Tamil Nadu Urban Habitat Development Board Tender
Search from a plethora of business opportunities for Tamil Nadu tenders posted on the eProcurement TamilNadu website and other online and offline sources. Here, on BidAssist, you can find the best tender opportunities to boost your enterprise by finding work in Tamil Nadu government tenders, PSUs, Municipal Corporations and more. Read on to learn about the bidder registration process, DSC and more.
Tamil Nadu Urban Habitat Development Board - TNUHDB Tender
Civil And Construction
Building Construction
Eprocure
Opening Date19 Oct 2024
Closing DateCancelled
Tender Amount₹ 2,29,00,000
Costs
EMD
₹ 1,25,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Summary
Providing Lift And Genset Arrangements For Work Of Construction Of 396 Tenements Adopting Type Design 86a/2019 And 86b/2019 (ground Plus 5 Storied) At Shenoy Nagar Old Bus Stand Scheme
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_TNUHB_494908_1Bid Award Id
ViewTender No
TNUHDB/788-1/D1/SE(NC-II)/2018Tender Authority
Tamil Nadu Urban Habitat Development Board ViewPurchaser Address
-Website
http://tntenders.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Wiring with 2x1.5sqmm PVC insulated single coreunsheathed Aluminium conductor cable of 1100V gradewith ISI mark confirming to IS: 694/1990 in suitablePVC rigid pipe of 1.8mm thick with ISI mark concealedin wall and ceiling with PVC accessories in flushwith wall including the cost of cable, pvc pipe andspecials, ceiling rose, flush type 5ams SP markswitch, PVC junction box, 16gauge MS switch box100mm x 100mm x 75mm covered by laminatedhylem sheet 3mm thick, cement, labour and makinggood of concealed portion with suitable colour forconcealed LIGHT point.
49
-
-
Supply and fixing of water tight bulk head fitting (heavy type) with guard suitable for 100 / 60 W bulb including the cost of bulb, necessary connection cost of materials etc complete in all respects as directed by the departmental officer.
49
-
-
Supplying and fixing of 100 A three phase 500 V 4 pole change over switch M-1410 etc complete in all respects as directed by the departmental officer.
7
-
-
Supply and laying of 4 X 16 Sq.mm PVC armoured LTUG Cable in a trench to be excavated at a depth of 0.75 metre putting 0.15 metre layer of sand and covering the cable completely eith bricks and sand refilling the earth to make good etc complete in all respects as directed by the departmental officer.
560
-
-
Supply and run of 25mm X 6mm GI flat down conductor with necessary clamps / supports on wall/ floor/ ground for earth connection etc complete in all respects as directed by the departmental officers.
490
-
-
Supplying and fixing of 5 A /15A 3 pin flush type wall socket with15A flush type switch concealed in suitable MS box in flush with wall and covered with 3mm thick hylem sheet including cost of wall socket, switch and labour charges fo wall cutting, grouting, flushing and making good, painting with primary and finishing coat for MS box etc., complete in all respects as directed by the departmental officers.
42
-
-
Supply and run off 2 of 2.50 sq.mm PVC insulated single core unsheathed copper conductor cable of 1100V grade with ISI mark confirming to IS:694/1990 with continuous earth connection by means of 1.50 sqmm PVC insulated single core unsheathed copper conductor cable confirming to IS:694/1990 in suitable PVC rigid pipe 1.8mm thick concealed on walls and ceiling for mains including the cost of cable, PVC pipes and specials, cement, brass screws, TW plugs, saddles and labour etc., complete in all respects as directed by the departmental officers.
175
-
-
Open Earth work excavation for foundation with all leads and lifts in all soils and subsoil’s to the required depth as may be directed except hard rock requiring blasting inclusive of shoring strutting and bailing out water wherever necessary refilling the sides of foundation with excavated earth in layers of 15 cm thickness well consolidated depositing the surplus earth in places shown and leveling the site with all initial leads and lifts etc complete complying with relevant standard specification etc complete in all respects as directed by departmental officers.
21
-
-
Filling in foundation and basement with Gravel in layers not exceeding 15 cm thick well watered rammed and consolidated complying with relevant standard specification including the cost of supplying Gravel etc., complete in a respects as directed by the departmental officers
7
-
-
Cement concrete 1:4:8 (one of cement, four of M-sand and eight of hard broken stone) using 40mm size hard broken stone inclusive of shoring, strutting, bailing out water, ramming, curing, etc complete in all respect as directed by the departmental officers.
