Indian Institute Of Toxicology Research Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Indian Institute Of Toxicology Research - IITR Tender
Eprocure
Opening Date10 Feb 2022
Closing Date16 Feb 2022
Tender Amount₹ 30,61,133
Costs
EMD
₹ 61,223Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2022_CSIR_105277_1Bid Award Id
ViewTender No
IITR/EME-17(26)/2021Tender Authority
Indian Institute Of Toxicology Research ViewPurchaser Address
-Website
http://https://www.csir.res.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
SUPPLY/FIXING OF EXHAUST FAN 300MM
6
-
-
SUPPLY/FIXING OF MIRROR LIGHT
2
-
-
Supply & Fixing of 100*50mm PVC Trunking
230
-
-
SUPPLYING AND FIXING OF PVC DIVIDER 50 MM DEEP
200
-
-
SUPPLYING AND FIXING OF END CAP
30
-
-
SUPPLYING AND FIXING OF JOINTER 100MM
30
-
-
SUPPLYING AND FIXING OF INTERNAL ANGLE 100*50MM
30
-
-
SUPPLYING AND FIXING OF EXTERNAL ANGLE 100*50MM
30
-
-
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
170
-
-
Wiring for twin control light point with 1.5 sq mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit,2 way modular switch,modular plate,suitable GI box and earthing the point with 1.5 sq mm FRLS PVC insulated copper conductor single core cable etc as required.
4
-
-
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. A) 2 Pair
300
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. A) Telephone socket outlet/ RJ-11
20
-
-
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc. as required. A) 75 mm X 75 mm X 60 mm deep
10
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
-
-
-
15/16 A switch
10
-
-
6 pin 15/16 A socket outlet
10
-
-
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (ii)25mm
100
-
-
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (iii)32mm
60
-
-
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required. (i) 3x1.5 sq mm
100
-
-
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required. (ii) 3x2.5 sq mm
150
-
-
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required. (iii) 3x4 sq mm
2000
-
-
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed PVC conduit as required. (iii) 3x6 sq mm
600
-
-
Supplying and fixing 6 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (i) single pole
310
-
-
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
40
-
-
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as requid. (i) 125 Amp,16 KA,Tp,MCCB
13
-
-
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required). (i) 4 way (4+12), Double Door
4
-
-
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required). (ii) 8 way (4 + 24), Double door
9
-
-
Supply of 3.5Core x 95 sq m pvc insulated, pvc sheathed/XLPE aluminium conductor 1.1 KV grade armoured power cable.
40
-
-
Supply of 3.5Core x 50 sq m pvc insulated, pvc sheathed/XLPE aluminium conductor 1.1 KV grade armoured power cable.
200
-
-
Supply of 3.5Core x 35 sq m pvc insulated, pvc sheathed/XLPE aluminium conductor 1.1 KV grade armoured power cable.
100
-
-
Laying and fixing of one No. pvc insulated and pvc sheathed/XLPE power cable of 1.1 KV grade/telephone cable of following size on wall surface as required. (ii) Above 35 sqmm and upto 95 sq mm.
340
-
-
Supplying and making indoor end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/XLPE conductor cable of 1.1 KV grade as required. (ii) 3x1/2x50 sqmm
16
-
-
Supplying & drawing of PVC insulated 4 pair cat 6,UTP Internet cable into existing surface/recessed steel/PVC Conduit/trunking as required.
1000
-
-
Providing and fixing of 25mmx5mm GI earth strip on surface or on recess for connections etc as required.
40
-
-
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of brass
nut bolt & spring washer spaced at 50mm)
40
-
-
Supply and Fixing of RJ45 Internet socket.
60
-
-
Supply & Fixing of PVC mounting Box 3Mod.
200
-
-
Supply & Fixing of PVC 3Mod.front plate. SCW
200
-
-
Supply & Fixing of 16A One way Swicth
200
-
-
Supply & Fixing of 6/16A Socket ISI Mark
200
-
-
Wiring for circuit/ submain wiring alongwith earth wire with the
following sizes of FRLS PVC insulated copper conductor, single
core cable in surface/ recessed medium class PVC conduit as
required.
-
-
-
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
120
-
-
S/F of LED Flood Light 120Watt
6
-
-
SITC of Indoor type LT Main Panel duly powder coated dust vermin proof, ground mounted comprising of 400Amp, MCCB, 4Pole, 50ka as Incomer -01No., and Outgoing - a) MCCB, 25KA, 160Amp, 4Pole - 08Nos.Complete with metering set and indicators. (For 2nd Floor)
2
-
-
Less buy back cost of the salvage value of dismantled electrical fixtures received after dismantling and removing of old existing light fittings and fixtures, switch boards,switches, MS conduits, DB boxes,fans, exhaust fans, electric wires from the building excluding Main LT Panel and main distributin panels including taking them out from the site complete with required labour, tools and plants.
1
-
-