Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Tidel Park Limited Tender
Software and IT Solutions
Eprocure
Opening Date22 Aug 2024
Closing Date4 Sep 2024
Tender Amount₹ 37,82,290 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 65,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_TIDEC_475210_1Bid Award Id
ViewTender No
TIDEL/2024-25/16Tender Authority
Tidel Park Limited ViewPurchaser Address
-
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply, Installation, Testing and Commissioning of BMS SOFTWARE:
Web enabled Graphical interface software based on MS Windows 10 / Latest. The system should be accessible from anywhere on LAN or WAN or Ethernet without additional licenses. The Communication protocol shall be Industry Standard BACNET Open Protocol. System should be scalable. The software shall be open system architecture type which facilitates interoperability with other system over BACNET IP with complete control and monitoring functions. Software shall be certified and complying to BACnet Advanced Operator Workstation. The software shall have facility to define alarms for certain consumption values. Software should be BACnet standard ISO 16484-5 protocol 1.13 or latest. Required gateway/open protocol software compatible to Modbus RTU/BACNet.
1
-
-
... More
Supply, Installation, Testing and Commissioning of Client version BMS software for "Monitor & Control" application, complete with Advance Graphics for Realtime Graphical Depiction of the Statuses and Controls as per the Detailed IO Summary.
2
-
-
... More
Supply, Installation, Testing and Commissioning of SMS & E-mail alarm notification module with unlimited user capability,SMS Paging & Email Facility for transmitting specified alarms to designated personnel.
1
-
-
... More
Supply,Installation,Testing & commissioning of Serial interface Modules (as a part of IO Module train) for High Level integration with following 3rd Party Equipment's as mentioned in the data point summary. Integration of the following equipment's and generating software for monitoring the parameters. Integration cost shall include charges towards development of graphic screens for all the equipment's listed below. The system will warrant an Exclusive, Dedicated Serial Interface Card / Controller for every single individual 3rd party system ( No other 3rd Party Integration shall be clubbed with any one integration ) The Interface controller shall be Capable to Integrate Open protocol systems on BACnet / Modbus / M-Bus Protocol Made available on serial RS 485 interface.
Such Interface controller shall be Installed in a deticated enclosure and the same has to be connected with the BMS system through BACNET / IP protocol with following accessories
-
-
-
... More
Integration of Fire Alarm System - 500 points
1
-
-
... More
Integration of Digital Load Managers for metering.- 50 Nos - 10 points each (total 500 points)
1
-
-
... More
Integration of AHU VFD - 28 Nos 10 points each (total 280 points)
1
-
-
... More
Integration of UPS - 2 Nos - 20 points each (total 40 no's)
1
-
-
... More
Integration of VRF System - 16 ODU's - Upto 30 nos
1
-
-
... More
Integration of VRF System - 32 IDU's
1
-
-
... More
Integration of Diesel Generator - 2 nos
1
-
-
... More
Integration of Lift - 3 nos
1
-
-
... More
Integration of Solar System- 3 nos
1
-
-
... More
Integration of STP
1
-
-
... More
BACNET / MODBUS communication card for VRF by the OEM to integrate the VRF system with IBMS
2
-
-
... More
Supply, Installation, Testing and Commissioning of DDC CONTROLLERS as per Data point summary.
The Enclosures shall be MS Powder Coated , IP 55 Rating for indoor; and IP 65 rating for outdoor Installations. The Enclosure shall be provided with mounting accessories for DDCs / and or IO Modules and Serial Modules- such as DIN Rails, Elmex Terminals for Cable Terminations, Cable Managers, Dressings for internal cabling, ferruling, tagging etc. PSU shall also cater to power requirment of the Instrumentation, Actuators and other connected equipment. Enclosure Shall be Complete with pilot relays, fuses, overload protection relays, auxiliary power output socket etc. as required to complete the installation and intended usage. Shall have Bottom Knockouts for Cable entry, and side vents for ventilation DDCs, I O Modules and Serial Modules shall confirm to Tender specs and design intent. Each DDC shall not exceed more than 24 IO ponits including spare, In a DDC Enclosure, there shall not be more than 6 controllers / expansion modules. The Enclousere shall be provided with UPS as per enclousere power Requiremnet. DDC CONTROLLERS : Automation stations / DDC Controller with I/O module etc., The controllers shall be NATIVE BACNET IP based. The controller shall be with 32 bit microprocessor, working in standalone or networkable mode, with real time clock and historical database & Peer to Peer Communication. The controller should have minimum of 24 IO Points with inbuilt Port for RS485 communication. The DDC's shall store programs and program parameters in non volatile memory. The DDCs shall be housed within a suitable powder coated MS enclosure complete with all protection, terminals, wiring and accessories as mentioned.