3
-
-
Providing and laying in position, Standardized Concrete Mix M-25 Grade in accordance with IS 456-2000, using 20mm and downgraded hard broken granite stone jelly for all RCC tems of works with minimum cement content of 350 kg/m3 and maximum water cement ratio of 0.45, including admixture (plasticizer super plasticizer) recommended proportions as per IS:9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability with about (5.0 cu.m.) 7730 kg. of 20mm machine crushed stone jelly and with about (3.3 cu.m.) 5156 kg of 10-12mm machine crushed stone jelly and with about (4.79 cu.m.) 7670 kg of M-Sand, but excluding cost of reinforcement gril and fabricating charges, centering and shuttering and also including laying. vibrating with mechanical vibrators, finishing. curing. etc. and providing fixtures like fan clamps in the RCC floor roof slabs wherever necessary without claiming extra, etc complete complying with standard specification and as directed by the departmental officers. The coarse and fine aggregates to be used should comply with the requirements of IS Standards. (No separate payment will be made by the Department for the excess usage of materials) In All floors.
10
-
-
Supplying fabricating and placing the following kinds of steel grills for reinforcement Fe 500D Grade steel reinforcement bars as per IS 786:1979 for all reinforced cement concrete works such as plinth beam, lintels, beams, sunshade, roof and floor slabs etc., including cost of steel and fabricating the reinforcement grills in position etc., complete in all respect as directed by the departmental officer ( In all floors) (The rate to include the cost of binding wire steel also, steel rods for all sizes)
1.2
-
-
Providing form work for centering, shuttering etc., for all reinforced concrete work such as plinth beam, raft beam, raft slab, grade beam etc., including strutting and shuttering wherever required using MS sheets of suitable size of BG 10, stiffened with MS angle of size 25mm x 25mm x 3mm laid over silver oak (Country wood) joists of size 10cm x 6.5 cm (Spaced about 91cm center to center) distance and supported by casurina props of size 10cm-13cm dia (spaced at 75 cm center to center) and removing the same after a specified period without damaging RCC works in all floors etc., complete in all respects as directed by the departmental officer. (for column footing, Grade beam / Plinth beam)
6
-
-
Providing form work for centering, shuttering etc., for all reinforced concrete work like slab, beams, lintels, loft etc., including shuttering, upto 3.00m high using MS sheet of size 90cm x 60cm and BG 10, stiffened with MS angle of size 25mm x 25mm x 3mm laid over silver oak (Country wood) joists of size 10cm x 6.5 cm (Spaced about 91cm center to center) distance and supported by casurina props of size 10cm-13cm dia (spaced at 75 cm center to center) and removing the same after a specified period without damaging RCC works in all floors etc., complete in all respects as directed by the departmental officer. (For Slabs, Lintels & Lofts)
16
-
-
Providing form work for centering, shuttering etc., for all reinforced concrete work like lintels, window boxing etc., including shuttering, upto 3.00m high using MS sheet of size 90cm x 60cm and BG 10, stiffened with MS angle of size 25mm x 25mm x 3mm laid over silver oak (Country wood) joist of size 10 cm x 6.5 cm (spaced about 91cm centre to centre) distance and supported by casurina props of size 10cm to 13cm dia (spaced at 75cm centre to centre) and removing the same after a specified period without damaging RCC works in all floors etc complete in all respects as directed by the departmental officer. (Sunshade/Window/Boxing / column)
16
-
-
Supply andfixing brass cable gland for 3 ½ x 70 sq. mm PVC armoured LTUG cable with earth connection etc complete in all respects as directed by the departmental officers.
4
-
-
Supply, erection testing, commissioning and handing over of 1No,62.5 KVA diesel generator set 0.80 P.F, 3phase, 415v/420 Volts, 50c/s, 1500 RPM complete in all respects as detailed below A.Engine Air Cooled diesel engine suitable for generator application with a shaft out put of 84HP/50KW suitable at 1500 RPM under NTP conditions as per BSS 5414-ISO 10000. The engine shall comprise the following standard scope of supply: (Make Kirloskar/ Cummins/ Ashok Leyland/ Greaves/ Equivalent) 1) Dry type Air cleaner, 2) Expansion bellow, 3) Radiator, radiator fan and mounting, 4) Air to air charge cooler, 5) Exhaust gas turbo charger, 6) Lube oil cooler and lube oil filter filter 7) Fuel filter (pre and micro), 8) In-line mono-block fuel injection pump with governor and fuel feed pump, 9) Electronic governor, 10) 12V / 24V battery charging alternator, 11) 12V / 24V Volt electric starter motor, 12) Engine test certificate, 13) Residential Mufler and 14) Fly wheel with starter ring.
