If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
New Okhla Industrial Development Authority Tender
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date23 Aug 2024
Closing Date5 Sep 2024
Tender Amount₹ 62,31,260
Costs
EMD
₹ 1,24,700Document Cost
₹ 2,832Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_NOIDA_948578_1Tender No
22/SM (JAL)-I/ET/2024-25Tender Authority
New Okhla Industrial Development Authority ViewPurchaser Address
-Website
http://https://www.noidaauthorityonline.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Repairing existing AC/CI/DI water line i/c all required materials such as CID joints, rubber packing, nut & bolts, bailling out of water, all labour and T&P i/c cutting of pipe etc. complete work as per direction of E/I. (But exluciding cost of Excavation filling and M.S. Special) 4.01) 200 mm dia C.I.
13
51516
3962.8
250 mm dia C.I.
13
66315
5101.2
300 mm dia C.I.
14
90220
6444.3
350 mm dia C.I.
11
88523
8047.6
400 mm dia C.I.
12
121029
10085.8
Repairing of Existing PVC water line bailing out of water by / Beldar / Deisel Engine, P/F PVC coupler, CID joint etc. complete work as per direction of E/I (But Excluding cost of Excavation filling) 5.01) 90 mm dia
65
131768
2027.2
110 mm dia
55
119113
2165.7
140 mm dia
25
66555
2662.2
160 mm dia
18
52885
2938.1
200 mm dia
16
63643
3977.7
250 mm dia
11
58934
5357.7
P/L following size of Finolex makes PVC pipes 6 Kg/Cm2 with required PVC standard special confirming to IS codes with latest amendment and lowering the same trenches and laying true to alignment and gradient complete i/c the cost of cutting of pipes for making up to length and making joints i/c cost of socket, plstochem PV-85 pvc solvent cement complete. PVC pipe must be confirming to IS:4985-2000 with latest amendment. Make-Finolex Industries Ltd./Kisan/Superme Industries Ltd. (Rate As per Comparative Statement Per. Rm.) 6.01) 90 mm dia with coupler @ 6 Kg/Cm2 Pressure with i/c all PVC standard Specials
123.5
25823
209.1
110 mm dia with coupler @ 6 Kg/Cm2 Pressure with i/c all PVC standard Specials
110
32802
298.2
140 mm dia with coupler @ 6 Kg/Cm2 Pressure with i/c all PVC standard Specials
52.5
25877
492.9
160 mm dia with coupler @ 6 Kg/Cm2 Pressure with i/c all PVC standard Specials
39.6
24199
611.1
200 mm dia with coupler @ 6 Kg/Cm2 Pressure with i/c all PVC standard Specials
40
39844
996.1
250 mm dia with coupler @ 6 Kg/Cm2 Pressure with i/c all PVC standard Specials
27.5
42080
1530.2
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth consolidating each deposited layer by ramming & watering, lead upto 50 m and lift upto 1.5 m.
2337.21
256485
109.74
P/F M.S. specials such as Tee, Bend, Collars, Tapers, Gap pieces, including Flange Ends as required, Painting, Cutting, welding as per site requirement of MS pipe thickness etc complete in all respect as per direction of E/I.
15793.73
1186109
75.1
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
54.94
372565
6781.32
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : "1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size).
