Pashchimanchal Vidyut Vitran Nigam Limited Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Pashchimanchal Vidyut Vitran Nigam Limited - PVVNL Tender
Civil And Construction
Road Construction
Eprocure
Opening Date23 Oct 2024
Closing Soon21 Nov 2024
Tender AmountRefer Documents
Costs
EMD
₹ 25,830Document Cost
₹ 3,540Tender Fee
Refer Documents
Summary
E-tender No. 44/2024-25, Eudc-ii Noida
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_PVVNL_967869_1Tender No
E-Tender No. 44/2024-25, EUDC-II NoidaTender Authority
Pashchimanchal Vidyut Vitran Nigam Limited ViewPurchaser Address
-Website
http://http://pvvnl.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
ST POLE 11MTR
4
-
-
STONE PAD
34
-
-
DOG CONDUCTOR
4750
-
-
11KV T CHANNEL
4
-
-
MS TOP CHANNEL
3
-
-
MS DROPPER CHANNEL
6
-
-
11KV DISC WITH FITTINGS
18
-
-
11 KV PIN INSULATOR WITH PIN
96
-
-
EARTHING COMPLETE
34
-
-
STAY SET COMPLETE WITH CONCRETING
10
-
-
11KV CROSS ARM
30
-
-
11KV XLPE CABLE 3X185
1120
-
-
11KV O/D KIT
9
-
-
11KV VCB O/G 600/300/5A
1
-
-
BASE ANGLE FOR CT/PT
2
-
-
11KV O/D CTPT UNIT
1
-
-
11KV I/D KIT 3X185
2
-
-
Errection of above Following material and Supply and errection of the DE-CENTRALISED material for completing the works as per RESPO.
-
-
-
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 65x8mm, G.I.Nut bolt & washer, P.G.Clamp, Stone Pad, Al. Binding wire, 'E' bracket 75x10mm, and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as any fabrication work if required & fixing of cross bracing sets 4.3mtr long, from G.I.Angle 65x65x6mm. The work includes cutting holes and providing G.I.Bolt of 16x40mm size, in the middle of the cross bracing with 01No. spring washer of proper size as per drawing/ as per schedule.
Double Pole Structures
(a) ST POLE 11MTR LONG
2
-
-
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required.
Single Pole
(a) PCC POLE- 8.5MTR LONG
30
-
-
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming.
Single Pole and Double Pole
(a) ST 11MTR LONG AND PCC POLE 8.5MTR
34
-
-
INSTALLATION AND FIXING OF O/D CTPT UNIT AT POLE WITH COMPLETE WORK IN ALL RESPECT.
1
-
-
FIXING OF BASE ANGLE AT POLE FOR CTPT, COMPLETE WORK IN ALL RESPECT.
2
-
-
FIXING OF PIN INSULATOR WITH PIN, COMPLETE WORK IN ALL RESPECT.
96
-
-
FIXING OF TOP CHANNEL AS PER SITE REQUIREMENT.
3
-
-
FIXING OF DROPPER CHANNEL AS PER SITE REQUIREMENT.
6
-
-
FIXING OF STONE PAD AS PER SITE REQUIREMENT.
34
-
-
FIXING OF T- CHANNEL AS PER SITE REQUIREMENT.
4
-
-
FIXING OF CROSS ARM AS PER SITE REQUIREMENT.
30
-
-
FIXING OF DISC INSULATOR WITH FITTINGS AS PER SITE REQUIREMENT.
18
-
-
INSTALLATION, FIXING AND COMMISSIONING OF NEW 11KV O/G VCB 600/300/5A WITH MAKING OF FOUNDATION AND COMPLETE WORK AND CONNECTIONS IN ALL RESPECT.
1
-
-
Supply of 160mm OD PN-4-PE-80 Grade UV Stabilized HDPE Pipe.(PVVNL GTP APPROVED)
1000
-
-
Drilling of dia 220 mm in two parallel bores for Double Curcuit by trenchless method by horizontal boring machine at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level with complete work in all respect as per RESPO.
