Nuclear Fuel Complex Tender
For getting the details of etenders, if you are looking for information about them from the cumbersome government websites but are tired of doing so, Bidassist comes up with a one stop solution. It collates every Eproc telangana tender on Bidassist. One can approach it for the bidding process, registration process, etc., are explained below.
Nuclear Fuel Complex - NFC Tender
Electrical Goods and Equipments
Electrical and Electronics
Eprocure
Opening Date15 Jun 2024
Closing Date15 Jul 2024
Tender Amount₹ 1,03,27,368
Costs
EMD
₹ 2,06,547Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Providing Ac Facility Tocontrol Rooms
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_NFC_811679_1Bid Award Id
ViewTender No
E662/2024Tender Authority
Nuclear Fuel Complex ViewPurchaser Address
-Website
http://eprocure.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
11 TR Capacity Floor Mountd Package Type AC unit (i) Power Supply : 3 Ph, 415Volts, 50 Hz (ii) Refrigerant : Eco friendly / R-410A (iii) Control :Intelligent Microprocessor contrl with LCD display (iv) No. of Compressors & Type : 02 No. & High Energy Efficient (v) No. of condensers : 02 No. (vi) Type of Condenser : Air cooled
(vii) Nominal Air Flow : Range from 4200 CFM to 4800 CFM
-
-
-
Supply
5
-
-
Erection
5
-
-
8 TR Capacity Floor Mountd Package Type AC unit (i) Power Supply : 3 Ph, 415Volts, 50 Hz (ii) Refrigerant : Eco friendly / R-410A (iii) Control :Intelligent Microprocessor contrl with LCD display (iv) No. of Compressors & Type : 01 No. & High Energy Efficient (v) No. of condensers : 02 No. (vi) Type of Condenser : Air cooled
(vii) Nominal Air Flow : Range from 3200 CFM to 3600 CFM
-
-
-
Supply
5
-
-
Erection
5
-
-
5.5 TR Capacity Floor Mountd Package Type AC unit (i) Power Supply : 3 Ph, 415Volts, 50 Hz (ii) Refrigerant : Eco friendly / R-410A (iii) Control : Intelligent Microprocessor contrl with LCD display (iv) No. of Compressors & Type : 01 No. &High energy efficient Scroll Compressor (v) No. of condensers : 01 No. (vi) Type of Condenser : Air cooled
(vii) Nominal Air Flow : Range from 2000 CFM to 2400 CFM
-
-
-
Supply
6
-
-
Erection
6
-
-
3TR Capacity Ductable Ceiling Suspended Type AC unit (i) Power Supply : 3 Ph, 415Volts, 50 Hz (ii) Refrigerant : Eco friendly / R-410A (iii) Control : Intelligent Microprocessor contrl with LCD display (iv) No. of Compressors & Type : 01 No. &High energy efficient Scroll Compressor (v) No. of condensers : 01 No. (vi) Type of Condenser : Water cooled
(vii) Nominal Air Flow : Range from 1200 CFM to 1600 CFM
-
-
-
Supply
12
-
-
Erection
12
-
-
2TR Capacity Ductable Ceiling Suspended Type AC unit (i) Power Supply : 3 Ph, 415Volts, 50 Hz (ii) Refrigerant : Eco friendly / R-410A (iii) Control : Intelligent Microprocessor contrl with LCD display (iv) No. of Compressors & Type : 01 No. &High energy efficient Scroll Compressor (v) No. of condensers : 01 No. (vi) Type of Condenser : Water cooled
(vii) Nominal Air Flow : Range from 800 CFM to 1200 CFM
-
-
-
Supply
3
-
-
Erection
3
-
-
Refrigerant Hard copper tubing ( sizes-as recommended by OEM) for 15TR /16 TR Package AC ( discharge line & liquid line ) with supporting grid (GI threaded rods with cable tray & its cover ), & necessary fittings , elbows , clampings, grouting, etc. from IDU to ODU. Discharge & liquid line shall be painted ( double coat with metal primar paint) with Red & Yellow coloures repsectively.
-
-
-
Supply
20
-
-
Erection
20
-
-
Refrigerant Hard copper tubing ( sizes-as recommended by OEM) for 5 TR / 5.5 TR Package AC ( discharge line & liquid line ) with supporting grid (GI threaded rods with cable tray & its cover ), & necessary fittings , elbows , clampings, grouting, etc. from IDU to ODU. Discharge & liquid line shall be painted ( double coat with metal primar paint) with Red & Yellow coloures repsectively. Control cable from IDU to ODU shall be run in suitable PVC pipe with fittings, etc.