54.94
437820
7969.07
P/F Sluice Valve shall generally conform to IS 14846 with latest amendment, with length over flanged as per PD of IS 14846 corresponding to BS EN-558 / ISO 5752 Basic series 3 in CI construction having metal seating (IS 318 Gr. LTB 2). With comple component & material of construction following below:-
1 - Body / Door / Dome - Cast Iron IS 210 Gr. FC 260
2 - Spindle - Non rising: Stainless Steel AISI 410
3 - Body seat / Door face - Gun metal : IS 318 Gr. LTB 2 (rings to be press fitted and riveted: no screws allowed)
4 - Rivets - Soft annealed brass
5 - Spindle Nut - Gun metal : IS 318 Gr. LTB 2
6 - Stem Seal - Greased Hemp
7 - Fasteners - Carbon steel
8 - Flange Drilling - IS 1538 Table 4 & 6
9 - PN 1.0
10 - Accessories (400 mm and above) - Ball thrust bearings to be housed above the wet chamber ie. above the gland. Enclosed Spur Gear Box for ease of operation. Air Plug
11 - Painting / Coating - Inside & Outside epoxy liquid coated; DFT minimum 250 micron, shade RAL 5005 / 5015 (BLUE)
12 - Hydro-test-(Open Ended only) (Seat : 10/16 Kg/cm2; Body: 15 / 24 Kg/cm2
13 - Upto 600mm dia Mannual Operated & above 600mm Gear box
Make-Indian Valve Pvt. Ltd. (IVC) / Kirloskar Brothers Limited KIRLOSKAR) 11.01) 150 mm dia
1
24073
24073.6
200 mm dia
1
42038
42038.9
250 mm dia
1
54867
54867.2
300 mm dia
1
78362
78362.6
350 mm dia
1
129265
129265.2
400 mm dia
1
164886
164886.4
P/F Reflex Valve upto 600mm dia shall conform to IS 5312 Part-1 & above to IS 5312 Part-2 with latest amendment, Valves shall be in graded CI with metal to metal (IS 318 Gr. LTB 2) seating, preferably slanted (and not perpendicular) vis-a-vis horizontal axis; SS AISI 410 stub pins & slant seat design. with comple component & material of construction following below:-
1 - Body / Door / Dome - Cast Iron IS 210 Gr. FC 260
2 - Hinge pin (single door) / Stub pin (multidoor type) - SS AISI 410
3 - Seat & Face rings - Gun metal : IS 318 Gr. LTB 2 4 - Rivets - Soft annealed brass
5 - Fasteners - Carbon steel
6 - Flange Drilling - IS 1538 Table 4 & 6
7 - PN 1.0
8 - By - pass arrangement - Optional
9 - Painting / Coating - Inside & Outside epoxy liquid coated; DFT minimum 250 micron, shade RAL 5005 / 5015 (BLUE)
10 - Hydro-test Seat : Seat : 10/16 Kg/cm2; Body: 15 / 24 Kg/cm2
Make-Indian Valve Pvt. Ltd. (IVC) / Kirloskar Brothers Limited KIRLOSKAR) 12.01) 150 mm dia
1
17018
17018.2
200 mm dia
1
28662
28662.6
250 mm dia
1
45523
45523.8
300 mm dia
1
61284
61284.1
350 mm dia
1
107403
107403
400 mm dia
1
138082
138082.8
Repairing of sluice valve with the change of spendle (I.e. S.S. non megnated) flapper adjusting nut & bolts & rod & welding machining of body for fitting the flapper properly complete as per direction of E/I. Kirloskar make. 13.01) 150 mm dia
5
12155
2431
200 mm dia
6
17586
2931
250 mm dia
6
28974
4829
300 mm dia
3
19902
6634
350 mm dia
3
21621
7207
400 mm dia
1
12857
12857.4
Repairing of reflex valve with the change of flapper sheet i/c new lever, rubber sheet, MS ring, S.S.pin shaft & shaft rubber etc. complete Kirloskar make. 14.01) 150 mm dia
5
15130
3026
200 mm dia
5
15910
3182
250 mm dia
6
28669
4778.3
300 mm dia
3
19134
6378
350 mm dia
3
20973
6991
400 mm dia
1
12354
12354
Constructing masonry Chamber inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design : With common burnt clay F.P.S.(non modular) bricks of class designation 10.00. 15.01) 90 x 90 x 100 cm.
6
87006
14501.02
120 x 120 x 100 cm.
6
121006
20167.72
Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
1500
163440
108.96
Hiring of Diesel Engine (Including cst of Diesel, Lubricant & Operator)
50
12500
250
Hiring of Gas cutting Set With oxygen and LPG Running Time @ 6 Hrs.
5
9375
1875
Hiring of Welding Set Running Time @ 6 Hrs.
5
8250
1650
Charge of Generator (Including cost Service of operating staff, supply of lubricating oil and diesel also) DG Set / Generator 50 KVA
50
36415
728.3
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
276.45
39325
142.25
Evaluation Notes How It Works ?