Central Drug Research Institute Tender
If you're a registered bidder for etender UP and want to inquire about any e-tender UP government has posted, this is your stop. No need to enter every detail on the website of <a href="https://etender.up.nic.in">etender.up.nic.in</a> - BidAssist filters will help you find the exact UP etender you're looking for. Read to learn how to search & bid for etender UP.
Central Drug Research Institute - CDRI Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date12 Oct 2023
Closing Date23 Oct 2023
Tender Amount₹ 32,79,808
Costs
EMD
₹ 65,596Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_CSIR_170642_1Bid Award Id
ViewTender No
2/07/2023-EnggTender Authority
Central Drug Research Institute ViewPurchaser Address
-Website
http://https://www.csir.res.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
2)3x1.5 Sq.mm
300
-
-
3)2x2.5 Sq.mm
100
-
-
4)3x2.5 Sq.mm
300
-
-
5)2x4 Sq.mm
100
-
-
6)3x4Sq.mm
300
-
-
7)2x6 Sq.mm
100
-
-
8)3x6 Sq.mm
100
-
-
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required:
-
-
-
1) 20 mm.
50
-
-
2) 25 mm.
50
-
-
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
-
-
-
1)1 way 5/6 amps
100
-
-
2)1 way 15/16 amps
100
-
-
3)5 Pins Socket 5/6 amps
50
-
-
4)6 Pins 15/16 amps socket
50
-
-
5)Telephone socket outlet
10
-
-
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
40
-
-
Supplying and fixing modular blanking plate on the existing modular plate & switch box including modular plate etc as required.
10
-
-
Supplying and fixing following size/modules.GI box along with modular base and cover plate for modular switches in recess etc as required.
-
-
-
a) 1 or 2 Module (75mmX75mm)
10
-
-
b) 3 Module (100mmX75mm)
10
-
-
c) 4 Module (125mmX75mm)
10
-
-
d) 6 Module (200mmX75mm)
20
-
-
e) 8 Module (125mmX125mm)
20
-
-
f) 12 Module (200mmX150mm)
20
-
-
Supplying and fixing following modular base and cover plate on existing modular metal boxes etc as required.
-
-
-
a) 1 or 2 Module
2
-
-
b) 3 Module
2
-
-
c) 4 Module
2
-
-
d) 6 Module
2
-
-
e) 8 Module
2
-
-
f) 12 Module
20
-
-
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
100
-
-
Installation, testing and commissioning of wall bracket /ceiling fittings of all sizes and shapes containing upto two GLS/CFL/LED lamps per fitting, complete with all accessories including connections etc. as required.
50
-
-
Supplying and fixing call bell suitable for single phase, 230Volt, 50Hz on the existing box excluding connections etc as required.
20
-
-
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
50
-
-
Numbering of ceiling fan/exhaust fan/ fluorescent fittings etc. as required.
200
-
-
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required.
-
-
-
a) Upto 450 mm sweep
1
-
-
b) 510 mm sweep
1
-
-
Extra for fixing the louvers/shutters completes with frame for exhaust fan of all sizes.
2
-
-
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
-
-
-
a) 12way, Double door
1
-
-
b) 16 way, Double door
1
-
-
Supply and fixing 5 amps to 32 amps. rating 240/415 volts, ‘C’ curve miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc as required.
-
-
-
i) Single pole
10
-
-
ii)Single pole and neutral
4
-
-
iii) Triple pole
2
-
-
iv)Triple pole and neutral
2
-
-
Supply and fixing single pole blanking plate in the existing MCB D.B. complete etc. as required.
10
-
-
Supply and fixing following rating, double pole, 240 V isolator in the existing MCB D.B. complete with connections, testing and commissioning etc as required.
-
-
-
i) 40 amps.
1
-
-
ii) 63 amps.
1
-
-
Supply and fixing following rating, four pole, 415 V isolator in the existing MCB D.B. complete with connections, testing and commissioning etc as required.
-
-
-
i) 40 amps.
1
-
-
ii) 63 amps.
1
-
-
Supplying and fixing DP sheet steel enclosure on surface/recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
10
-
-
Supplying and fixing TP sheet steel enclosure on surface/ recess along with 16/25/32 A, 415 V “C” curve TP MCB complete with connections, testing and commissioning etc. as required.
1
-
-
Supplying and fixing 20 A, 240 V SPN industrial socket outlet with 2 pole and earth, metal enclosed plug top along with 20A “C” curve SP MCB in sheet steel enclosure on surface or in recess with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc. as required.
34
-
-
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following sizes direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required:
-
-
-
a)Upto 35 sq.mm
100
-
-
b)Above 35 sq.mm and up to 95 sq.mm
10
-
-
c)Above 95 sq.mm and up to 185 sq.mm
10
-
-
d)Above 185 sq.mm and up to 400 sq.mm
10
-
-
Laying and fixing of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 K V grade of following sizes on wall surface as required:
-
-
-
a) Upto 35 sq.mm (clamped with 1mm thick saddle)
100
-
-
b) Above 35 sq.mm and up to 95 sq.mm (clamped with 25x3mm MS flat clamp)
10
-
-
c) Above 95 sq.mm and up to 185 sq.mm (clamped with 25/40x3mm MS flat clamp)
10
-
-
d) Above 185 sq.mm and up to 400 sq.mm (clamped with 40x3mm MS flat clamp)
10
-
-
Supplying and making end termination with brass compression gland & heavy duty lugs for the following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grades as required:
-
-
-
a)3½ X 25 sq. mm (28mm)
2
-
-
b) 3½ X 35 sq. mm (32mm)
2
-
-
c) 3½ X 50 sq. mm (35 mm)
2
-
-
d) 3½ X 70 sq. mm (38mm)
2
-
-
e) 3½ X 95 sq. mm (45 mm)
2
-
-
f) 3½ X 120 sq. mm (45 mm)
2
-
-
g) 3½ X 150 sq. mm (50 mm)
2
-
-
h) 3½ X 185 sq. mm (57mm)
2
-
-
i) 3½ X 240 sq. mm (62mm)
2
-
-
j) 3½ X 300 sq. mm (70 mm)
2
-
-
k) 4 X 10 sq. mm (25 mm)
10
-
-
l) 4 X 16 sq. mm (28mm)
10
-
-
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
-
-
-
a) 3½ X 70 sq. mm
1
-
-
b) 3½ X 95 sq. mm
1
-
-
c) 3½ X 120 or 150 sq. mm
1
-
-
d) 3½ X 185 sq.