[ Note: 1. The selection of DDC controller shall be as per I/O schedule and the quantity of DDC controller shall be as mentioned below, no deviation shall be acceptable.
2. Please include the plug top and wiring required to tap the power supply from the sockets provided for DDC panel.]
7
-
-
... More
Supply, installation, testing & commissioning of Differential Pressure Switches to monitor AHU Fan Status with necessary coolectiong tube for suitable length and NO NC for the status of range of 500 pascal
28
-
-
... More
Supply, installation, testing & commissioning of Differential Pressure Switches to monitor AHU Pre Filter Status with necessary coolectiong tube for suitable length and NO NC for the status of range of 300 pascal
28
-
-
... More
Supply, installation, testing & commissioning of Return air temperature sensor - Duct mount type Air Temperature (Range: 0-50⁰C ) having pt1000 / Ni1000 output for Temperature and temperature accuracy +/- 0.5 ˚C & with accessories & all complete,
28
-
-
... More
Supply, installation, testing & commissioning of Ambient Temperature and RH Sensor with Radiation shield - Outside Air Temperature & RH Sensor (Range: Temp 0-50⁰C & Humidity 0-100% ) having 0-10V DC output for Temperature & RH , Temperature accuracy +/- 0.5 ˚C, RH accuracy +/- 3% for 10-90% RH , to be installed in common return duct at AHU side with accessories & all complete.
1
-
-
... More
Supply, installation, testing & commissioning of Level Switch For Water Tank
4
-
-
... More
Supply and Run of 2 Core 1.0 SQ. MM, GI unarmored ATC conductor multi strand, Unscreened cable. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
1500
-
-
... More
Supply and Run of 2 Core 1.0 SQ. MM, GI unarmored ATC conductor multi strand, screened cable. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
1500
-
-
... More
Supply and Run of 2 Core 1.5 SQ. MM, GI unarmored ATC conductor multi strand, screened cable. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
1500
-
-
... More
Supply and Run of 3 core x 1.5 sqmm screened unarmored cable for Power. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
500
-
-
... More
Supply and Run of 4 Core 1.0 SQ. MM, GI unarmored ATC conductor multi strand, screened cable.. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
500
-
-
... More
Supply and Run of CAT 6 Communicatiuon cable.. Laid on Surface / On Cable Trays. All Cables shall be ferruled and tagged, and shall use lugs for termination at both ends.
1200
-
-
... More
Supply & laying PVC- FRLS conduits complete with all fittings and accessories-1 " PVC Conduit on wall
1500
-
-
... More
Supply & laying PVC- FRLS conduits complete with all fittings and accessories-19MM PVC Conduit on wall
1000
-
-
... More
Supply and fixing of Factory Fabricated Perforated Cable tray of size : 50 mm x 50 mm made out of 1.6 mm thick galvanized sheet. for housing communication cables from all the systems. In all AHU Rooms, Cable trays between DDC panel to the termination should be used.
50
-
-
... More
Supply and fixing of Factory Fabricated Perforated Cable tray of size : 150 mm x 50 mm made out of 1.6 mm thick galvanized sheet. for housing communication cables from all the systems. In all AHU Rooms, Cable trays between DDC panel to the termination should be used.
50
-
-
... More
Supply, installation, testing & commissioning of of Network Switch : 24 port layer Network switch with 10/100/1000 Mpbs
2
-
-
... More
Supply, installation, testing & commissioning of 24U Rack - 19" type Equipment racks for mounting the Servers/ Switches in the BMS Equipment Room, & for mounting field mounted Switches at every Floor. Racks shall be complete with Modular Patch Panels for Patching the Field Cables ( Cu and FO) with the Edge Switches on floor as required. Racks shall be provided with Dual Power A&B, and should have 2 PDU Strips, Redundant Fans and Door to have Tamper Switch.
1
-
-
... More
Any other accessories required to complete the system configuration as per vendor specific requirements i.e. Power supplies, fiber converters, LIUs, Specific System cables etc. to complete the installation.
Contractor to mention the quantity of the below items with cost apart from the below item if any other accessories are required , contractor to add the same Patch Panels,1mtrs Cat6 Patch Cords LIU’s Pigtail cables 1mtr LC to LC Single Mode Patch Cords, Labels, any Other component to complete the design intent