1000
-
-
Laying of HDPE Pipe PE-80, PN-4, DN-160mm dia by HDD trenchless method for 11KV, 3x185sq.mm XLPE cable as per site requirement. (PVVNL GTP APPROVED HDPE PIPE SHALL BE SUPPLIED WITH INSPECTION.)
1000
-
-
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. in HDPE Pipe dia after digging HDD trenchless method boring including complete connections at both ends after providing and crimping of lugs of proper size for completion of work. as per site requirement.
1000
-
-
Digging of pits of size 4 mtr x 4 mtr x 1.5 mtr for cable loop and making risers at double pole and re-filling of pits in proper manner with required material at kacha/pakka and hot mix road. (All Work and material in the scope of contractor)
9
-
-
Laying of 11 KV 3X185 Sq.mm XLPE Cable in the air on cable Riser Double Pole, existing trench cable trench, nala x-ing & G.I.Pipe and making connection complete at both ends.
120
-
-
Preparation and Fixing of 11 KV Power Cable ends:
Making and Fixing of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
9
-
-
Preparation and Fixing of 11 KV Power Cable ends:
Making and Fixing of 11 KV XLPE Heat shrinkable Indoor Kit suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
2
-
-
Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting.
34
-
-
Fixing, tightening & nozzling of stay set complete with wireand stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 11KV and Stay Clamps with Grouting of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc.
10
-
-
Providing and Fixing of GI Pipe 6" Dia as per site requirement.
12
-
-
Providing and Fixing of Danger Board as per site requirement.
34
-
-
Providing and Fixing of Ms Holding Clamp as per site requirement.
55
-
-
PROVIDING AND FIXING OF F BRACKET AS PER REQUIREMENT.
34
-
-
PROVIDING AND FIXING OF NUMBER PLATE AS PER REQUIREMENT.
34
-
-
Providing and Fixing of MS Nut Bolt as per site requirement.
55
-
-
Laying, spreading, lifting and final sagging of 3 OR 4 phases ACSR Dog conductor in accordance with Line chart includidng binding and fixing of all accessories in 03Nos OR 04 Nos. Conductor in parallel as per site requirement.
4750
-
-
Road Cutting and Road Restoration Charges for the above work.
1
-
-
S/S NTPC Road Dadri Under Proposed New 11 KV Industrial Feeder
-
-
-
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 3 to 18
-
-
-
PCC POLE 8.5MTR
20
-
-
ST POLE 11MTR
4
-
-
STONE PAD
24
-
-
DOG CONDUCTOR
1483
-
-
11KV T CHANNEL
2
-
-
MS TOP CHANNEL
4
-
-
MS DROPPER CHANNEL
8
-
-
11KV DISC WITH FITTINGS
12
-
-
11 KV PIN INSULATOR WITH PIN
70
-
-
EARTHING COMPLETE
24
-
-
STAY SET COMPLETE WITH CONCRETING
6
-
-
11KV CROSS ARM
18
-
-
11KV XLPE CABLE 3X185
1060
-
-
11KV I/D KIT 3X185
2
-
-
11KV O/D KIT
16
-
-
11KV VCB O/G 600/300/5A
1
-
-
BASE ANGLE FOR CT/PT
2
-
-
11KV O/D CTPT UNIT
1
-
-
Errection of above Following material and Supply and errection of the DE-CENTRALISED material for completing the works as per RESPO.
-
-
-
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 65x8mm, G.I.Nut bolt & washer, P.G.Clamp, Stone Pad, Al. Binding wire, 'E' bracket 75x10mm, and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as any fabrication work if required & fixing of cross bracing sets 4.3mtr long, from G.I.Angle 65x65x6mm. The work includes cutting holes and providing G.I.Bolt of 16x40mm size, in the middle of the cross bracing with 01No. spring washer of proper size as per drawing/ as per schedule.
Double Pole Structures
(a) ST POLE 11MTR LONG
2
-
-
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required.
Single Pole
(a) PCC POLE- 8.5MTR LONG
20
-
-
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming.
Single Pole and Double Pole
(a) ST 11MTR LONG AND PCC POLE 8.5MTR
24
-
-
INSTALLATION AND FIXING OF O/D CTPT UNIT AT POLE WITH COMPLETE WORK IN ALL RESPECT.
