For getting the details of etenders, if you are looking for information about them from the cumbersome government websites but are tired of doing so, Bidassist comes up with a one stop solution. It collates every Eproc telangana tender on Bidassist. One can approach it for the bidding process, registration process, etc., are explained below.
Costs
EMD
₹ 64,698Document Cost
₹ 1,180Tender Fee
Refer Documents
Summary
Replacement Of Old Ht Ocb Panels At Substation I And Ii At Begumpet Airport Hyderabad.
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_AAI_228913_1Bid Award Id
ViewTender No
AAI/HYD/CW-2/ VCB/2Tender Authority
Airports Authority Of India ViewPurchaser Address
-Website
http://https://www.aai.aero/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Single phase 11 KV Potential C ast Resin Potential Transformer FIXED TYPE 11KV/√3/110/√3 C-1 CL 0.5 50VA- 3 set.
-
-
-
... More
Current Transformer: 11KV Epoxy Cast Resion Type Single Phase CTs.
200/1-1A (SITC 25KA/1Sec) CORE 1 - CL 0.5 15V CORE 2 - CL SP10 15VA - 3 Nos
-
-
-
... More
800 amps TP, 12KV air insulated and encapsulated copper Bus bar of Suitable size as per panel configation.
-
-
-
... More
supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for size of 3 core X 300 Sq.mm, XLPE aluminium conductor cable of 11 KV grade as required
4
-
-
... More
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol.
(vi) Master-Trip and Trip-Circuit Supervision
The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
-
-
-
... More
01no. Incomer VCB Panel each comprising of
-
-
-
... More
SITC of 11KV 630A 26.3KA Indoor HT VCB 3 Panel Board
-
-
-
... More
01 No. for each breaker:- Digital Multifunction Meter, accuracy class 0.5s, with LED/LCD screen of Max Demand Load, I ;V; Hz; Active, Reactive , Apparent Power & Energy; Power factor; % unbalance of current & voltage; , %THD , individual harmonics up to 15th level (complying with IEC61557-12) with RS 485 / Ethernet port and protection MCBs. and required accessories to complete the system.
-
-
-
... More
11kV, 630A, Vacuum Circuit Breaker
-
-
-
... More
Numerical Protection Relay, modular design , confirming to IEC 60255, protection scheme for detecting, indicating and tripping the breaker on critical faults like (i)over current & short circuit 51,51N & one earth fault element in the three phases, (ii) negative sequence currents due to line-to-line or conductor-break faults, (iii) residual and three-phase under-voltages/over-voltages, (iv) circuit-breaker-failure alarm, (v) tripping-circuit-failures and interpanel tripping/blocking signals via GOOSE based peer-to-peer communication, on IEC61850 protocol.
(vi) Master-Trip and Trip-Circuit Supervision
The relay shall be integrated with the feeder, capturing status like Breaker On/Off/Spring. Charged/Test/Service/AC-Fail, Line-Current, Line-Voltage etc. and display the same on graphical display (MIMIC), remote communication on IEC61850 platform on Ethernet. Arc Flash Protection Shall be provided: Sensing of any ARC produced in any of the 3 chambers i.e. Breaker, Cable and Busbar apart from Protection features, along with arc sensors , fibre cables etc. along with other accessories to complete the system.
-
-
-
... More
supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for size of 3 core X 240 Sq.mm, XLPE aluminium conductor cable of 11 KV grade as required
2
-
-
... More
Current Transformer: 11KV Epoxy Cast Resion Type Single Phase CTs.
100/1-1A (SITC 25KA/1Sec) CORE 1 - CL 0.5 15V CORE 2 - CL SP10 15VA - 6 Nos
-
-
-
... More
SITC of 11KV 630A 26.3KA Indoor HT VCB 3 Panel Board AS ABOVE
2
-
-
... More
Dismantling of Existing HT OCB Panels including dismantling of Incomming and outgoing cables etc. and shifting to AAI store as per Instructions of EIC.
2
-
-
... More
Supply, Installation, Testing and Commissioning of 11KV indoor type floor mounted metal clad VCB Panel, fabricated of 2 mm thick CRCA/Aluzinc sheet, with (03) Nos. VCBs, totally enclosed & electrically interlocked, horizontal drawout on floor, horizontal isolation type VCB as per IEC62271-100 for breakers and 200 for panels/ IS3247 of switch board, as per specifications, having capacities as mentioned below, single break, trip free mechanism, electrical and manually charged and closing breaker suitable for use on 11 kV, 3Phase, 50Hz A.C. supply , complete with self contained electrically interlocked rack in and rack out mechanism, air insulated and encapsulated copper bus bars, breaker featured with mechanical ON/ OFF indicator with hand trip device, spring release coil, shunt trip coil and auxiliary switch of 4NO + 4NC and equipped with following switchgears and accessories i/c connections suitable for 1 R X 3C X 300 sq.mm. XLPE 11 kV cable as incomer as well as outgoing feeder.
STC 26.3 kA for 3 sec , Internal Arc Test for AFLR 26.3 kA for 1 sec. at individual compartments i.e. Busbar, VCB and cable compartment.
Separate earthing truck shall be required for each bus earthing & cable earthing. Earthing truck shall be so designed that it is impossible to earth a live. It shall be provided with capacitive voltage divider and complete with audio visual annunciation, one for each panel. (noted: cost of end termination are not included in this Item s & cable entry from bottom considered).
-
-
-
... More
02 nos. Outgoings VCB Panel each comprising of
-
-
-
... More
11kV, 630A, Vacuum Circuit Breaker
-
-
-
... More
Busbars
-
-
-
... More
The panel shall be complete with suitable surge protection device required for the suitable voltage level and withstanding current.
-
-
-