-
-
-
Supply
40
-
-
Erection
40
-
-
Cooling tower water pipe line for INLET in GI - ( Size of GI piping shall be - 1.5" i.e. one and halft inches) for 3 TR Ductable ODU - including flanges, elbows, couplings, nipples , welding, etc. as required. Ball valve - 1/2 " size - 16 nos., Butter fly valves for Inlet - 16 nos.; digital pressure guages ( range 0-16Kg/Cm2) - 8 nos. , digital flow meters( range up to 200 lpm) - 8 nos. for measuring cooling water in the Inlet. Entire GI piping shall be done painting with red oxide & double coat metal primer painting ( preferably - green colour) & as required as per site conditions .
-
-
-
Supply
60
-
-
Erection
60
-
-
Cooling tower water pipe line for OUTLET in GI - ( Size of GI piping shall be - 2 " i.e. two inches) for 3 TR Ductable ODU - including flanges, elbows, couplings, nipples , welding, etc. as required. Ball valve - 1/2 " size - 16 nos., Butter fly valves for Outlet - 16 nos.; digital pressure guages ( range 0-16Kg/Cm2) - 8 nos. , digital flow meters( range up to 200 lpm) - 8 nos. for measuring cooling water in the Outlet. Entire GI piping shall be done painting with red oxide & double coat metal primer painting ( preferably - green colour) & as required as per site conditions .
-
-
-
Supply
80
-
-
Erection
80
-
-
Cooling water pipe line for Inlet & Outlet in GI with Isolation valves( size as recommended by OEM) for 2 TR Ductable Split AC with MS supports as per site condition.
-
-
-
Supply
10
-
-
Erection
10
-
-
Refrigerant Hard copper tubing ( sizes-as recommended by OEM) for 8 TR/11 TR Package AC ( discharge line & liquid line ) with supporting grid (GI threaded rods with cable tray & its cover ), & necessary fittings , elbows , clampings, grouting, etc. from IDU to ODU. Discharge & liquid line shall be painted ( double coat with metal primar paint) with Red & Yellow coloures repsectively. Control cable from IDU to ODU shall be run in suitable PVC pipe with fittings, etc.
-
-
-
Supply
30
-
-
Erection
30
-
-
Refrigerant Hard copper tubing ( sizes-as recommended by OEM) for 5 TR / 5.5 TR Ceiling Mounted Ductable AC ( liquid line & suction line ) with insulation nitrile foam tubing - wall tk - 12 mm ; masking tape and supporting grid (GI threaded rods with cable tray & its cover ) , necessary fittings , elbows , clampings, grouting, etc. from IDU to ODU. Control cable from IDU to ODU shall be run in suitable PVC pipe with fittings, etc.
-
-
-
Supply
20
-
-
Erection
20
-
-
GI Ducting: Supply, fabrication & erection of GI l ducting along with supporting MS angle frame / structure based on the approved drawings as per the site conditions.
-
-
-
Supply :GI ducting 22 Guage
80
-
-
Erection : GI ducting 22 Guage
80
-
-
Supply :GI ducting 24 Guage
40
-
-
Erection : GI ducting 24 Guage
40
-
-
THERMAL INSULATION OF DUCTS (UN EXPOSED) : Supply and Application of External Thermal Insulation of Supply Air ducting. Material of construction shall be cross linked polyolefin/ polyethelene foam material with closed cell structure and with factory applied reinforced aluminium foil. The density of the same shall be within 25 Kg/m3.The material should have a thermal conductivity not exceeding 0.032 W/mK. The insulation material shall be shall be stuck to the cleaned duct surface by factory pre-fixed cold adhesive. The material and installation methodology should be in accordance with the specifications. Thickness of insulation:25mm.
-
-
-
Supply
100
-
-
Erection
100
-
-
ACOUSTIC INSULATION OF DUCTS : Supply and Application of Acoustic insulation for the initial portion of supply air ducting. Material of construction shall be fibre-free elastomeric nitrile rubber foam with open cell structure . The density of the same shall be within 140-180 Kg/m3. The material should have a thermal conductivity not exceeding 0.050 W/mK. The maximum surface temperature the material should withstand is 105° C and minimum temperature should be -20°C. The material should conform to Class 1 rating for surface spread of Flame as per BS 476 Part 7. The insulation material shall be shall be stuck to the cleaned duct surface by factory pre-fixed cold adhesive. The material and installation methodology should be in accordance with the specifications. Thickness of insulation:25mm.
-
-
-
Supply
30
-
-
Erection
30
-
-
SA / RA Grill : Supply & Installation of Aluminium powder coated ( of minimum thickness of 0.8 mm ) grill without Volume Control Damper (VCD) alongwith all necessary hardware complete in all respects.
-
-
-
Supply
8
-
-
Erection
8
-
-
SA Grill : Supply & Installation of Aluminium powder coated ( of minimum thickness of 0.8 mm ) grill with Volume Control Damper (VCD) alongwith all necessary hardware complete in all respects.