(C)ENGINE INSTRUMENT PANEL MOUNDING Engine instrument panel /mounted engine control panel consisting of ON/OFF/START/KEY, lube oil pressure gauge, oil temperature gauge, high water temperature gauge and electronic hour Mtr and RPM indicator. Safety system of Engine: The engine shall trip for the following conditions with Visual alarm device: 1) Low lubricating oil pressure, 2) High water temperature, 3) Vee- belt failure and over speed and 4) Low battery indicationThe Engine should be capable of Providing 10% over load for one hour for every 11 hours Continuous Running at full load. (D) ALTERNATOR: 62.5 KVA capacity of brushless alternator AC 3 phase 50 c/s 415 volts, 0.8 PF 1500 RPM under NTP conditions confirming to IS 13364 (part II) 1992 to be means of coupling.
(H)ACOUSTIC ENGLOSURE : Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS Sheet . The silent canopy shall be of nut bolt type construction. Critical processes of punching are done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm . Power coating is done after seven – tank surface preparation process of sheet metal canopy panel and doors shall have inside lining of Fire Retardant 64 Kg / Cu Mt Density Mineral wool of 100 mm thick ness as acoustic material . Four hinged doors shall be provided to canopy. The maximum permissible sound pressure level should be as per the norms prescribed by the central pollution control board/state pollution control Board/Competent Authority concerened or shouble be 75 db (A) at 1 mtr from the enclosure surface whichever is advantageous to the department. The emergency stop should be available on the enclosure panel The Engine Manufacturer of the Engine provided for diesel Generator sets mounted inside and should be to the satisfaction of inspection / testing authority concern. SURFACE TREATMENT – PAINTING: The enclosure surface hall be suitably treated for degreasing . degusting and posphating . The canopies are passed thought seven – tank treatment thoroughly. ADDITIONAL FEATURES OF CANOPIES :-
Canopy fabricated on CNC machine with dimensional accuracy of 0.1 mm so as to increase its durability . special designed supporting rips / structures are used in canopies so as to give sturdiness and to reduce the vibrations of the DG sets if any. WORLD CLASS COOLING PACKAGE:- Canopies shall have cooling package for which it can also perform at 45 deg c / ambient Temperature. No grouting required on the ground , only a level surface capable of with standing the DG weight . Lifting hooks shall be provided for the acoustic enclosure , which should unloaded independent of the DG set . the Gen set base frame shall also provided with hooks for unloading. TEMPERATURE RISE INSIDE THE CANOPY Canopies shall be designed so as to maintain the temperature difference between ambient and air inlet at air cleaner with the enclosure well within 5 – 7 Degree Centigrade. (G)BASS FRAME: Base frame should be fabricated MS Channel sheet Metal , The base frame is rigged in construction and designed for mounting engine and brush less alternator closely coupled . with cross members mounted on AVM . The base frame shall have provision for mounting of acoustic enclosure on it . The supply of Gen set includes loading , unloading and transportation charges. 6) Fuel Tank. 150 Ltrs. Removable Fuel tank shall be fabricated out of 14 SWG CRCA MS sheet and is part of base frame. It is duly painted and fitted with inlet an outlet connections and mechanical fuel gauge. Fuel tank can be easily removed for cleaning or any maintenance. 7) Battery - 12V 100 AH battery-1 NO
1
-
-
Supply and providing cable end termination of 3 ½ x 70 sq. mm PVC LTUG Aluminium armoured cable with necessary aluminium cable sockets by crimping etc. with electrical connection etc complete in all respects as directed by the departmental officers.
4
-
-
Supplying and laying of 3½ X 70 sq.mm PVC armoured aluminium LT UG Cable of approved brand having IS mark in a trench to be excavated to a depth of 0.75 meter, putting 0.15m layer of sand and covering the cable completely with bricks and sand and refilling the earth to make good etc., complete in all respects as directed by the departmental officer.
170
-
-
Earthing as per ISI Specification with an earth electrode of 2.1mt class 'B' GI pipe of dia not less than 40mm and with 20mm dia copper earth flat of size125mm x50mmx6mm, with funneling arrangement using charcoal, common salt, G.I.reducer, check nuts etc., and mansonry work and providing RCC coverslab 38mm thick for the Brick mansory including cost of steel and fabrication of reinforcement etc., complete in all respectes as directed by the departmental officers.
2
-
-
Supplying and run off 8 SWG copper wire on walls or below ground level with necessary 'U' nail,earth work excavation and refilling inclusive of the costll materials etc complete in all respects as directed by the departmental officers
30
-
-
Added GST of 18% (All Items)
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements