If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Indian Institute Of Toxicology Research - IITR Tender
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date12 Aug 2024
Closing Date2 Sep 2024
Tender Amount₹ 1,16,64,420
Costs
EMD
₹ 2,33,288Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
SITC of 2X320 KVA/ 256KW Prime CPCB-IV+emission compliant silent type DG Sets
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_CSIR_204578_1Tender No
IITR/EME-17(18)/2023Tender Authority
Indian Institute Of Toxicology Research ViewPurchaser Address
-Website
http://https://www.csir.res.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
( c ) Alternator: Synchronous alternator rated at 320 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS/IEC: 60034-1 suitable for tropical conditions and with class- F/H insulation, compact desighn with sealed bearings and impregnavion on all wound components for better strength and lesser maintenance.
-
-
-
(d) MS Base Frame mounting arrangement: Both the engine and alternator shall be mounted on a common suitable base frame made of MS channel with necessary reinforcement with integral fuel tank and DEF tank provided with drain plug, air vent, inlet and outlet connection and provision for cleaning. and vibration isolation arrangement as per recommendations of the manufacturer.
-
-
-
( e ) Fuel Tank: Daily service fuel tank not less than of 500 liters capacity and DEF tank capacity of 60 ltrs fabricated out of 2/3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS class 'C' pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications.
-
-
-
(f) Exhaust System: Dry exhaust mainfold with residential grade exhaust silencer inside canopy with rain cap suitablaily obtimiased to meet stringent noise limit and catalytic convertor.
-
-
-
(g) Starting System: 12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with suitable nos. of batteries of suitable AH capacity with leads as required as per OEM specifications.
-
-
-
(h) Acoustic Enclouser: Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere, desighn to meet stringent MoEF/ CPCB- IV norms. The enclosure should have fire- retardant grade ecostic insulation material (rockwool) complying to IS 8183 and also having external fuel and DEF filling provision. Total cost for item 1 to 1.08 above
2
-
-
SITC of LT panel floor mounted type, made of 16 gauge CECA sheet, powder coated paint, dust and vermin proofe suitable for 2X320 KVA silent type DG set complete with set of CTs for metering & protection and energy analyser to indicate currents, phase and line voltages, frequency, overload and short circuit protection, restricted earth fault, control cabling from panel to diesel engine all complete and inter locking, between both incomers with the bus coupler, comprissing of the following items (as per drawing enclose):-
-
-
-
(a) Incomer- 800 Amp., 4 pole manual draw-out ACB-50KA, MDO with thermomagnetic release for O/C & E/F and shunt trip. - 02No.
-
-
-
(b) Bus coupler- 800A 4P ACB without protection release and having electrical interlocking with both of the incomers - 01No.
-
-
-
( c ) Power command controller with remote on/off facility for the DG sets.
-
-
-
(d) Busbar- TPN, aluminium conductor busbar of 1000A capacity, dully insulated and supported on DMC supports. -01Set
-
-
-
( e ) Instrument-CT Coils - 800/5A, LED Indicating lamps for RYB for incomming supply, load on mains and load on set, multi fuction meter(AVF), Protection MCB's for instruments - 02 Sets
-
-
-
(f) Battery charger, complete with transformer/ rectifier, D.C voltmeter and ammeter, selector switch for trickle, off and boost and current adjustment.
-
-
-
(g) Outgoings- 100A TPN MCCB 18 KA -01Nos - 160A TPN MCCB 18 KA -01Nos - 200A TPN MCCB 35 KA - 03 Nos - 250 A TPN MCCB 35 KA - 01 Nos Total cost for item 2 to 2.07 above
1
-
-
Supplying and fixing exhaust gas piping of suitable dia. Welded black MS, 'B' Class pipe conforming to IS:3589 cut to required lengths and installed with necessary bends, supports and clamps, anti-vibration mountings, insulation of exhaust system with mineral wool/ Rockwool, 50 mm thick wiremesh & aluminium cladding etc., as required as per specifications.
12
-
-
Exhaust piping support structure made off MS angle/ Chanel of size 150 x 75 upto 6 meter hight and as per drawing and guidence of Engineer in charge during the execution of work with painting and grouting 1.5 meter deep into the ground with contreate and cement etc as required.
2000
-
-
Sub Head 'B'
-
-
-
Supply, Laying and end termination of one number PVC insulated, 2.5 sqmm x 4 core copper conductor, armoured control cable, in the existing pipe as required. Make Havells/ KEI/ Pollycab.
80
-
-
Supply of one number PVC insulated, armoured XLPE aluminium conductor power cable of 1.1 KV grade.
-
-
-
300 Sqmm x 3.5 core, cable
120
-
-
240 Sqmm x 3.5 core, cable
400
-
-
185 Sqmm x 3.5 core, cable
80
-
-
Laying of following sizes, 3.5 core XLPE power cable, 1.1 KV grade in ground after exacavation, sand cushing, protective covering and refilling the trench as required.
-
-
-
One No. 240 Sqmm and 300 Sqmm x 3.5 core cable.
200
-
-
Additional cable 240 Sqmm and 300 Sqmm x 3.5 core cable in the same trench.
380
-
-
01 No. 185 Sqmm x3.5 core cable
40
-
-
Laying of 01 No. Additional cable of 185 sqmm x 3.5 core in the same trench
40
-
-
Supplying and making end termination with brass compression gland and alluminium lux for following sizes of XLPE insulated alluminium conductor armoured cable.
-
-
-
3.5 x 300 Sqmm
8
-
-
3.5 x 240 Sqmm
6
-
-
3.5 x 185 Sqmm
2
-
-
SITC of 315 A, 415V onload change over switch with sheet steel enclouser, cable end boxes and suitable wall mounting M.S stand
3
-
-
Sub head 'C' (C.C Foundation)
-
-
-
Construction of a suitable foundation 6.00 mtr x 2.50 mtr x 0.50 mtr for 320 KVA DG Set, using rainforced cement contreate (RCC) in a 1:2:4 ratio (cement, coarse sand : 20 mm stone aggregate) including cost of excavation, shutring and rainforcement (minimum 243 Kg) over 10 cm thick plane cement concreate (PCC) layer in a 1:5:10 ratio (cement: coarse sand: 40mm thick stone aggregate). Finishing work with cement plaster mix in a 1:6 ratio. Additionally installing M.S bidding upper perimeter of the foundation, using angle section 50 x 50 x 5 mm. Job also include disposal of surplus building material and removal of rubish/malba from campus complete as per instructions of the site engineer.
2
-
-
Sub Head 'D' (Earthing)
-
-
-
Earthing with copper earth plate 600mm x 600mm x 3mm thick including accessories and providing masonry enclouser with cover plate having locking arrangement and watering pipe of 2.7 mtr long etc with charcoal and salt as required. (For Natural Earthing)
4
-
-
Providing, Laying & Connection 25mm x 5mm Copper strip, with brass nut bolt and washer etc in existing G.I Pipe from earth electrode in ground, as required.
30
-
-
Earthing with G.I earth plate 600mm x 600 mm x6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
6
-
-
Supplying and laying 32mm x 6 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I nut bolt & spring washer spaced at 50mm)
36
-
-
Buyback of old 250 KVA(Unserviceable) Cummins make D.G Sets, panel & external fuel tank at Main campus including loading, unloading and transportation from campus all complete.
1
-
-
Buyback of old 75 KVA(Unserviceable) Cummins make D.G Sets at CRK campus including loading, unloading and transportation from campus all complete.
1
-
-