-
-
-
Supply
8
-
-
Erection
8
-
-
STRUCTURAL FABRICATED STEEL WORK: Supply, Fabrication , Cutting, Welding , Erection at site and painting of M. S. Angle structural steel work for required truss, AC /Supporting structurer/etc. & as per site requirements, etc. based on the approved drawings. The work should be carried out as per good manufacturing and installation practices in concurrence with approved drawings. The structural steel materials should confirm to IS : 2062 (latest version) as per drawings. All welding electrodes to confirm to relevant IS codes. Fabrication and erection of the structural steel works shall be as per IS: 800 and welding work as per IS:816 and IS: 822. Finally all steel work to be painted with one coat of zinc chromate primer and two coats of synthetic enamel paint.
-
-
-
Supply
800
-
-
Erection
800
-
-
Electrical power supply panel (MCBDB) board for 15 TR / 16 TR Package AC Unit - One suitable size incommer- isolator and 2 outgoing MCB's.(as recommended by OEM). Indication lamps for incoming power supply; AC Units - ON & OFF.
-
-
-
Supply
1
-
-
Erection
1
-
-
Electrical power supply panel (MCBDB) board for 5 TR / 5.5 TR Package AC Unit - One suitable size incommer- isolator and 3 outgoing MCB's.(as recommended by OEM). Indication lamps for incoming power supply; AC Unit - ON & OFF.
-
-
-
Supply
2
-
-
Erection
2
-
-
Electrical power supply panel (MCBDB) board for 3 TR Ductable Split AC Unit - One suitable size incommer- isolator and 3 outgoing MCB's.(as recommended by OEM). Indication lamps for incoming power supply; AC Unit - ON & OFF.
-
-
-
Supply
4
-
-
Erection
4
-
-
Electrical power supply panel (MCBDB) board for 8 TR / 11 TR Package AC Unit - One suitable size incommer- isolator and 4 outgoing MCB's.(as recommended by OEM). Indication lamps for incoming power supply; AC Unit - ON & OFF.
-
-
-
Supply
2
-
-
Erection
2
-
-
POWER CABLING : Supply & Installation of Power supply cable - BIS certfied PVC insulated Armoured FRLS electrical - four core copper cable - including GI Strip 25x3mm for earthing & clamping, etc.
-
-
-
16 Sq. mm - Supply
10
-
-
16 Sq. mm - Erection
10
-
-
10 Sq.mm - Supply
20
-
-
10 Sq.mm - Erection
20
-
-
6 Sq.mm - Supply
50
-
-
6 Sq.mm - Erection
50
-
-
4 Sq.mm - Supply
60
-
-
4 Sq.mm - Erection
60
-
-
2.5 Sq.mm - Supply
20
-
-
2.5 Sq.mm - Erection
20
-
-
Control Cabling : Supply & Installation of control cabling - BIS certified PVC insulated FRLS copper control cable of - 1.5 Sq.mm size interconnecting the IDU & ODU Units.
-
-
-
Supply
100
-
-
Erection
100
-
-
Condensate water drain piping : CPVC drain piping required for 2 TR / 3 TR / 5 TR / 8 TR /11 TR / 16 TR AC units with insulated out of class O closed cell elastomeric nitrile rubber material with U trap., bends, clamping, etc.
-
-
-
Supply
100
-
-
Erection
100
-
-
Panel Air Conditioner of Side Mounting type as per the following specifications : (i) Cooling Capacity : Range from 1000-1100 watts (OR) 3500-3800 K. Cal./ Hr. (ii) AC Mounting type : Side mounting type (iii) Power Supply : Single phase , 230 volts (iv) Refrigerant : Eco-friendly / R- 134a (v) Temperature controller : Digital Temperature Controller - with an accuracy of Plus(or)Minus : 1 Deg C (vi) Cold air should always be injected into the panel from the bottom and hot air sucked from the top of Panel AC unit.
-
-
-
Supply
4
-
-
Erection
4
-
-
DAMPERS: Supply, installation, testing and commissioning of Factory fabricated low leakage manually operated volume control duct dampers with Aerofoil-blades and MOC as 1.5mm thick powder coated Aluminium . Canvas cloth of suitable size with zip shall be connected to outlet of AC & Damper.
-
-
-
Supply
60
-
-
Erection
60
-
-
Supply and Erection Canvas cloth of rexin coated suitable size with zip shall be connected to outlet of AC & Damper.
-
-
-
Supply
60
-
-
Erection
60
-
-
CABLE TRAYS: Supply & Installation of following size of perforated Hot Dipped Galvanised Iron Cable tray & GI Cover ( Galvanisation thickness not less than 50 microns) with perforation not more than 17.5% in conveinet sections, joined with connectors, suspeneded from the ceiling with GI suspenders including GI bolts & nuts , / MS supports, etc. as required at site.
-
-
-
Supply-100 mm widith X 75 mm depth X 1.6 mm thickness
100
-
-
Erection-100 mm widith X 75 mm depth X 1.6 mm thickness
100
-
-