1
-
-
e) 3½ X 240 sq.
1
-
-
f) 3½ X 300 sq. mm
1
-
-
Filling available excavated earth (excluding rock) in trenches, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering,lead up to 50 meter.
2
-
-
Excavation of the cable trenches in hard rock not exceeding 1.5 meter in width, and lift upto 1.5 meter, including getting out the excavated soil and disposal of excavated soil as directed within a lead of 50 meter.
2
-
-
Supply, installation, testing and commissioning of following sizes , BEE 5 star rated, ceiling fan with brush less direct current(BLDC) motor, class of insulation:B, 3nos. blades, 30cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, power factor not less than 0.9, service value (CMM/W) minimum 6.85, air delivery minimum 215 CMM, 350RPM (tolerance as per IS:374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, tempreture rise=75degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230V,50Hz, single phase AC supply, earthing etc. complete as required:
-
-
-
a)1200 mm sweep
100
-
-
b)1400 mm sweep
100
-
-
Earthing with copper earth plate 600mmx600mmx6mm thick including accessories, and providing masanory enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc with charcoal / coke and salt etc. as required.
2
-
-
Providing and laying/fixing GI tape 32mmx6mm from earth electrode directly in ground and its connections, etc as required.
20
-
-
Supplying and making end termination with brass compression gland & heavy duty lugs for the following size of PVC insulated and PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grades as required:
-
-
-
a)3 X 300 sq. mm
2
-
-
Supply of 1.1KV grade, PVC insulated and PVC sheathed heavy duty aluminium conductor cables of following sizes etc as required:
-
-
-
a)4 x 10mm square
100
-
-
b)4x 16mm square
50
-
-
c) 3&1/2 x 25mm square
10
-
-
d)3&1/2 x 35mm square
10
-
-
e)3&1/2 x 50mm square
10
-
-
f)3&1/2 x 70mm square
10
-
-
g) 3&1/2 x 95mm square
10
-
-
h) 3&1/2 x 120mm square
10
-
-
i) 3&1/2 x 150mm square
10
-
-
j)3&1/2 x 185mm square
10
-
-
k) 3&1/2 x 240mm square
10
-
-
l) 3&1/2 x 300mm square
10
-
-
Dismantling of defective existing office light fixture or fan or point wiring and handing over the material to electrical section as required.
200
-
-
Dismantling of sub main wiring from the surface or reccessed , restoring the surface & handing over the materials to the electrical section, etc as required.
50
-
-
Dismantling of existing or defective old metal clad power switches, MCB enclosures, DB’s, after disconnection of cables / wires, restoring of walls and handing over the material to electrical section, etc as required.
34
-
-
Dismantling of various sizes of cable from the surfaces, restoring the surfaces & handing over the materials to electrical section, etc as required.
50
-
-
Supply & mounting of 3 or 4 pole, 63 Amps, 16KA, 415V MCCB on existing mild steel box or enclosure, etc as required.
1
-
-
Supply & fixing of sheet steel enclosure box for fixing of 63 or 100 or 125 or 160 or 200Amps 3 or 4 pole MCCBs etc as required.
1
-
-
Providing and fixing of 3mm phenolic laminated sheet/perspex sheet on existing metal board/box etc as required.
8000
-
-
Supply & laying of 6 SWG GI earth wire along with existing aluminium power cable including end termination with proper size of lugs etc as required.
200
-
-
Supply & installation of following type of energy efficient LED light fitting along with accessories and manpower, including dismantling of defective light fitting, etc as required:
-
-
-
a)9 or 10 Watt, 2feet stand alone industrial type aluminium extruded CW
100
-
-
b)18 or 20 Watt, 4feet stand alone industrial type aluminium extruded CW
600
-
-
e) 40 or 45 Watt, Post top lantern CW
2
-
-
f) 90 Watt, street light CW
2
-
-
g) 50 to 70 Watt, street light CW flood light
2
-
-
Supply & fixing of following sizes of single phase, 230 volt, 50Hz metallic exhaust or fresh air fan, etc as required:
-
-
-
a)225 mm sweep
40
-
-
b)300 mm sweep
40
-
-
c)450 mm sweep
4
-
-
Supply, testing and commissioning of 11KV RMU (ring mains unit), 3way (01 No. Isolator + 02 Nos. Circuit Breaker) with over cureent and earth fault relay having breaking capacity of 21KA, 630 Amps including all the manpower and materials, etc as required.
1
-
-
Supply, testing and commissioning of 25 litres of capacity electric geyser 5 star rated, having SS tank, glass lining including all the pipe fittings/consumables, dismantling of old and existing geyser and installation of new unit, etc as required.
30
-
-
GST 18 % (already included in the items rate, please do not fill GST here)
1
-
-
Evaluation Notes How It Works ?