Dakshinanchal Vidyut Vitran Nigam Limited Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Dakshinanchal Vidyut Vitran Nigam Limited - DVVNL Tender
Eprocure
Opening Date12 Jul 2023
Closing Date19 Jul 2023
Tender AmountRefer Documents
Costs
EMD
₹ 3,000Document Cost
₹ 1,180Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_DVVNL_819781_1Bid Award Id
ViewTender No
EDC2A-18/2023-24Tender Authority
Dakshinanchal Vidyut Vitran Nigam Limited ViewPurchaser Address
-Website
http://https://www.dvvnl.org/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Erection of single support including complete H.T/L.T fittings as per RESPO manual and as per direction of Engineer incharge including the cost of labour, T & P and carrier etc. required for proper completion of work.
-
-
-
PCC poles 8.5 Mtr./ST poles 11 Mtr.
39
-
-
Dismentling of old and damaged Double pole after dismentling of all accessories. It includes the work of cartage, cost of labour, T&P carrier etc. required for proper completion of work.
-
-
-
33 KV/ 11 KV line double pole
3
-
-
Erection of double pole on PCC /ST pole including the work of complete line as per RESPO norm manual and as per direction of Engineer Incharge including the cost of labour, T & P and carrier etc. required for proper completion of work.
-
-
-
33 KV/ 11 KV line double pole
3
-
-
Erection and grouting of stay set including the work of nozzling etc. as per RESPO manual and also including the cost of arrangement of all grouting material, labour, T&P etc. required for proper completion of work.
12
-
-
Providing and fixing of stay insulator.
12
-
-
Grouting of PCC poles 8.5 Mtr./ ST poles 11 Mtr. Long as per RESPO norms
45
-
-
Making the plinth of Steel poles.
6
-
-
Fixing of earthing rod as per RESPO manual and as per direction of supervising engineer including the cost of labour, T&P etc. Required for proper completion of work.
45
-
-
Chopping of tree branches which are touching to HT/LT lines.
10
-
-
Retighting of stay complete with nozelling & binding including cost of labour T&P etc required for proper completion of work.
5
-
-
Straightening of tilted PCC/Steel pole at various places as per direction of JE.
7
-
-
Digging of proper size of pit for following work of damaged steel support with the provision of temporary support :- Then reinforcement of steel support by welding of 4 Nos. 2 feet long M.S. angle iron of 50x50x6 mm. at equal distance around each pole/rail & also welding of these angle iron with each other by providing M.S. flat of size 35x6 mm. in round. After this construction of round plinth of pole will be done with cement, sand and concrete in 1:3:6 ratio of size 450 mm dia & 600mm height (300 mm under the ground+300 mm. above the ground). The plinth should be plastered with ½ inch thick cement and sand of ratio 1:4 & taper rounding the upper most part of the plinth. The rate will include all cost of material, labour and T&P etc, for completion of the above work which will be provided by the contractor at his own cost.
2
-
-
Drilling and cutting of tee off channel, V cross arms, Top channel, cross bracing angle, MS garding angle, Dropper chanel. as per specification of UPPCL construction manual including including loading and unloading at the both ends.
20
-
-
Laying, sagging, stringing, binding and jumpering etc. of new/old line conductor on the newly/old erected pole as per RESPO manual and as per direction of supervising engineer, including the cost of arrangement of labour, T&P carrier etc. required for proper completion of work.
-
-
-
ACSR Weasal Conductor
2600
-
-
ACSR DOG Conductor
100
-
-
ABC 3x120+1x95+1x16 sq.mm/ABC 3x95+1x70+1x16 sq.mm/ABC 3x50+1x35+1x16 sq.mm
100
-
-
Re-sagging of loose HT/LT line conductor as per direction of superwising engineer. It includes the cost of labour T&P carrier etc. required for proper completion of work.
-
-
-
ACSR Weasal Conductor
1300
-
-
ACSR Dog Conductor
100
-
-
Replacement/Re-fixing of following damaged/ disturbed/de-aligned accessories:-
-
-
-
33 KV Disc Insulator with fitting
15
-
-
33 KV Pin Insulator with pin
50
-
-
33 KV V-type Cross Arm
15
-
-
11 KV Disc Insulator with fitting
40
-
-
11 KV Pin Insulator with pin
120
-
-
11 KV V-type Cross Arm
40
-
-
F bracket
40
-
-
Providing & Fixing of Clamps of LT, Cross Arm Holding, F-Clamp, Stay Clamp, Danger board clamp with Nut & Bolts.
30
-
-
Providing/Fixing of missing Nut bolts and washer
10
-
-
Dismantling and removal of existing conductor from the various area preparing their coils and then stacking in the respective JE’s (Store) as per direction of Supervising Engineer. It includes the work of cartage, cost of labour, T&P carrier etc. required for proper completion of work.
-
-
-
ACSR Weasal Conductor/GI wire.
1300
-
-
ACSR Dog Conductor
100
-
-
Guarding of old 11 KV line damaged due to storm by laying two nos. GI wire parallel and fixing of lacings (tilli) at a distance at 2-3 Mtr. as per RESPO manual and also including the cost of arragement of labour, T & P etc. required for proper completion of work.
150
-
-
Filling of 3x70/3x120/3x185/3x300 Sq.mm. 11KV/33 KV XLPE heat shrinkable cable jointing kits indoor & outdoor type including the cost of labour T&P carrier etc for proper completion of work.
3
-
-
Repairing of 3x70/3x120/3x185/3x300 Sq.mm 11 KV/33 KV under ground cable by Straight Through after digging trench of 600 mm. wide, 1500 mm deep, providing the fine sand cushion beneath and above the cable. The cable shall be duly protected by Ist class bricks, two on either side and third on top of the cable, laid in series one after the other. The work includes supplying of fine sand and bricks, filling and ramming of the left out soil, closing the trench and levelling. Spare cable shall be left and buried in the trench in the shape of rings at both ends. All material (except cable), labour, T&P carrier etc, required for proper completion of work will be arranged by the contractor at his own cost.
100
-
-
Safe carriage of Old line material viz. Conductor, G.I. Earth wire, ABC conductor, Cross Arm, Angle, Channel, Insulators, Clamps & other line material from any other place or from site of work to the work of its loading & unloading at the respective ends including the cost of labour, T&P and carrier etc. required for proper completion of work.
1
-
-