provide test certificate of LED Fixtures from NABL.

-

-

-

... More
36 W LED light Fixture 2' x 2' with acrylic / prismatic front cover.

4

2502

10009.5

... More
Complete wiring of Pump house with 1.5 sqmm and 2.5 sqmm with multistarned copper conductor 1.1 KV with required 6A,16A switches,sockets,MCCB etc.

1

14392

14392.5

... More
HOT of 3 Ton capacity, 10 mtr span , 12 mtr lift with traveling trolly for Chlorination system Complete in all respect.

1

359374

359374.97

... More
Painting works

1

28785

28785

... More
Automation For 2.90 MLD WTP

-

-

-

... More
CE & UL Certified PLC/RTU with redundantCPU & Power supplyin IP 54 enclose suitable to Communicate with GSM based moden unit with redudant CPU & Power supply with annlog & digital parameter & featuers as specified, for each WTP to store and transmit data on GSM backbone, RTU/PLC desgined with logic to transfer data at multiple stations as specified in tender technical specifications.

1

550000

550000

... More
G.S.M./G.P.R.S. based wireless communication with 4G modem for RTU/PLC Capable to transfer & gather data from remote sites to control stations all accessories include with signal enhancer antenna made for pumping plant internet charges as specified in tender technical specification .

1

30000

30000

... More
Intelligent energy meters

1

25000

25000

... More
CE/UL Certified 3 KVA UPS with batteries as per technical bid documents

1

150000

150000

... More
Auto Phase reversal unit / Automatic switch with inbuilt the delay & enclosure (Confirms to IEC: 60947-1 & IEC: 60947-6-1) of followint rating:

-

-

-

... More
200 Amp.

1

120000

120000

... More
Motor operated Actuators with Sulice Valves of size 200 mm for inlet line to WTP.

1

150000

150000

... More
Electromagnetic flow meters 200 mm dia for raw water inlet line.

1

190000

190000

... More
Electrically Actuated Valve of size 250mm at inlet of hopper

2

190000

380000

... More
Settling tanks-Outlet- Electrically Actuated Valve (size 200 mm)

2

150000

300000

... More
Back Wash Water Filling Pumps inlet-Electrically Actuated Valve (size 200 mm)

2

150000

300000

... More
Back Wash Water Filling Pumps outlet-Electrically Actuated Valve (size 200 mm)

2

150000

300000

... More
Back Wash Water Filling Pumps common header-Electromagnetic flow meter (size 200 mm)

1

190000

190000

... More
Filter Bed-Back Wash inlet- Electrically Actuated Valve (size 300 mm)

2

215000

430000

... More
Filter Bed-Back Wash outlet- Electrically Actuated Valve (size 250 mm)

2

190000

380000

... More
Filter Bed-Clear Water outlet- Electrically Actuated Valve (size 300 mm)

2

215000

430000

... More
Clear Water Electromagnetic Flow Meter of size 300 mm

1

260000

260000

... More
Filter outlet inspection box-Rate of Flow Transmitter( ROFT)

2

125000

250000

... More
Loss of Head Transmitter(LOHT)

2

125000

250000

... More
Wash Water tank level- Ultrasonic Level Sensor

1

120000

120000

... More
Clear Water Channel-Turbidity Sensor with Analyzer

1

315000

315000

... More
Clear Water Channel-pH Sensor with Analyzer

1

135000

135000

... More
Clear Water Sump- TDS Analyser

1

135000

135000

... More
Complete cabling

1

100000

100000

... More
Security Survelliance IP Camera

4

20000

80000

... More
Installation of all equipments, power wiring of Electrical equipments and commissioning of the equipments.

1

300000

300000

... More
Trial and run for Zone-1,2 ( without electricity )

1

567471

567471.53



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.