1
-
-
FIXING OF BASE ANGLE AT POLE FOR CTPT, COMPLETE WORK IN ALL RESPECT.
2
-
-
FIXING OF PIN INSULATOR WITH PIN, COMPLETE WORK IN ALL RESPECT.
70
-
-
FIXING OF TOP CHANNEL AS PER SITE REQUIREMENT.
4
-
-
FIXING OF DROPPER CHANNEL AS PER SITE REQUIREMENT.
8
-
-
FIXING OF STONE PAD AS PER SITE REQUIREMENT.
24
-
-
FIXING OF T- CHANNEL AS PER SITE REQUIREMENT.
2
-
-
FIXING OF CROSS ARM AS PER SITE REQUIREMENT.
18
-
-
FIXING OF DISC INSULATOR WITH FITTINGS AS PER SITE REQUIREMENT.
12
-
-
INSTALLATION, FIXING AND COMMISSIONING OF NEW 11KV O/G VCB 600/300/5A WITH MAKING OF FOUNDATION AND COMPLETE WORK AND CONNECTIONS IN ALL RESPECT.
1
-
-
Supply of 160mm OD PN-4-PE-80 Grade UV Stabilized HDPE Pipe.(PVVNL GTP APPROVED)
840
-
-
Drilling of dia 220 mm in two parallel bores for Double Curcuit by trenchless method by horizontal boring machine at a depth of 1.50 mtrs to 2.50 mtrs. (as requirement at site) below the ground level with complete work in all respect as per RESPO.
840
-
-
Laying of HDPE Pipe PE-80, PN-4, DN-160mm dia by HDD trenchless method for 11KV, 3x185sq.mm XLPE cable as per site requirement. (PVVNL GTP APPROVED HDPE PIPE SHALL BE SUPPLIED WITH INSPECTION.)
840
-
-
Laying and commissiong of 11KV 3x185sqmm XLPE Cable Double Ckt. in HDPE Pipe dia after digging HDD trenchless method boring including complete connections at both ends after providing and crimping of lugs of proper size for completion of work. as per site requirement.
840
-
-
Digging of pits of size 4 mtr x 4 mtr x 1.5 mtr for cable loop and making risers at double pole and re-filling of pits in proper manner with required material at kacha/pakka and hot mix road. (All Work and material in the scope of contractor)
16
-
-
Laying of 11 KV 3X185 Sq.mm XLPE Cable in the air on cable Riser Double Pole, existing trench cable trench, nala x-ing & G.I.Pipe and making connection complete at both ends.
220
-
-
Preparation and Fixing of 11 KV Power Cable ends:
Making and Fixing of 11 KV XLPE Heat shrinkable outdoor jointing kits suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
16
-
-
Preparation and Fixing of 11 KV Power Cable ends:
Making and Fixing of 11 KV XLPE Heat shrinkable Indoor Kit suitable for 3x185sqmm XLPE Cable after duly plumbing and taping of cable, providing, fixing and crimping of proper size good quality lugs with complete connention in all respect.
2
-
-
Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting.
24
-
-
Fixing, tightening & nozzling of stay set complete with wireand stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 11KV and Stay Clamps with Grouting of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc.
6
-
-
Providing and Fixing of GI Pipe 6" Dia as per site requirement.
12
-
-
Providing and Fixing of Danger Board as per site requirement.
24
-
-
Providing and Fixing of Ms Holding Clamp as per site requirement.
55
-
-
PROVIDING AND FIXING OF F BRACKET AS PER REQUIREMENT.
20
-
-
PROVIDING AND FIXING OF NUMBER PLATE AS PER REQUIREMENT.
24
-
-
Providing and Fixing of MS Nut Bolt as per site requirement.
35
-
-
Laying, spreading, lifting and final sagging of 3 OR 4 phases ACSR Dog conductor in accordance with Line chart includidng binding and fixing of all accessories in 03Nos OR 04 Nos. Conductor in parallel as per site requirement.
1483
-
-
Road Cutting and Road Restoration Charges for the above work.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%